Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-09 Cont ID  
Sent By pkrauss Date 2003-07-09 Time 14:54 Rev Time 0.15
Received By pkrauss Date 2003-07-09 Time 14:54 Sent To  
Notes
2003-07-09 00:00:00SUBMITTAL LTR ON HOOD #2 INCREASING
 FPM TO 1,525

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-08 Cont ID  
Sent By nmccray Date 2003-07-07 Time 15:57 Rev Time 0.50
Received By pkrauss Date 2003-07-08 Time 16:12 Sent To  
Notes
2003-07-08 00:00:00PLEASE CLARIFY HOOD #2 DUCT VELOCITY
 INDICATES 1,059 FPM - AS PER 2001 FBC(M)
 506.3.6, VELOCITY SHALL BE NOT LESS THAN
 1,500 FPM AND NOT GREATER THAN 2,500
 FPM.SPOKE WITH MIKE FROM HOOD DEPOT
 ENGINEER TO CORRECT PROBLEM & SUBMIT
 AN AMMENDED CALCULATION FOR HOOD # 2
 PLANS WILL THEN BE APPROVED.