Plan Review Details - Permit 03062200
Plan Review Stops For Permit 03062200
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-12 Cont ID  
Sent By hpiskura Date 2003-07-12 Time 11:00 Rev Time 0.00
Received By hpiskura Date 2003-07-12 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-03 Cont ID  
Sent By dpalmer Date 2003-10-03 Time 15:37 Rev Time 0.33
Received By dpalmer Date 2003-10-03 Time 15:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-26 Cont ID  
Sent By dpalmer Date 2003-09-26 Time 16:40 Rev Time 0.25
Received By dpalmer Date 2003-09-26 Time 16:40 Sent To  
Notes
2003-09-26 00:00:00*********** UNSAT ************
  
 1)NOTE: PLANS NEED TO BE SIGNED, DATED
 AND SEALED BY ENGINEER OF RECORD.
 61G15-23.002/ 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-15 Cont ID  
Sent By dpalmer Date 2003-07-15 Time 10:00 Rev Time 0.50
Received By dpalmer Date 2003-07-15 Time 10:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-08-14 Cont ID  
Sent By nmccray Date 2003-08-14 Time 10:48 Rev Time 0.00
Received By nmccray Date 2003-08-14 Time 10:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-26 Cont ID  
Sent By csiegber Date 2003-09-26 Time 12:06 Rev Time 0.00
Received By csiegber Date 2003-09-26 Time 12:06 Sent To  
Notes
2003-09-26 00:00:00TO COMM BD#64

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 10:44 Rev Time 0.00
Received By alange Date 2003-07-30 Time 10:44 Sent To  
Notes
2003-07-30 00:00:00TO COMM BD # 17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-07-01 Time 12:42 Rev Time 0.00
Received By shernand Date 2003-07-01 Time 12:42 Sent To  
Notes
2003-07-01 00:00:00COMM BOARD #41

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-09-30 Cont ID  
Sent By pkrauss Date 2003-09-30 Time 12:04 Rev Time 0.45
Received By pkrauss Date 2003-09-30 Time 12:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-08-21 Cont ID  
Sent By pkrauss Date 2003-08-21 Time 10:00 Rev Time 0.35
Received By pkrauss Date 2003-08-21 Time 10:00 Sent To  
Notes
2003-08-21 00:00:00PLANS APPROVED 8-19-03 / DONNA
 INSERTED REVISED PAGES INTO RESUB PLANS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-08-18 Cont ID  
Sent By pkrauss Date 2003-08-18 Time 13:39 Rev Time 0.40
Received By pkrauss Date 2003-08-18 Time 13:39 Sent To  
Notes
2003-08-18 00:00:00CALLED SCOTT DAY (GC) - PLANS ARE NOT
 COMPLETE.PLANS RESUBMITTED WITHOUT
 ORIGINAL PERMIT APPLICATION AND THE
 COMPLETE SET OF PLANS.ONLY THE PAGES
 WITH CHANGES SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-07-15 Cont ID  
Sent By pkrauss Date 2003-07-15 Time 10:43 Rev Time 0.40
Received By pkrauss Date 2003-07-15 Time 10:38 Sent To  
Notes
2003-07-15 00:00:00DENIED:
  
 PLAN SHEET M3 PENETRATIONS TO THE AUDIO
 POST AND MIXING ROOM.SIDE WALL GRILLES
 ARE REQUIRED TO HAVE FIRE DAMPER AS PER
 2001 FBC(M) 607.1.2.PLEASE PROVIDE
 MANUFACTURER INSTALLATION INSTRUCTIONS
 ON THE JOBSITE AT TIME OF INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-08-21 Cont ID  
Sent By kstevens Date 2003-08-21 Time 14:40 Rev Time 1.00
Received By kstevens Date 2003-08-21 Time 14:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-08-14 Cont ID  
Sent By kstevens Date 2003-08-14 Time 13:38 Rev Time 0.75
Received By kstevens Date 2003-08-14 Time 13:38 Sent To  
Notes
2003-08-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) ORIGINAL PLANS/APPLICATION NOT SUB-
 MITTED WITH RESUBMITTAL.
 2) LOOS SHEETS AS SUBMITTED NOT ACCEPT-
 ABLE. 2 COMPLETE SETS SHALL BE SUBMITTED
 FOR REVIEW. REMOVE ALL OLD SHEETS AND
 INSERT NEW SHEETS. SUBMIT A SET OF OLD
 SHEETS FOR COMPARISON. SEC 140.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-15 Cont ID  
Sent By kstevens Date 2003-07-15 Time 07:45 Rev Time 1.00
Received By kstevens Date 2003-07-14 Time 16:45 Sent To  
Notes
2003-07-15 00:00:00DENIED
  
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 BLDG.
  
 1) SHT A1 RADIO STUDIO, SUBMIT CALCULAT-
 IONS FOR MINIMUM FACILITIES PER TABLE
 1003.1 (BLDG.) AND TABLE 403.1 (PLMG.)
 2) SHT A2 PERTABLE 403.1 A DRINKING
 FOUNTAIN IS REQUIRED.
 3) SHT A3 TOILET ROOM ELEVATIONS, HEIGHT
 FOR W/C SHALL BE 17" TO 19" PER SECTION
 11-4.16.3. PLEASE INDICATE ON PLANS.
 4) SHT P1 PLUMBING SPECIFICATIONS #3,
 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 DELETE FROM REFERENCE.
 5) SHT P2 ALL CAPPED PIPING SHALL BE IN-
 SPECTED PRIOR TO COVERING.
 6) SHT P2 DOMESTIC WATER ISOMETRIC RISER
 AIR CHAMBERS ARE NOT APPROVED. WATER
 HAMMER ARRESTORS REQUIRED ONLY PER SEC.
 604.9 AT QUICK CLOSING VALVES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692