Plan Review Details - Permit 03062190
Plan Review Stops For Permit 03062190
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-12 Cont ID  
Sent By hpiskura Date 2003-07-12 Time 09:26 Rev Time 0.00
Received By hpiskura Date 2003-07-12 Time 09:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-15 Cont ID  
Sent By dpalmer Date 2003-07-15 Time 09:09 Rev Time 1.00
Received By dpalmer Date 2003-07-15 Time 09:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-16 Cont ID  
Sent By mcarsill Date 2003-07-16 Time 17:05 Rev Time 0.00
Received By mcarsill Date 2003-07-16 Time 17:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-28 Cont ID  
Sent By alange Date 2003-07-28 Time 13:34 Rev Time 0.00
Received By alange Date 2003-07-28 Time 13:34 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-07-01 Time 09:18 Rev Time 0.00
Received By shernand Date 2003-07-01 Time 09:18 Sent To  
Notes
2003-07-01 00:00:00COMM BOARD #7

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-09 Cont ID  
Sent By pkrauss Date 2003-07-09 Time 08:24 Rev Time 0.30
Received By pkrauss Date 2003-07-09 Time 07:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-09 Cont ID  
Sent By kstevens Date 2003-08-09 Time 08:25 Rev Time 1.50
Received By kstevens Date 2003-08-09 Time 08:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-09 Cont ID  
Sent By alange Date 2003-07-28 Time 13:34 Rev Time 1.00
Received By kstevens Date 2003-07-09 Time 14:13 Sent To  
Notes
2003-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 A) SEPARATE DEMO PLUMBING PERMIT REQUIR-
 ED. ALL PIPING CAPPED OFF SHALL BE IN-
 SPECTED PRIOR TO COVERING.
 1) SHT A-2 DETAIL #3 RESTROOM ELEVATION,
 SHOW HEIGHT OF W/C SECTION 11-4.16.3 AND
 FLUSH CONTROL LOCATION 11-4.16.5
 2) SHT A-3 PLUMBING NOTES: AIR CHAMBERS
 ARE NOT APPROVED. DELETE FROM REFERENCE.
 SECTION 604.9
 3) SHT A-3 PLUMBING PLAN & RISER DIAGRAM
 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. DRINKING FOUNTAIN SHALL BE
 VENTED SEPARATELY. SECTION 909.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721