Plan Review Details - Permit 03062036
Plan Review Stops For Permit 03062036
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-02-13 Cont ID  
Sent By rmcdouga Date 2004-02-13 Time 16:30 Rev Time 1.00
Received By rmcdouga Date 2004-02-13 Time 16:30 Sent To  
Notes
2004-02-13 00:00:00REVISED SHEETS 4,12,& 13 ARE OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-02-13 Time 15:21 Rev Time 1.00
Received By rmcdouga Date 2004-01-28 Time 12:27 Sent To M
Notes
2004-01-28 00:00:00REVISION DENIED
  
 1) ENERGY CALCULATION FORM IS REQUIRED
 TO BE SIGNED AND DATED BY THE OWNER/
 AGENT. FBC CHAPTER 13.
  
 2) REVISE SHEET 3 WHICH HAS THE SQUARE
 FOOTAGE SCHEDULE FOR THE STRUCTURE.
  
 3) HAVE THE REVISED PLANS STAMPED BY
 PALM BEACH COUNTY FOR IMPACT FEES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-14 Cont ID  
Sent By csiegber Date 2004-01-27 Time 12:39 Rev Time 3.00
Received By rmcdouga Date 2003-08-14 Time 09:22 Sent To  
Notes
2003-08-14 00:00:00BUILDING PROVISO
  
 1) SUBMIT 2 COPIES OF SOIL BORING TEST
 REPORT AS REQUIRED BY FBC 1804.2.2 AND
 SHEET 5 OF THE PLANS, PRIOR TO POURING
 THE FOUNDATION FOR ADDITION.
  
 2) A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE STORM PANELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-29 Cont ID  
Sent By alange Date 2003-08-13 Time 13:32 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-07-29 00:00:00DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO COPIES OF A SURVEY OR A
 SITE PLAN SIGNED AND SEALED BY THE
 DESIGNER OF RECORD.
  
 4) THE ELEVATIONS ON SHEETS 12 AND 13
 ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE DESIGNER OF RECORD AND HAVE HIS
 TITLE BLOCK.
  
 5) PROVIDE SPECIFICATIONS FROM THE
 WINDOW MANUFACTURER THAT PROVIDE THE
 CLEAR OPENING AREA AND DIMENSIONS FOR
 THE CASEMENT WINDOWS TO ASSURE
 COMPLIANCE WITH FBC 1005.4. THE PLAYROOM
 NURSERY, MAID'S ROOM, BEDROOM #5, AND
 ALL OTHER SLEEPING ROOMS ARE REQUIRED TO
 HAVE EMERGENCY EGRESS.
  
 6) FIREBLOCKING IS REQUIRED AT THE
 CONCEALED SPACES BETWEEN THE STAIR
 STRINGERS AT THE TOP AND BOTTOM OF RUNS
 PER FBC 2305.1.4.
  
 7) TREADS LESS THAN 10" ARE REQUIRED TO
 HAVE A NOSING OF APPROXAMATELY 1" PER
 FBC 1007.3 EXCEPTION 1.
  
 8) THE GUARDRAIL AT THE SIDE OF OPEN
 STAIRS IS REQUIRED TO BE A MIN. OF 36"
 HIGH PER FBC 1015.1 AND 1026.5. IT
 APPEARS YOU MAY HAVE GUARDRAILS CONFUSED
 WITH HANDRAILS ON SHEET 5. PLEASE
 CORRECT.
  
 9) FBC 1015.3 STATES THAT A SIX INCH
 SPHERE SHALL NOT PASS THROUGH THE
 TRIANGULAR OPENING FORMED BY A TREAD,
 RISER AND THE BOTTOM OF A GUARDRAIL.
  
 10) FBC 1609.4 DOES NOT ALLOW THE ONE-
 THIRD INCREASE IN THE STEEL CALCULATIONS
 FOR TRUSS CONNECTORS. PLEASE REVISE THE
 UPLIFT VALUES IN THE CONNECTOR SCHEDULES
 ON SHEETS 8 AND 9. SEE THE 2003 USP OR
 2002 SIMPSON HIGH WIND-RESISTANT CONST.
 CATALOGS FOR VALUES THAT DO NOT INCLUDE
 A 1/3 INCREASE ON THE STEEL CALCULATIONS
  
 11) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. INDICATE
 THE ANCHOR TYPES, SPACING, MOUNT TYPE,
 PANEL SPANS, PRESSURES, ETC.
  
 12) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE HUNG WINDOW (IMPACT)
 - ARCHED TOP FIXED GLASS WINDOWS(IMPACT)
  
 13) PLEASE CLARIFY WHY THE PRODUCT
 APPROVAL FOR AN OVERHEAD GARAGE DOOR
 WITH A MAXIMUM WIDTH OF 9' WAS SUBMITTED
 BOTH DOORS ARE EXISTING AND ARE LARGER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-02-05 Cont ID  
Sent By btrobaug Date 2004-02-05 Time 12:05 Rev Time 0.50
Received By btrobaug Date 2004-02-05 Time 11:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-16 Cont ID  
Sent By btrobaug Date 2003-07-16 Time 17:11 Rev Time 0.50
Received By btrobaug Date 2003-07-15 Time 08:43 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-13 Time 15:20 Rev Time 0.00
Received By csiegber Date 2004-02-13 Time 15:20 Sent To B
Notes
2004-02-13 00:00:00TO RM DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 12:39 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 12:39 Sent To B
Notes
2004-01-27 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-13 Cont ID  
Sent By alange Date 2003-08-13 Time 13:31 Rev Time 0.00
Received By alange Date 2003-08-13 Time 13:31 Sent To B
Notes
2003-08-13 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-30 Cont ID  
Sent By mmclean Date 2003-07-02 Time 15:02 Rev Time 0.00
Received By shernand Date 2003-06-30 Time 16:49 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-02-05 Cont ID  
Sent By pkrauss Date 2004-02-05 Time 11:13 Rev Time 0.20
Received By pkrauss Date 2004-02-05 Time 11:13 Sent To  
Notes
2004-02-05 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
  
 PLEASE NOTE, MECHANICAL PLANS REQUIRED.
 PLANS INDICATE A/C CONTRACTOR TO SUBMIT
 PLANS.PROVIDE PLANS INDICATING NEW
 DUCTWORK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-18 Cont ID  
Sent By rmcdouga Date 2004-01-28 Time 12:51 Rev Time 0.25
Received By pkrauss Date 2003-07-18 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-07-17 Cont ID  
Sent By btrobaug Date 2003-07-16 Time 17:12 Rev Time 0.50
Received By kstevens Date 2003-07-17 Time 14:49 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-07-02 Cont ID  
Sent By shernand Date 2003-06-30 Time 16:49 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***