Plan Review Details - Permit 03061872
Plan Review Stops For Permit 03061872
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-17 Cont ID  
Sent By hpiskura Date 2003-09-17 Time 10:04 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-09-17 00:00:00CAN WASH REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-12 Cont ID  
Sent By kstevens Date 2003-09-11 Time 18:01 Rev Time 0.00
Received By hpiskura Date 2003-07-12 Time 09:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-02-26 Cont ID  
Sent By dpalmer Date 2004-02-26 Time 06:48 Rev Time 0.33
Received By dpalmer Date 2004-02-26 Time 06:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:24 Rev Time 0.50
Received By dpalmer Date 2004-02-12 Time 07:31 Sent To  
Notes
2004-02-12 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE SEE ONLY ONE SET/PAGE
 WAS SUBMITTED FOR REVIEW.
 PLEASE SUBMIT A MIN OF TWO SIGNED,
 DATED AND SEALED COPIES PER FS.
  
 2)NOTE: PLEASE SEE FS 471.023 AND
 FAC 61G15-23.002. PLEASE INCLUDE ALL
 INFORMATION IN TITLE BLOCK PER FS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-14 Cont ID  
Sent By csiegber Date 2004-02-06 Time 12:21 Rev Time 0.50
Received By dpalmer Date 2003-07-14 Time 08:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-11 Cont ID  
Sent By mcarsill Date 2003-07-11 Time 13:20 Rev Time 0.00
Received By mcarsill Date 2003-07-11 Time 13:20 Sent To  
Notes
2003-07-11 00:00:001) SEPARATE PERMITS
 REQUIRED FOR NEW HOOD, DUCT, AND
 EXTINGUISHING SYSTEM.
  
 2) CLEAN-OUTS ARE REQUIRED IN EXHAUST
 DUCT WHERE CHANGE OF DIRECTIONS OCCUR.
  
 3) PROPER CLEARANCES ARE REQUIRED TO
 EXHAUST DUCT TO ANY COMBUSTIBLE
 MATERIALS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 805-6722
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-17 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:24 Rev Time 0.00
Received By csiegber Date 2004-02-17 Time 16:24 Sent To E
Notes
2004-02-17 00:00:00TO DP SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 12:21 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 12:21 Sent To E
Notes
2004-02-06 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 14:13 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 14:13 Sent To P
Notes
2003-09-30 00:00:00TO KS BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-09-03 Time 15:36 Rev Time 0.00
Received By csiegber Date 2003-09-03 Time 15:42 Sent To P
Notes
2003-09-03 00:00:00TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-24 Cont ID  
Sent By alange Date 2003-07-24 Time 14:44 Rev Time 0.00
Received By alange Date 2003-07-24 Time 14:44 Sent To  
Notes
2003-07-24 00:00:00TO COMM BD. 40

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 13:05 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 13:05 Sent To  
Notes
2003-06-26 00:00:00COMM BOARD #31

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-29 Cont ID  
Sent By pkrauss Date 2003-07-29 Time 07:01 Rev Time 0.40
Received By pkrauss Date 2003-07-29 Time 07:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-07-09 Cont ID  
Sent By pkrauss Date 2003-07-09 Time 09:58 Rev Time 0.40
Received By pkrauss Date 2003-07-09 Time 09:57 Sent To  
Notes
2003-07-09 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
  
 1.PLAN SHEET M-1.0 INDICATES A FIRE
 DAMPER ON THE MAKE-UP AIR (SUPPLY) TO
 THE HOOD.PLEASE CLARIFY WHY THIS IS
 NECESSARY.
  
 2.PROVIDE INFORMATION ON CLEARANCE
 TO COMBUSTIBLES.GREASE DUCT SYSTEMS
 SHALL HAVE A CLEARABCE TO COMBUSTIBLE
 CONSTRUCTION OF NOT LESS THAN 18 INCHES.
  
 4.ADDITIONAL PERMIT AND PLANS REQUIRED
 FOR FIRE SUPPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-10-11 Cont ID  
Sent By kstevens Date 2003-10-11 Time 10:56 Rev Time 0.50
Received By kstevens Date 2003-10-11 Time 10:56 Sent To  
Notes
2003-10-11 00:00:00REVISION OK - MOVED JANITOR SINK (SERV-
 ICE SINK)

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-09-11 Cont ID  
Sent By csiegber Date 2003-09-30 Time 14:13 Rev Time 1.00
Received By kstevens Date 2003-09-11 Time 17:57 Sent To B
Notes
2003-09-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) CAN WASH SHALL DRAIN TO GREASE INTER-
 CEPTOR.
 2) CAN WASH SHALL BE PROTECTED FROM
 STORM WATER FROM ENTERING THE SANITARY
 SEWER SYSTEM. PLEASE INDICATE HOW THIS
 WILL BE DONE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-30 Cont ID  
Sent By csiegber Date 2003-09-03 Time 15:43 Rev Time 2.50
Received By kstevens Date 2003-07-30 Time 16:24 Sent To  
Notes
2003-07-30 00:00:00PASSED/PROVISO
  
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 PER PDI-WH 201 AND MANUFACTURE INSTALL-
 ATION INSTRUCTIONS
  
 SEPARATE GAS PERMIT REQUIRED. - INFOR-
 MATION REQUIRED AT TIME OF APPLICATION -
 MANUFACTURE SPECIFICATION SHEETS SHOWING
 LISTING OF APPLIANCE AND BTU'S
  
 DEMO PERMITS REQUIRED FOR PLUMBING AND
 GAS DEMO. ALL CAPPED PIPING SHALL BE IN-
 SPECTED PRIOR TO COVERING.
  
 WATER FILTER FOR KITCHEN EQUIPMENT SHALL
 BE NSF COMPLIANT. MANUFACTURE SPECIFICAT
 ION SHEET REQUIRED SHOWING "NSF APPROVAL
 AT TIME OF PLUMBING FINAL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-08 Cont ID  
Sent By kstevens Date 2003-07-08 Time 12:26 Rev Time 3.00
Received By kstevens Date 2003-07-08 Time 12:26 Sent To  
Notes
2003-07-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 FUEL GAS
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) SHT P-0.1 PLUMBING GENERAL NOTES:
 #15 SHALL READ FBC-2001 CHAPTER 11
 #16 AIR CHAMBERS NOT APPROVED. DELETE
 FROM REFERENCE. 604.9
 PLAN NOTES #4 AIR CHAMBERS NOT APPROVED.
 DELETE FROM REFERENCE. 604.9
 2) SHT P-0.1 PLUMBING SYSTEM INSTALLAT-
 ION NOTES: TABLE 704.1 - 2-1/2" AND
 SMALLER PIPE SHALL SLOPE AT 1/4" PER FT.
 3) SHT P-0.1 GAS PIPING INSTALLATION
 NOTES: #'S 1 AND 4, NFPA-54 HAS NOT BEEN
 ADOPTED. CHANGE REFERENCE TO READ FBC-
 2001 FUEL GAS. SEC 104.2.1
 4) SHT P-0.1 PLUMBING ABBREVIATIONS AND
 PLUMBING SYMBOLS, AIR CHAMBERS ARE NOT
 APPROVED, REMOVE FROM CHARTS.104.2.1
 5) SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION REQUIRED FOR GAS
 PERMIT. SECTION 104.2.1
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. SHOW ALL PIPING BACK TO
 METER.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARD NFPA 58, AND THE FBC-2001 FUEL
 GAS CODE SEC 402.2.
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. SHOW UNION
 BETWEEN MANUAL VALVE AND SOLENOID VALVE.
 **EXISTING GAS THROUGH SLAB NOT ALLOWED
 PER SECTION 404.6. PIPING SHALL NOT BE
 INSTALLED IN SOLID FLOOR SLABS, SUCH AS
 CONCRETE OR MASONRY, EXCEPT WHERE THE
 CODE OFFICIAL DETERMINES THAT THERE IS
 NO OTHER PRATICAL MANNER OF INSTALLING
 SUCH PIPING. FOR THIS TYPE OF FLOOR CON-
 STRUCTION, THE HOUSE PIPING SHALL BE IN-
 STALLED ABOVE THE FLOOR, IN AN OPEN OR
 FURRED SPACE, HOLLOW PARTITION, HOLLOW
 WALL, ATTIC SPACE OR PIPE CHASE.
 6) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, INDUSTRIAL PRETREATMENT FOR
 SIZING OF THE GREASE INTERCEPTOR. WASTE
 ORD #2938-96. (561) 837-4074
 7) SHT P-1.0 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 8) SHT P-1.0 DEMOLITION KEYED NOTES: #'S
 1, 2, 3, 6, & 8 NOT SHOWN ON DEMO PLAN.
 PLEASE CLAIRFY. SEC 104.2.1
 9) SHT P-1.0 KITCHEN EQUIPMENT, WATER
 FILTER SHALL BE "NSF" APPROVED. SUBMIT
 MANUF. INFORMATION.SEC 303.4
 10) SHT P-2.0 GREASE RISER DIAGRAM, ALL
 INDIRECT WASTE SHALL DRAIN INTO A FLOOR
 SINK. SECTION 802.3 - FLOOR DRAINS ARE
 NOT APPROVED INDIRECT WASTE RECEPTORS.
 11) SHT P-5.1 WATER HEATER DETAIL, SEC
 607.3.2 THERMAL EXPANSION CONTROL REQD.
 SUBMIT DETAIL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692