Plan Review Details - Permit 03061836
Plan Review Stops For Permit 03061836
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-08 Cont ID  
Sent By sthyng Date 2003-08-08 Time 12:13 Rev Time 0.50
Received By sthyng Date 2003-08-08 Time 12:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-03 Cont ID  
Sent By dpalmer Date 2003-08-08 Time 05:51 Rev Time 0.25
Received By sthyng Date 2003-07-03 Time 17:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-08 Cont ID  
Sent By dpalmer Date 2003-08-08 Time 05:51 Rev Time 0.25
Received By dpalmer Date 2003-08-08 Time 05:50 Sent To B
Notes
2003-08-08 00:00:00NEW SHEETS,
 PASSED ON ORIG REVIEW.
 RE-STAMPED FOR ELECTRICAL.
 SENT TOP S. THYNG

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-02 Cont ID  
Sent By mmclean Date 2003-08-05 Time 10:13 Rev Time 0.33
Received By btrobaug Date 2003-07-02 Time 12:13 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-30 Cont ID  
Sent By alange Date 2003-07-30 Time 14:19 Rev Time 0.00
Received By alange Date 2003-07-30 Time 14:19 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 09:09 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 09:09 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-05 Cont ID  
Sent By kstevens Date 2003-08-05 Time 10:06 Rev Time 0.50
Received By kstevens Date 2003-08-05 Time 10:06 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By alange Date 2003-07-30 Time 14:19 Rev Time 1.00
Received By kstevens Date 2003-07-01 Time 08:27 Sent To E
Notes
2003-07-01 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 3) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 6) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 2 Status P Date 2003-08-05 Cont ID  
Sent By mmclean Date 2003-08-05 Time 10:13 Rev Time 0.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-26 Cont ID  
Sent By kstevens Date 2003-08-05 Time 10:06 Rev Time 1.00
Received By mmclean Date   Time   Sent To P
Notes
***NONE***