Plan Review Details - Permit 03061823
| Plan Review Stops For Permit 03061823 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-15 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-15 |
Time |
14:10 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-06-25 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-25 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-25 |
Time |
14:19 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-09-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-23 |
Time |
14:57 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-09-23 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2003-09-23 00:00:00 | | | | | | | | | | | | | PER N. MELICK MANUFACTURE INFO | | | NOT REQUIRED FOR 1 & 2 FAMILY HOMES. | | | JULY 17, 2002 OFFICAL INTERPRETATION. | | | THE FIELD INSPECTOR SHALL VERIFY THE | | | INSTALLED EQUIPMENT INPUT DOES NOT EX- | | | CEED THE PIPE SIZING. | | | | | | IF DRYER ROOM IS A CONFINED SPACE, | | | OPENINGS REQUIRED PER SECTION 304.3.1 0R | | | SECTION 304.3.2 SHALL BE INSTALLED. | | | MINIMUM 1,000 CUBIC FEET REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-06-30 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-15 |
Time |
14:10 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-06-30 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2003-06-30 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | A) THE FOLLOWING INFORMATION REQUIRED AT | | | TIME OF APPLICATION FOR GAS PERMIT. | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 3. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | 4. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | 5. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. (WATER HEATER) | | | 6. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
|