Plan Review Details - Permit 03061713
Plan Review Stops For Permit 03061713
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-02 Cont ID  
Sent By shill Date 2004-03-02 Time 12:05 Rev Time 0.50
Received By shill Date 2004-03-02 Time 12:05 Sent To  
Notes
2004-03-02 00:00:00MASTERED UNDER 04030004

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-11-18 Cont ID  
Sent By sthyng Date 2003-11-18 Time 12:55 Rev Time 1.50
Received By sthyng Date 2003-11-18 Time 12:14 Sent To  
Notes
2003-11-18 00:00:00******CORRECTIONS******
  
 SAMANTHA HILL (THYNG)
 BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEE PREVIOUS CORRECTION LISTS, ITEM
 #1.PROVIDE FIRE RATING INFORMATION
 FOR THE 1 1/2 HR. ENTRY DOORS.THE
 INSWING DOORS WERE SUBMITTED WITH NO
 FIRE RATING INFORMATION.
  
 2.)SEE PREVIOUS CORRECTION LISTS,
 ITEMS #2 AND #7 RESPECTIVELY,
 REGARDING FIRE RATING INFORMATION
 FOR THE DOORS (PREVIOUSLY LOUVERED)
 AT THE STORAGE ROOMS.IF SEPARATE
 PRODUCT APPROVALS AND FIRE RATING
 INFORMATION FOR THESE DOORS ARE NOT
 SUBMITTED, THEY WILL EITHER NOT BE
 COVERED UNDER THIS PERMIT OR WILL BE
 REQUIRED TO BE 90 MINUTE DOORS AS PER
 THE DOOR INFORMATION SUBMITTED.
  
 3.)THE FIRE RATING INFORMATION FOR THE
 OUTSWING DOOR DOES NOT REFER TO A TEST
 STANDARD OR A BRAND (OUTSWING DOOR).
  
 4.)AS PER CONVERSATION WITH THE
 ARCHITECT, PROVIDE AN ALTERNATE
 ANCHORING DETAIL FOR THE ARMOUR SCREEN,
 APPROVED BY BOTH THE ENGINEER FOR
 ARMOUR SCREEN AND THE DESIGNER OF
 RECORD.THE PRODUCT APPROVAL SHOWS TOP
 ANCHORING INTO A TIE BEAM OR A TRUSS,
 YOUR APPLICATION IS INTO THE BOTTOM OF
 A CONCRETE SLAB.
  
 5.)THE PRODUCT APPROVAL FOR THE
 ARMOUR SCREEN INCLUDES AN EXPIRED 3 PAGE
 COVER SHEET.REMOVE FROM THE PACKAGE
 AS THIS EXPIRED COVER SHEET IS NOT
 NEEDED.
  
 6.)SEE THE PREVIOUS CORRECTION LIST,
 ITEM #8, REGARDING THE HURRICANE SHUTTER
 INSTALLATION SCHEDULE.PER MY
 CONVERSATION WITH TONY GIZZI, HURRICANE
 SHUTTERS ARE NOT TO BE A PART OF THIS
 PERMIT PACKAGE.HOWEVER, HURRICANE
 SHUTTER PRODUCT APPROVALS WERE
 SUBMITTED.IF THE INSTALLATION
 SCHEDULE IS NOT SUBMITTED, HURRICANE
 SHUTTERS WILL REQUIRE A SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-10-29 Time 13:55 Rev Time 2.50
Received By sthyng Date 2003-10-03 Time 11:45 Sent To  
Notes
2003-10-03 00:00:00****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS CORRECTION LIST, ITEM
 #1.PROVIDE FIRE RATING INFORMATION
 FOR THE 1 1/2 HR ENTRY DOORS.
  
 2.)SEE PREVIOUS CORRECTION LIST, ITEM
 #7.PROVIDE FIRE RATING INFORMATION
 FOR THE LOUVERED DOORS.
  
 3.)AS PER THE CONVERSATION WITH THE
 ARCHITECT, YOU CANNOT SUBSTITUTE
 INSWING DOORS FOR OUTSWING DOORS.
 PROVIDE PRODUCT APPROVALS FOR THE
 OUTSWING ENTRY DOORS, WITH FIRE RATING
 INFORMATION.
  
 4.)THE PERMIT APPLICATION LISTS IMPACT
 SLIDING GLASS DOORS BUT PRODUCT
 APPROVALS WERE NOT SUBMITTED.THE
 PERMIT APPLICATON LISTS IMPACT AND NON
 IMPACT SINGLE HUNG WINDOWS, BUT PRODUCT
 APPROVALS WERE NOT SUBMITTED AND SINGLE
 HUNG WINDOWS ARE NOT ON THE PLAN.
  
 5.)THE PRODUCT APPROVALS FOR THE ARMOR
 SCREEN CONFLICT WITH THE ATTACHMENT
 DETAIL ON THE PLAN (A-DT4).
  
 7.)SEE THE ATTACHED IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION, ITEMS 13, 14 AND PROCEDURE
 I.
  
 8.)PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE (SEE ATTACHED).
 NOTE THAT THE LOUVERED DOORS REQUIRE
 IMPACT PROTECTION.
  
 9.)AS DISCUSSED, A PRE-STORM
 PREPARATION PLAN MUST BE SUBMITTED TO
 THE BUILDING OFFICIAL FOR APPROVAL
 BEFORE C.O.SUBMIT A LETTER, SIGNED
 BY THE QUALIFIER, INDICATING THAT YOU
 ARE AWARE OF THIS POLICY, ARE AWARE THAT
 ALL SHUTTERS MUST BE STORED ON SITE, AND
 ARE AWARE THAT THE PLAN MUST BE
 APPROVED BY THE BUILDING OFFICIAL BEFORE
 A C.O. WILL BE ISSUED.
  
 10.)SEE ATTACHED, ITEM #14.
 PERMANENTLY AFFIXED PROTECTIVE DEVICES
 SHALL REQUIRE THE WRITTEN APPROVAL OF
 THE BUILDING OFFICIAL.SUBMIT A LETTER
 ADDRESSED TO THE BUILDING OFFICIAL
 REQUESTING APPROVAL FOR THE USE OF THE
 ARMOR SCREEN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-25 Cont ID  
Sent By sthyng Date 2003-06-24 Time 13:44 Rev Time 2.50
Received By sthyng Date 2003-06-24 Time 13:44 Sent To  
Notes
2003-06-24 00:00:00******CORRECTIONS********
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE FIRE RATING INFORMATION
 FOR THE ENTRY DOOR.THIS DOOR IS
 REQUIRED TO BE A B-LABEL DOOR
 AS PER CBAA CASE NUMBER 1224 (SEE
 ATTACHED), WITH A DOOR CLOSER AS PER
 KEYNOTE 6, SHEET A-T3.1.
  
 2.)THE ARCHITECT OR ENGINEER OF
 RECORD IS TO REVIEW AND APPROVE THE
 PRODUCT APPROVALS.
  
 3.)A ROOF PERMIT IS REQUIRED FOR THE
 ROOFING WORK.EITHER HAVE THE ROOFING
 CONTRACTOR SIGN THE BACK OF THE
 APPLICATION, OR SUBMIT THE ROOF PRODUCT
 APPROVALS SEPARATELY WITH THE ROOF
 PERMIT APPLICATION.
  
 5.)TWO COPIES OF EACH PRODUCT APPROVAL
 ARE REQUIRED PER PERMIT (THREE WERE
 SUBMITTED).
  
 7.)SUBMIT PRODUCT APPROVALS FOR THE
 LOUVERED EQUIPMENT ROOM DOORS.THESE
 DOORS ARE REQUIRED TO BE 3/4 HOUR RATED
 FIRE DOORS; SUBMIT PRODUCT INFORMATION.
  
 8.)PRODUCT APPROVALS FOR A GARAGE DOOR
 ARE NOT NECESSARY AS THERE AREN'T ANY
 GARAGE DOORS ON THE BUILDING.
  
 9.)COMPLETE FILLING OUT THE PERMIT
 APPLICATIONS.REMOVE THE WORK FROM
 THE DESCRIPTION WHICH WILL NOT BE
 PERFORMED UNDER THIS PERMIT (ROOF IF
 BEING APPLIED FOR SEPARATELY, GARAGE
 DOORS)."MASTER PERMIT NUMBER" SHOULD
 BE THE BUILDING PERMIT NUMBER FOR THAT
 ADDRESS.INCLUDE A VALUE.
  
 10.)THERE IS A CONFLICT ON THE PLAN
 BETWEEN SHEETS A-T3.1 AND A-T3.2 AND
 CBAA CASE #1224.THE WALL, KEYNOTE
 1 ON SHEET A-T3.2, REFERS TO: 5"
 CONCRETE WALL", BUT THE FLOOR PLAN DOES
 NOT IDENTIFY THE CORRECT WALL.
  
 11.)THERE IS A CONFLICT ON THE PLAN
 BETWEEN KEYNOTE, SHEET A-T3.2, AND THE
 CBAA CASE #1224.KEYNOTE 3 REFERS TO:
 5" CONC. WALL - 1 HR FIRE RATED.THIS
 SHOULD BE IDENTIFIED AND DESIGNED AS
 A 2 HOUR FIRE RATED WALL.
  
 12.)THE ENTRANCE DOORS TO THE UNITS,
 IDENTIFIED ON SHEET A-T3.1, KEYNOTE 6,
 ARE REFERRED TO AS A "C" LABEL 1 HR
 FIRE RATED DOOR.THIS SHOULD BE A
 B LABEL DOOR AS PER CBAA CASE NO. 1224.
  
 13.)SHEET A-T3.2, KEYNOTE 4, TEXT
 STATES IS A 6" EXT. METAL STUD EXTERIOR
 WALL.THE TENANT SEPARATION IS
 INCORRECTLY NOTED AS SUCH.
  
 14.)REGARDING THE ABOVE CORRECTIONS
 #10 THROUGH #13, THE DESIGNER OF RECORD
 IS TO MAKE AN APPOINTMENT TO CHANGE THE
 PLANS FOR ALL PERMITS AFFECTED.CALL
 561-805-6724, SAMANTHA THYNG, TO
 SCHEDULE THIS APPOINTMENT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-18 Cont ID  
Sent By csiegber Date 2003-10-29 Time 13:55 Rev Time 0.00
Received By sthyng Date 2003-10-29 Time 13:55 Sent To B
Notes
2003-10-29 00:00:00TO ST DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-18 Cont ID  
Sent By sthyng Date 2003-09-26 Time 12:55 Rev Time 0.00
Received By shill Date 2003-09-26 Time 10:44 Sent To  
Notes
2003-09-26 00:00:00TO ST DESK