Plan Review Details - Permit 03061679
Plan Review Stops For Permit 03061679
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-22 Cont ID  
Sent By jwitmer Date 2003-07-22 Time 10:57 Rev Time 0.75
Received By jwitmer Date 2003-07-22 Time 10:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-08 Cont ID  
Sent By jwitmer Date 2003-07-08 Time 13:06 Rev Time 0.55
Received By jwitmer Date 2003-07-08 Time 13:06 Sent To  
Notes
2003-07-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03061679
 ADD: 400 VILLAGE BLVD SUITE- B
 CONT: CIDS & ASSOC
 TEL: (561)718-3189
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 301.2 OCUPANCY OR USE CATEGORY.
  
 4)11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 THE RESTROOM DOOR TO BE TURNED TO SWING:
 11-4.22.2 DOORS. ALL DOORS TO
 ACCESSIBLE TOLIET ROOMS SHALL COMPLY
 WITH 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-31 Cont ID  
Sent By dpalmer Date 2003-07-31 Time 12:35 Rev Time 0.50
Received By dpalmer Date 2003-07-31 Time 12:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-21 Cont ID  
Sent By dpalmer Date 2003-07-21 Time 13:49 Rev Time 0.50
Received By dpalmer Date 2003-07-21 Time 13:43 Sent To  
Notes
2003-07-21 00:00:00********** PROVISO/REVISION *********
  
 PLEASE SEE NOTE ON FIRST REVIEW.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE W/ A SUBMITTED PANEL
 SCHEDULE.
  
 2)NOTE: PLEASE SHOW CIRCUITING FOR
 EM/EXT LTS PER 700.12E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-07 Cont ID  
Sent By dpalmer Date 2003-07-07 Time 13:19 Rev Time 0.50
Received By dpalmer Date 2003-07-07 Time 13:19 Sent To  
Notes
2003-07-07 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE W A SUBMITTED PANEL
 SCHEDULE.
 PLEASE SHOW/CLARIFY NEW RECEPTS AND
 USEAGE AND LOAD?
 PLEASE ALSO SHOW NEW OR EXISTING EM/EXT
 LTS. 700-12E
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 W/ EXISTING AND NEW LOADS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-23 Cont ID  
Sent By nmccray Date 2003-07-23 Time 14:58 Rev Time 0.00
Received By nmccray Date 2003-07-23 Time 14:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-09 Cont ID  
Sent By nmccray Date 2003-07-09 Time 09:59 Rev Time 0.00
Received By nmccray Date 2003-07-09 Time 09:58 Sent To  
Notes
2003-07-09 00:00:001) WHAT IS THE OCCUPANCY OR USE CATEGORY
  
 2) PLAN DO NOT SHOW EXIT SIGNS OR
 EMERGENCY LIGHTS.
  
 3) WHAT ARE THE INTERIOR FINISH
 CLASSIFICATION FOR THE WALLS AND
 CEILINGS. CLASS "A" OR CLASS "B" ARE
 REQUIRED.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 12:31 Rev Time 0.00
Received By alange Date 2003-07-31 Time 12:31 Sent To  
Notes
2003-07-28 00:00:00TO COMM BD #
 TO COMM BOX #50.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-15 Cont ID  
Sent By shernand Date 2003-07-15 Time 09:36 Rev Time 0.00
Received By shernand Date 2003-07-15 Time 09:36 Sent To  
Notes
2003-07-15 00:00:00COMM BOARD #24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-24 Cont ID  
Sent By shernand Date 2003-06-24 Time 10:23 Rev Time 0.00
Received By shernand Date 2003-06-24 Time 10:23 Sent To  
Notes
2003-06-24 00:00:00COMM BOARD #3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-07-24 Cont ID  
Sent By alange Date 2003-07-24 Time 09:15 Rev Time 0.00
Received By alange Date 2003-07-24 Time 09:15 Sent To  
Notes
2003-07-24 00:00:00NO MECH NEED PER LMALANGE

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-07-08 Cont ID  
Sent By kstevens Date 2003-07-08 Time 07:24 Rev Time 0.25
Received By kstevens Date 2003-07-08 Time 07:24 Sent To  
Notes
2003-07-08 00:00:00NO PLUMBING WORK SHOWN