Plan Review Details - Permit 03061664
Plan Review Stops For Permit 03061664
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-10 Cont ID  
Sent By rbrown Date 2003-07-10 Time 08:05 Rev Time 0.00
Received By rbrown Date 2003-07-10 Time 08:05 Sent To  
Notes
2003-07-10 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 FBC 1606.2.4THE SIMPSON MSTA AND SP
 TIES SPECIFIED AT THE HEAD AND BASE OF
 EACH STUD ARE NOT DESIGNED TO RESIST THE
 HORIZONTAL SHEAR LOADS DUE TO LATERAL
 WIND PRESSURES.PROVIDE AN A3 ANGLE OR
 SIMILAR TO ATTACH EACH STUD TO THE HEAD
 AND SOLE PLATES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-03 Cont ID  
Sent By mmclean Date 2003-07-02 Time 14:21 Rev Time 0.00
Received By rbrown Date 2003-07-03 Time 15:59 Sent To  
Notes
2003-07-03 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.1CONSTRUCTION DETAILS.
 THE PLAN DOES NOT CLEARLY SHOW THE
 EXTENT OR MATERIALS/TYPE OF CONSTRUCTION
 FOR THE PROPOSED WORK.THE EXISTNG
 BATHROOM IS SHOWN WITH NO DOOR.AMEND/
 ANNOTATE THE PLAN TO CLARIFY WHAT IS
 NEW AND WHAT IS EXISTING CONSTRUCTION.
  
 2) FBC* 104.2.1IS THE GARAGE DETACHED
 OR ATTACHED TO THE MAIN BUILDING. AMEND/
 ANNOTATE THE PLAN TO CLARIFY.
  
 3) FBC 1606.2.2.1INSTALLATION OF NEW
 DOOR.THE PLANS DO NOT SHOW THE FRAMING
 AROUND THE NEW DOOR OPENING (SEE COMMENT
 #1 ABOVE).AMEND THE PLANS TO SHOW THE
 CONSTRUCTION AT THE DOOR OPENING
 INCLUDING HEADERS, STUDS, AND BUCK
 DETAIL TO WITHSTAND THE WIND LOADS
 ACTING ON THE DOOR.
  
 4) FBC 3401.7.2.4THE SUBMITTED PRODUCT
 APPROVAL IS FOR A GLAZED STEEL DOOR BUT
 THE PLANS DO NOT SHOW ANY GLAZING IN THE
 DOOR.IF THERE IS TO BE ANY GLAZING IN
 THE NEW DOOR, THE PLANS SHALL BE
 AMENDED/ANNOTATED TO STATE THE AREA OF
 NEW GLAZING AND THE AREA OF EXISTING
 GLAZING IN THE BUILDING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-07-09 Cont ID  
Sent By rbrown Date 2003-07-09 Time 08:16 Rev Time 0.00
Received By rbrown Date 2003-07-09 Time 08:15 Sent To  
Notes
2003-07-09 00:00:00TO RB DESK

Review Stop Z ZONING
Rev No 2 Status P Date 2003-07-02 Cont ID  
Sent By mmclean Date 2003-07-02 Time 14:21 Rev Time 1.00
Received By mmclean Date   Time   Sent To B
Notes
2003-07-02 00:00:007/2/03 PASS ZONING FOR RECREATION ROOM M

Review Stop Z ZONING
Rev No 1 Status F Date 2003-06-30 Cont ID  
Sent By mmclean Date 2003-06-30 Time 15:06 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-06-30 00:00:006/30/03 DENIED, GARAGE CAN NOT BE
 USED AS A SLEEPING ROOM IN SF7. NO
 VARIANCE WILL BE ALLOWED. CALLED CONTR
 FILE R MM