Plan Review Details - Permit 03061612
Plan Review Stops For Permit 03061612
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-02-28 Cont ID  
Sent By shill Date 2004-02-28 Time 16:24 Rev Time 1.00
Received By shill Date 2004-02-20 Time 08:12 Sent To  
Notes
2004-02-28 00:00:00REVISION A03

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-01-17 Cont ID  
Sent By kstevens Date 2004-02-17 Time 18:38 Rev Time 0.50
Received By shill Date 2004-01-17 Time 19:09 Sent To  
Notes
2004-01-17 00:00:00REVISED A03, A07 AS REQUESTED

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-11-12 Cont ID  
Sent By csiegber Date 2004-01-14 Time 16:40 Rev Time 1.50
Received By sthyng Date 2003-11-12 Time 12:47 Sent To  
Notes
2003-11-12 00:00:00REVISE SHEETS A03, S02

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-11-10 Cont ID  
Sent By csiegber Date 2003-11-10 Time 14:50 Rev Time 2.00
Received By sthyng Date 2003-11-08 Time 17:45 Sent To  
Notes
2003-11-08 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.A NOTICE OF
 COMMENCEMENT IS IN THE PACKAGE BUT IT IS
 INCOMPLETE.IT MUST BE COMPLETED AND
 FILED WITH THE CLERK OF COURTS.
  
 3.)SEE PREVIOUS LIST, ITEM #3, AND
 FIRST CORRECTION LIST, ITEM #3.AS
 DISCUSSED WITH YOU ON THE TELEPHONE, A
 34 SINGLE HUNG WINDOW DOES NOT MEET
 EMERGENCY EGRESS REQUIREMENTS.A COPY
 OF STANDARD WINDOW SIZES WAS ATTACHED TO
 THE PREVIOUS LIST (IT IS STILL IN THE
 PACKAGE) AND I FAXED ONE TO YOU AFTER
 OUR TELEPHONE CONVERSATION.YOU HAVE
 CHANGED THE NOTE TO SAY "EH"; UNSURE AS
 TO WHAT THAT IS.IF YOU FEEL THAT I AM
 IN ERROR, PROVIDE THE MANUFACTURER'S
 SPECIFICATION SHOWING THAT A 34 SINGLE
 HUNG MEETS THE EMERGENCY REQUIREMENTS
 PER FBC1005.4.
  
 4.)SEE THE PREVIOUS LIST, ITEM 5.
 A NOTE WAS MADE THAT A WINDOW IN THE
 MASTER BATH NEEDS TO COMPLY WITH
 FBC2405.1.THE CORRECTION WAS MADE
 REFERENCING BATH 2, THE WINDOW AT THE
 SHOWER.WHEN REVISING THE PLAN, DO NOT
 QUOTE CODE SECTION. THE PRODUCT APPROVAL
 SUBMITTED IS FOR IMPACT WINDOWS; THE
 PLAN CAN INDICATE EITHER SAFETY GLASS,
 TEMPERED, OR IMPACT, BUT DO NOT
 REFERENCE CODE SECTION ONLY FBC104.2.
  
 5.)SEE PREVIOUS LIST, ITEM #6.A
 NOTE WAS ADDED IN REGARDS TO THE LIVE
 LOAD FOR THE BOTTOM CHORD, BUT #11 OF
 THE ROOF PLAN NOTES STILL SHOWS THE LIVE
 LOAD, BOTTOM CHORD AS 5PSF.THIS SHOULD
 BE 30 FOR ATTICS WITH STORAGE, 10 FOR
 ATTICS WITHOUT STORAGE.
  
 6.)THE HURRICANE SHUTTER INSTALLATION
 SCHEDULE IS A FORM TO BE FILLED OUT.A
 COPY WAS PROVIDED WITH THE LAST REVIEW.
 A NOTE ON THE PLAN IS NOT NECESSARY, BUT
 THE FORM DOES NEED TO BE COMPLETED.
  
 7.)PLEASE DO NOT DISSASEMBLE THE
 PACKAGES I HAVE PUT TOGETHER.THEY HAVE
 BEEN PUT TOGETHER TO PREPARE THE PACKAGE
 FOR ISSUANCE; TAKING THE PACKAGES APART
 DELAYS THE PERMIT PROCESS.
  
 8.)THE SOILS REPORT RECOMMENDS A
 CONTINUOUS FOUNDATION WIDTH OF AT LEAST
 18".REVISE THE FOUNDATION PLAN.
  
 10.)SEE PREVIOUS CORRECTION LIST, ITEM
 #8.THE PRODUCT APPROVAL SUBMITTED FOR
 DOORS WAS FOR AN IMPACT FRENCH DOOR WITH
 SIDELITES.THE FRONT DOOR IS A SERIES
 OF THREE FRENCH DOORS.THIS IS NOT
 COVERED BY THE PRODUCT APPROVAL
 SUBMITTED.THE MULLION PRODUCT APPROVAL
 SUBMITTED HAS A MAX DESIGN LOAD OF
 +-35 FOR THAT SIZE.PLEASE NOTE THAT
 A HEAVY DUTY MULLION HAS A HIGHER DESIGN
 LOAD.SUBMIT PRODUCT APPROVALS FOR THE
 MULLION FOR THE FRONT DOOR AND THE
 FRENCH DOORS (WITHOUT SIDELITES).
  
 11.)THE FRONT DOOR (MAIN EGRESS) IS
 REQUIED TO HAVE A MINIMUM CLEARANCE OF
 32", FBC1012.1.1.
  
 WHEN RESUBMITTING, REPLACE SHEETS WHICH
 HAVE BEEN REVISED AND SUBMIT OLD SHEETS
 SEPARATELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-11-04 Time 13:56 Rev Time 2.50
Received By sthyng Date 2003-10-07 Time 07:15 Sent To  
Notes
2003-10-07 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 3.)SEE ATTACHED NOTICE REGARDING
 FS553.80(2)(B).SEE PREVIOUS CORRECTION
 LIST #6 - "EXISTING MASTER BEDROOM AND
 BEDROOM ARE REQUIRED TO HAVE EMERGENCY
 EGRESS.SPECIFY THE TYPE OF WINDOW,
 SHOWING COMPLIANCE WITH FBC1005.4."
 THE CORRECTION ON THE PLAN, A-03, WAS
 "PROVIDE NEW EGRESS WINDOW IN EXISTING
 M.O." WITH AN OPENING SIZE OF 37X51.
 PRODUCT APPROVALS FOR AWNING WINDOWS
 WERE SUBMITTED.AWNING WINDOWS DO NOT
 MEET EMERGENCY EGRESS REQUIREMENTS.
 SINGLE HUNG WINDOWS IN THIS SIZE (SEE
 ATTACHED) ALSO DO NOT MEET EMERGENCY
 EGRESS REQUIREMENTS.PLEASE ADDRESS.
  
 4.)THE "NEW GIRDER TRUSS ABOVE DEN"
 (A03) ATTACHES TO A BEAM ABOVE A WINDOW.
 IS THIS CORRECT?
  
 5.)THE WINDOW AT THE SHOWER, BATH 2,
 MUST COMPLY WITH FBC2405.1.SHOW ON THE
 FLOOR PLAN (A03).
  
 6.)S-02, LIVE LOAD FOR THE BOTTOM
 CHORD OF THE TRUSSES, ATTIC W/STORAGE
 SPACE SHOULD BE 30PSF, FBC TABLE 1604.1.
  
 7.)THE PRODUCT APPROVALS FOR THE
 LOUVERED VENT IS EXPIRED.
  
 8.)NOTE THAT ON PAGE A04 OF THE PLAN,
 A DESIGN PRESSURE OF +46/-62 IS
 REQUIRED FOR DOORS AND WINDOWS.THE
 MAX PRESSURES FOR THE FOLLOWING PRODUCTS
 DO NOT MEET THE DESIGN PRESSURE
 REQUIREMENTS AS PER THE PRODUCT
 APPROVALS:
 AWNING WINDOWS
 GARAGE DOOR (+44/-56)
 MULLIONS (FOR 96X90, +/-35 - FR DOORS)
 NOTE - MULLIONS OK FOR WINDOWS
  
 NOTE - THE IMPACT PRODUCT APPROVALS
 FOR THE FRENCH DOORS WERE FOR IMPACT
 DOORS W/SIDELITES.IT APPEARS FROM THE
 PRODUCT APPROVALS THAT YOU ARE
 INSTALLING IMPACT AT THE MASTER BEDROOM,
 NON-IMPACT FRENCH DOORS W/MULLIONS AND
 SHUTTERS AT THE DINING ROOM (NO SIDELITE
 SHOWN ON THE FRENCH DOORS AT THAT
 LOCATION).
  
 9.)PROVIDE A HURRICANE SHUTTER
 ATTACHMENT SCHEDULE, SEE ATTACHED
 POLICY.
  
 10.) IF ANY PRODUCT APPROVALS ARE NOT
 APPROVED AT THE TIME OF ISSUANCE WILL
 REQUIRE THAT A SEPARATE PERMIT BE
 APPLIED FOR, WITH ADDITIONAL FEES, FOR
 THOSE ITEMS.
  
 PRODUCT APPROVALS MAY BE AVAILABLE AT
 WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING
 CODE COMPLIANCE, PRODUCT CONTROL,
 SEARCH APPROVED PRODUCTS).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-16 Cont ID  
Sent By jleech Date 2003-10-02 Time 17:10 Rev Time 3.00
Received By sthyng Date 2003-07-16 Time 09:06 Sent To  
Notes
2003-07-16 00:00:00*******CORRECTIONS********
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)AREA CALCULATIONS SHOULD INCLUDE
 EXISTING CONDITIONED AND UNCONDITIONED
 SPACE, PROPOSED, NEW SUBTOTALS AND A
 NEW TOTAL.
  
 4.)LEGAL DESCRIPTION (A01) SHOULD NOT
 SAY "RELOCATED".THE CORRECT WORD IS
 "LOCATED".
  
 5.)THIS IMPROVEMENT IS OVER 25% AND
 MUST COMPLY WITH FBC 3405 (SEE COMMENTS
 #6, #7.
  
 6.)EXISTING MASTER BEDROOM AND BEDROOM
 2 IS REQUIRED TO HAVE EMERGENCY EGRESS.
 SPECIFY THE TYPE OF WINDOW, SHOWING
 COMPLIANCE WITH FBC1005.4.
  
 7.)GLASS AT THE SHOWER MUST COMPLY
 WITH FBC2405.1.
  
 8.)THE WALL SECTION (3-A05) SPECIFIES
 R19 INSULATION IN THE CEILING; THE
 ENERGY CALC REQUIRES A MINIMUM OF R30.
  
 9.)THE NEW GIRDER OVER THE DINING
 ROOM IS SHOWN AS BEING SUPPORTED BY A
 COLUMN AT THE ENTRY ON THE FOUNDATION
 AND ROOF FRAMING PLAN, BUT IS NOT SHOWN
 ON THE FLOOR PLAN. REVISE.
  
 10.) SPECIFY THE MINIMUM SIZE OF THE
 ATTIC ACCESS, COMPLYING WITH FBC2309.6
 AND FBC2309.7.
  
 11.)SOFFIT VENTS (WALL SECTION 4-A05)
 CANNOT "MATCH EXISTING"; MUST COMPLY
 WITH FBC2309.7.
  
 12.)SPECIFY SIZE OF FIRE STOP (4-A05),
 FBC705.3.
  
 13.)STRUCTURAL NOTE #10 (S01) REFERS
 TO SOUTH FLORIDA BUILDING CODE.THE
 GOVERNING CODE IS FLORIDA BUILDING
 CODE 2001.REVISE.
  
 14.) A CONNECTOR SCHEDULE IS PROVIDED
 ON S03.THE CONNECTOR MARKS (U2, U4,
 U5, U8) ARE NOT SHOWN ON THE ROOF
 FRAMING PLAN (S02).
  
 15.)ROOF SHEATHING SCHEDULE DID NOT
 PRINT PROPERLY (S02).
  
 16.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE ORIGINAL RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.233-5025
  
 17.)SUBMIT PRODUCT APPROVALS FOR ALL
 EXTERIOR COMPONENTS AND CLADDING,
 INCLUDING:
 WINDOW MULLIONS
 ROOF(MAY BE SUBMITTED WITH ROOF
 PERMIT)
 GARAGE DOOR
 GLASS BLOCK
 LOUVERED VENT
 IMPACT PROTECTION
 WINDOWS
 FRENCH DOORS
 SIDELITES
  
 18.)PROVIDE A 2ND COPY OF THE SURVEY.
  
 WHEN RESUBMITTING, REPLACE SHEETS WHICH
 HAVE CHANGED WITH NEW SHEETS (DO NOT
 REPLACE WITH A NEW PACKAGE UNLESS ALL
 OF THE SHEETS HAVE CHANGED).SUBMIT
 THE OLD SHEETS WITH THE PACKAGE. CLEARLY
 MARK ALL CHANGES.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-11-16 Cont ID  
Sent By btrobaug Date 2004-11-16 Time 07:46 Rev Time 0.50
Received By btrobaug Date 2004-11-16 Time 07:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-30 Cont ID  
Sent By jleahy Date 2004-06-30 Time 09:26 Rev Time 0.30
Received By jleahy Date 2004-06-30 Time 09:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-23 Cont ID  
Sent By csiegber Date 2004-06-25 Time 15:09 Rev Time 0.50
Received By btrobaug Date 2003-09-23 Time 10:55 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-09 Cont ID  
Sent By csiegber Date 2003-09-17 Time 16:03 Rev Time 1.00
Received By btrobaug Date 2003-07-09 Time 06:56 Sent To P
Notes
2003-07-09 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLAN AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE NOTE THAT THE GEC MUST ALSO GO
 TO FOOTER STEEL PER 250-50(C),IF
 AVAILABLE.
  
 3} PER 210-11(C)(3),THE RECEPTACLES IN
 THE MASTER BATH CAN NOT BE ON THE SAME
 CIRCUIT AS THE GFI IN THE REAR OF THE
 HOUSE.
  
 4} THE RECEPTACLE IN THE BATHOUTSIDE
 THE MASTER BEDROOM IS SHOWN ON A CIRCUIT
 THAT IS LISTED AS A SPARE (A-36),COULD
 BE ON B-7 PER 210-11(C)(3) AND
 EXCEPTION.
  
 5} THE EXISTING MASTER BEDROOM IS LISTED
 ON THE A/C CIRCUIT(A-3),PLEASE CLARIFY.
  
 6} ALL KITCHEN RECEPTACLES THAT SERVE
 COUNTERTOP SURFACES SHALL BE GFI PER
 210-8(A)(6),PLEASE INDICATE SAME ON
 PLAN. ALSO NOTE SPACING PER
 210-52(C)(1).NOTE THEAT THERE WILL BE
 COUNTERTOP OVER THE DISHWASHER.
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 8} THE DEN IS CONSIDERED A BEDROOM BY
 THE FLORIDA BUILDING CODE AND IS
 THEREFORE REQUIRED TO HAVE A SMOKE
 DETECTORS PER8-1.4 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-11-08 Cont ID  
Sent By csiegber Date 2004-11-08 Time 12:18 Rev Time 0.00
Received By csiegber Date 2004-11-08 Time 12:18 Sent To E
Notes
2004-11-08 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 15:09 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 15:09 Sent To E
Notes
2004-06-25 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-12 Time 14:35 Rev Time 0.00
Received By csiegber Date 2004-02-12 Time 14:35 Sent To P
Notes
2004-02-12 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-14 Time 16:40 Rev Time 0.00
Received By csiegber Date 2004-01-14 Time 16:40 Sent To B
Notes
2004-01-14 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-11-10 Cont ID  
Sent By csiegber Date 2003-11-10 Time 14:50 Rev Time 0.00
Received By csiegber Date 2003-11-10 Time 14:50 Sent To B
Notes
2003-11-10 00:00:00TO ST DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-11-04 Time 13:55 Rev Time 0.00
Received By csiegber Date 2003-11-04 Time 13:55 Sent To B
Notes
2003-11-04 00:00:00TO ST DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-17 Time 16:03 Rev Time 0.00
Received By csiegber Date 2003-09-17 Time 16:03 Sent To E
Notes
2003-09-17 00:00:00TO BT DESK RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 10:14 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 10:14 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-23 Cont ID  
Sent By mmclean Date 2003-06-25 Time 15:31 Rev Time 0.00
Received By shernand Date 2003-06-23 Time 13:01 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-14 Cont ID  
Sent By kstevens Date 2003-07-09 Time 16:57 Rev Time 0.25
Received By pkrauss Date 2003-07-14 Time 07:14 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-02-17 Cont ID  
Sent By kstevens Date 2004-02-17 Time 18:38 Rev Time 0.50
Received By kstevens Date 2004-02-17 Time 18:38 Sent To B
Notes
2004-02-17 00:00:00REVISION OK - CHANGED FLOOR PLAN LAYOUT
 IN MASTERBATH - CHANGED RISER DIAGRAM
 AND FLAT PIPING LAYOUT SHTS P-01 & P-02

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-02 Cont ID  
Sent By csiegber Date 2004-02-12 Time 14:35 Rev Time 0.33
Received By jleech Date 2003-10-02 Time 17:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-07-09 Cont ID  
Sent By btrobaug Date 2003-09-23 Time 11:23 Rev Time 0.50
Received By kstevens Date 2003-07-09 Time 16:56 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-06-23 Time 13:01 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***