Plan Review Details - Permit 03061500
Plan Review Stops For Permit 03061500
Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2004-09-16 Cont ID  
Sent By lsmith Date 2004-09-16 Time 10:28 Rev Time 0.50
Received By lsmith Date 2004-09-16 Time 10:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2004-08-02 Cont ID  
Sent By csiegber Date 2004-09-15 Time 14:45 Rev Time 0.50
Received By lsmith Date 2004-08-02 Time 07:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2004-05-27 Cont ID  
Sent By csiegber Date 2004-07-30 Time 14:45 Rev Time 0.50
Received By lsmith Date 2004-05-27 Time 15:18 Sent To  
Notes
2004-05-27 00:00:00CHANGED DIMENSIONS TO 10.7 (129") PER SH

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2004-04-27 Cont ID  
Sent By shill Date 2004-04-27 Time 16:03 Rev Time 0.50
Received By shill Date 2004-04-27 Time 16:03 Sent To  
Notes
2004-04-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST IN REGARDS TO
 THE SIZE OF THE SCREEN ENCLOSURE.THE
 DIMENSION ON THE SITE PLAN WAS CHANGED
 BUT YOUR STRUCTURAL STILL SHOWS A
 DEPTH OF 12 WITH POSTS 6' APART.THE
 SCREEN ROOM ON THE STRUCTURAL SHEET DOES
 NOT FIT ON YOUR SITE PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-04-19 Cont ID  
Sent By csiegber Date 2004-04-26 Time 09:26 Rev Time 0.50
Received By shill Date 2004-04-19 Time 11:16 Sent To  
Notes
2004-04-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)ZONING HAS NOTED ON THE PLAN THAT
 THE SCREEN ENCLOSURE IS TO BE 2' FROM
 THE PROPERTY LINE MINIMUM.THE
 STRUCTURAL STILL SHOWS THE SCREEN
 ROOM AT 12'.SEE MY NOTE, WHICH WAS
 ENCLOSED IN YOUR RESUBMITTAL.THE MAX
 DEPTH OF THE SCREEN ROOM BASED ON THE
 SURVEY AND ZONING REQUIREMENT WOULD BE
 10.7'.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-04-07 Time 10:57 Rev Time 0.00
Received By mmclean Date 2004-03-25 Time 15:27 Sent To  
Notes
2004-03-25 00:00:00DENIED BY SAMANTHA HILL NEED TO PROVIDE
 NEW DRAWINGS TO MEET ZOING 2FT ON ZERO
 SIDE.CONTR PICKED UP MM

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-03 Cont ID  
Sent By shill Date 2004-03-03 Time 15:47 Rev Time 0.50
Received By shill Date 2004-03-03 Time 15:47 Sent To Z
Notes
2004-03-03 00:00:00PROVISO - ZONING APPROVAL
 REVISION TO CHANGE SIZE

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-10-28 Cont ID  
Sent By csiegber Date 2004-02-13 Time 16:17 Rev Time 1.00
Received By sthyng Date 2003-10-28 Time 10:36 Sent To  
Notes
2003-10-28 00:00:00CONTRACTOR BROUGHT IN PICTURES SHOWING
 SHUTTERS ON EXISTING HOUSE - PORCH
 DESIGNED AS OPEN

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-15 Cont ID  
Sent By csiegber Date 2003-10-20 Time 16:13 Rev Time 1.00
Received By sthyng Date 2003-07-15 Time 15:57 Sent To Z
Notes
2003-07-15 00:00:00******CORRECTIONS******
  
 1.)THE OLD SHEETS WERE MISSING FROM
 THE PLAN.SUBMIT ALL OLD SHEETS WHEN
 RESUBMITTING.
  
 2.)IS THE ROOF OF THE SCREEN ENCLOSURE
 SOLID?SHOW ON THE SITE PLAN AND THE
 ROOF PLAN.
  
 3.)THE ENGINEERING PROVIDED IS
 APPARENTLY FOR THE SCREEN ENCLOSURE.
 PROVIDE ENGINEERING FOR THE ENCLOSURE
 OF THE EXISTING PATIO.
  
 4.)SEE THE PREVIOUS CORRECTION LIST
 #1.A NOTE WAS SENT TO ME INDICATING
 THAT THE REMAINDER OF AMOUNT WAS ON
 A SHUTTER PERMIT.YOUR CONTRACT DOES
 NOT MENTION SHUTTERS.
  
 5.)SEE PREVIOUS CORRECTION LIST
 #2.THE PLAN THAT I WAS REFERRING TO
 IS NO LONGER WITH THE PACKAGE.THE
 NOTE IS NOT ANYWHERE ON THE PLAN.
  
 6.)THE PRODUCT REPORT IS ILLEGIBLE.
 SEE PREVIOUS CORRECTION LIST #5.
  
 7.)SEE PREVIOUS CORRECTION LIST #4.
 IF THE ENGINEERING FOR THE ENCLOSURE
 INCLUDES WOOD BUCKS, A BUCK ATTACHMENT
 SCHEDULE MUST BE INCLUDED.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-07-15 Time 09:40 Rev Time 1.00
Received By sthyng Date 2003-06-27 Time 12:19 Sent To  
Notes
2003-06-27 00:00:00******CORRECTIONS*******
  
 1.)THE INCORRECT VALUE WAS SPECIFIED
 ON THE APPLICATION, ADDITIONAL FEES
 REQUIRED.
  
 2.)THE ACRYLIC PANELS ARE REQUIRED
 TO BE REMOVABLE FBC2002.3 WITH AN
 IDENTIFICATION DECAL. SHOW ON THE PLAN.
  
 3.)THE ENGINEERING SHOWS A PAN/POLY
 ROOF, 14' SPAN HIGHLIGHTED, BUT THE
 SURVEY SHOWS AN EXISTING 8'SPAN ROOF.
 CLARIFY.
  
 4.)THE TEST REPORT INDICATES THAT
 THE TEST WAS PERFORMED ATTACHED TO
 WOOD BUCKS, BUT THIS IS NOT THE
 APPLICATION YOU ARE USING.HAVE THE
 ENGINEER REVIEW AND APPROVE THE PRODUCT
 APPROVAL.
  
 5.)THE GENERAL NOTES ON THE PRODUCT
 REPORT ARE NOT LEGIBLE.
  
 6.)THE CONTRACT SHOWS A 208 SF SLAB.
 THIS IS NOT SHOWN ON THE SITE PLAN.IS
 THIS SLAB TO BE A PART OF THIS ACRYLIC
 ENCLOSURE?

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 14:45 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 14:45 Sent To B
Notes
2004-09-15 00:00:00TO LS DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-07-30 Cont ID  
Sent By csiegber Date 2004-07-30 Time 14:45 Rev Time 0.00
Received By csiegber Date 2004-07-30 Time 14:45 Sent To B
Notes
2004-07-30 00:00:00TO LS DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-04-26 Cont ID  
Sent By csiegber Date 2004-04-26 Time 09:26 Rev Time 0.00
Received By csiegber Date 2004-04-26 Time 09:26 Sent To B
Notes
2004-04-26 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-04-07 Cont ID  
Sent By csiegber Date 2004-05-05 Time 15:43 Rev Time 0.00
Received By csiegber Date 2004-04-07 Time 10:57 Sent To  
Notes
2004-04-07 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-13 Time 16:17 Rev Time 0.00
Received By csiegber Date 2004-02-13 Time 16:16 Sent To B
Notes
2004-02-13 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-20 Cont ID  
Sent By csiegber Date 2003-10-20 Time 16:13 Rev Time 0.00
Received By csiegber Date 2003-10-20 Time 16:13 Sent To B
Notes
2003-10-20 00:00:00TO ST DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-14 Cont ID  
Sent By csiegber Date 2003-10-14 Time 14:33 Rev Time 0.00
Received By csiegber Date 2003-10-14 Time 14:33 Sent To B
Notes
2003-10-14 00:00:00TO ST DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-15 Cont ID  
Sent By mmclean Date 2003-07-21 Time 10:49 Rev Time 0.00
Received By shernand Date 2003-07-15 Time 09:40 Sent To B
Notes
2003-07-15 00:00:00STHYNG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-24 Cont ID  
Sent By shernand Date 2003-06-24 Time 10:52 Rev Time 0.00
Received By shernand Date 2003-06-24 Time 10:52 Sent To B
Notes
2003-06-24 00:00:00MISC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-20 Cont ID  
Sent By mmclean Date 2003-06-24 Time 09:09 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 11:56 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2004-04-07 Cont ID  
Sent By sgraham Date 2004-04-07 Time 10:15 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2004-03-25 Cont ID  
Sent By mmclean Date 2004-03-25 Time 15:26 Rev Time 0.00
Received By mmclean Date 2004-03-25 Time 15:26 Sent To  
Notes
2004-03-25 00:00:00DENIED, NEED TO PROVIDE NEW DRAWINGS &
 SURVEY SHOWING 2FT ON ZERO SIDE CONTR
 PICKED UP MM

Review Stop Z ZONING
Rev No 3 Status F Date 2004-03-03 Cont ID  
Sent By mmclean Date 2004-03-03 Time 16:53 Rev Time 0.00
Received By mmclean Date 2004-03-03 Time 16:53 Sent To  
Notes
2004-03-03 00:00:00DENIED, NEED TO BE 2FT ON ZERO SIDE &
 NONE ZERO SIDE CALLED CONTR FILE S MM
 (REVISION)

Review Stop Z ZONING
Rev No 2 Status P Date 2003-07-21 Cont ID  
Sent By shill Date 2004-03-03 Time 15:47 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-24 Cont ID  
Sent By sthyng Date 2003-07-15 Time 16:35 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***