Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-16 Cont ID  
Sent By hmoser Date 2003-07-08 Time 18:01 Rev Time 2.00
Received By jgomez Date 2003-07-16 Time 14:49 Sent To PC
Notes
2003-07-16 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-RESUBMIT SHEET A-3. DRAWINGS ARE NOT
 COMPLETE.
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITH SIDELITE AS SHOWN ON PLANS.
 3-SPECIFY GLASS BLOCK TO BE SAFETY GLASS
 IF FACE THICKNESS IS LESS THAN 0.25".
 SEC. 2405.2 FBC 2001.
 4-REVISE DETAIL SECTION 3 ON DRAWING S2.
 FASTENERS TO MATCH DIAPHRAGM SCHEDULE.
 5-PROVIDE GENERAL SPECIFICATIONS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES
 AS REQUIRED BY SEC. 2305 FBC 2001.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-06 Cont ID  
Sent By btrobaug Date 2003-11-06 Time 10:30 Rev Time 0.33
Received By btrobaug Date 2003-11-06 Time 10:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-07 Cont ID  
Sent By csiegber Date 2003-10-24 Time 09:28 Rev Time 0.33
Received By dpalmer Date 2003-07-07 Time 08:23 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-11-03 Time 14:05 Rev Time 0.00
Received By csiegber Date 2003-11-03 Time 14:05 Sent To M
Notes
2003-11-03 00:00:00TO PK DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 09:28 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 09:28 Sent To E
Notes
2003-10-24 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-18 Cont ID  
Sent By mmclean Date 2003-06-19 Time 12:16 Rev Time 0.00
Received By shernand Date 2003-06-18 Time 08:21 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-12-02 Cont ID  
Sent By pkrauss Date 2003-12-02 Time 08:02 Rev Time 0.33
Received By pkrauss Date 2003-12-02 Time 07:55 Sent To  
Notes
2003-12-02 00:00:00DENIED:
 EQUIPMENT SCHEDULE ON PLAN SHEET MP-2
 INDICATES A 12 SEER AND THE APPROVED
 ENERGY CALCULATIONS CALL FOR AN 11 SEER.
  
 PLEASE REVISE PLANS OR THE ENERGY
 CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-08 Cont ID  
Sent By csiegber Date 2003-11-03 Time 14:05 Rev Time 0.25
Received By hmoser Date 2003-07-08 Time 18:01 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-07-08 Cont ID  
Sent By dpalmer Date 2003-07-07 Time 08:23 Rev Time 0.25
Received By jleech Date 2003-07-08 Time 18:23 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-19 Cont ID  
Sent By shernand Date 2003-06-18 Time 08:21 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***