Plan Review Details - Permit 03061305
Plan Review Stops For Permit 03061305
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-16 Cont ID  
Sent By jwitmer Date 2003-09-16 Time 16:52 Rev Time 1.00
Received By jwitmer Date 2003-09-16 Time 16:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-08-07 Cont ID  
Sent By jwitmer Date 2003-08-07 Time 10:28 Rev Time 1.00
Received By jwitmer Date 2003-08-07 Time 10:28 Sent To  
Notes
2003-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03061305
 ADD:7717 S DIXIE HWY
 CONT: CANVAS CONT
 TEL: (954) 779-2280 RAFAEL
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
  
 ACTION: DENIED
  
 1) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
 MISSING REPORTS:
 A) EXTERIOR DOOR
 B) WINDOWS, STOREFRONT
 C) MULLIONS
 D) STORM SHUTTERS
  
 2)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 3)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-08 Cont ID  
Sent By jwitmer Date 2003-07-08 Time 10:42 Rev Time 0.00
Received By alange Date 2003-07-23 Time 08:47 Sent To  
Notes
2003-07-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03061305
 ADD: 7717 S DIXIE HWY
 CONT: CANDAS CONSTRUCTION
 TEL: (974)779-2280
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) BUILDING CODE DATA, OCCUPANT LOAD FOR
 THIS EXSPANSION, 1003.1.1 FOR DETERMIN-
 ING THE MEANS OF EGRESS REQUIRED, THE
 MINIMUM NUMBER OF PERSONS FOR ANY FLOOR
 AREA SHALL BE IN NO CASE TAKEN LESS THAN
 SPECIFIED IN TABLE 1003.1. TOTAL OCCU-
 PANT LOAD WITH LUNCHROOM IS CLOSER TO
 189, NOT 133.
  
 2) STOREFRONT WINDLOADS:
 A) ASCE 7-___, THIS EDITION OF THE CODE
 REFLECTS ASCE 7-98.
  
 B) IMPORTANCE FACTOR I IS ASCE 7-98
 TABLE 1-1, THIS CATEGORY IS FOR AGRICULT
 URAL FACILITIES, TEMPORY FACILITIES OR
 MINOR STORAGE FACILITIES. SEE III-
 BUILDINGS AND OTHER STRUCTURES WITH ELE-
 MENTARY OR SECONDARY SCHOOL FACILITIES
 WITH THTE CAPACITY GREATER THAN 150.
 TABLE 6-1 IMPORTANCE FACTOR 111= 1.15 IN
 HURRICANE REGIONS WITH > 100 MPH.
  
 C) INTERNAL PRESSURE COEFFICIENT:
 MISSING, SEE TABLE 6-7 FOR ENCLOSED
 BUILDINGS.
  
 3) STOREFRONT DETAIL A/A-2:
 A) THIS DETAIL IS UNCLEAR HOW THE STORE
 FRONT FRAME IS TO TIE INTO THE BEAM, IT
 APPEARS THAT A UPPER STOREFRONT TRACK
 IS TO BE COVERED OVER WITH ADDITIONAL
 MATERIALS, ONE CONCERN IS THIS DOESN'T
 INDICATE IF THERE IS VERTICAL MULLIONS
 ATTACHING BACK INTO THE STRUCTURE, OR IF
 THIS IS A 16'-10" SPAN?
 B) THIS DETAIL ALSO REFLECTS THE USE OF
 5/8" CDX PLYWOOD ON THE WALL, THIS STRUC
 TURE IS IN A "FIRE DISTRICT" TYPE V
 CONSTRUCTION, (NON-COMBUSTIBLE) MATER-
 IALS ARE TO BE USED.F 102.1 TYPES OF
 CONSTRUCTION ALLOWED IN A FIRE DISTRICT.
  
 C) THIS SAME DETAIL INDICATES A THE USE
 OF A 8"X8" BEAM BUT NO VERTICAL STEEL
 FROM THE FOUNDATION TO THE NEW BEAM???
 WILL THIS BE SUFFICIENT ENOUGH FOR THE
 NEW LATERAL WIND LOADING OF THE WINDOWS
 AND WALL PLUS LOADING FOR LARGE MISSLE
 IMPACT WITH THE NEW FACTORS FIGURED IN??
  
 D) WITH THE NEW FACTORS FIGURED IN WHAT
 WILL THE NEW PRESSURES BE????
  
 E) SAME DETAIL DISCREPANCY, LOOK HOW THE
 WINDOW IS DIMENSIONED ?
  
 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 6) SHEET A-1 INDICATES THE CUTTING
 THROUGH A EXISTING BLOCK WALL, TIEING A
 NEW BEAM INTO AN EXISTING COLUMN BUT NO
 MENTION AS TO HOW THE OTHER END OF THE
 BEAM IS TO BE SUPPORTED?
  
 7) ROOM 102 WHAT IS HAPPENING AT THE
 REAR OF THE CLASSROOM?
  
 8) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORT:
 A) EXTERIOR DOOR
 B) WINDOWS, STOREFRONT
 C) MULLION
 D) STORM SHUTTERS IF GLAZING NOT LARGE
 MISSLE RESISTENT
  
 9)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-29 Cont ID  
Sent By dpalmer Date 2003-07-29 Time 15:39 Rev Time 0.50
Received By dpalmer Date 2003-07-29 Time 15:29 Sent To  
Notes
2003-07-29 00:00:00PLEASE NOTE, OLD/ VOIDED SHEETS SHOULD
 HAVE BEEN REMOVED AND NEW SHEETS INSERT-
 -ED TO MAKE TWO COMPLETE PACKAGES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-03 Cont ID  
Sent By dpalmer Date 2003-07-03 Time 08:41 Rev Time 0.50
Received By dpalmer Date 2003-07-03 Time 08:41 Sent To  
Notes
2003-07-03 00:00:00************* UNSAT **************
  
 1)NOTE: PLESE SHOW LOAD CALCAULTIONS
 PER NEC 220-3,220-10,220-11,220-11,220-
 13, PLEASE ALSO SHOW ALL CONTINUOUS
 LOADS AT 125%. 215-3/230-42
  
 PLEASE SEE ANY COMMENT FROM OTHER
 REVIEWERS THAT MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-08-11 Cont ID  
Sent By nmccray Date 2003-08-11 Time 11:39 Rev Time 0.00
Received By nmccray Date 2003-08-11 Time 11:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-11 Cont ID  
Sent By mcarsill Date 2003-07-11 Time 13:52 Rev Time 0.00
Received By mcarsill Date 2003-07-11 Time 13:52 Sent To  
Notes
2003-07-11 00:00:001) SINCE THE AREA IS FIRE SPRINKLER
 PROTECTED, THE CORRIDOR WALLS ARE
 REQUIRED TO BE SMOKE RESISTANT. DOORS
 ARE REQUIRED TO BE EQUIPPED WITH SELF
 CLOSING DEVICES.
  
 2) PLEASE INDICATE AGES AND NUMBERS OF
 STUDENTS. ALSO PLEASE INDICATE TEACHER
 RATIO.
  
 3) ARTWORK AND OTHER MATERIALS AFFIXED
 TO WALLS CANNOT EXCEED 20 PERCENT.
  
 4) FIRE DRILLS ARE REQUIRED TO BE
 PERFORMED. PLEASE KEEP A DETAILED
 LOG OF THESE FIRE DRILLS.
  
 5) OPENINGS IN SMOKE PARTITIONS ARE
 TO BE PROPERLY SEALED.
  
 6) NO COOKING IS PERMITTED IN THE
 LUNCHROOM SINCE NO HOOD, DUCT OR
 SUPPRESSION SYSTEM IS MENTIONED.
  
 7) ALL PLANNED WORK IS TO COMPLY WITH
 NFPA 241.
  
 8) PROVIDE PLANS AND PERMITS FOR ANY
 FIRE SPRINKLER REMODELING.
  
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM EQUIPMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 805-6722
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-10 Cont ID  
Sent By csiegber Date 2003-09-10 Time 15:55 Rev Time 0.00
Received By csiegber Date 2003-09-10 Time 15:55 Sent To  
Notes
2003-09-10 00:00:00ON COMM BD#24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-23 Cont ID  
Sent By alange Date 2003-07-23 Time 08:49 Rev Time 0.00
Received By alange Date 2003-07-23 Time 08:49 Sent To  
Notes
2003-07-23 00:00:00COMM BD # 30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-17 Cont ID  
Sent By shernand Date 2003-06-17 Time 15:54 Rev Time 0.00
Received By shernand Date 2003-06-17 Time 15:54 Sent To  
Notes
2003-06-17 00:00:00COMM BOARD #12

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-07 Cont ID  
Sent By pkrauss Date 2003-07-07 Time 09:22 Rev Time 0.55
Received By pkrauss Date 2003-07-07 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-16 Cont ID  
Sent By jwitmer Date 2003-09-16 Time 17:06 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2003-09-16 00:00:00OK PER K STEVENS SEE PLAN 7/28/03

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-02 Cont ID  
Sent By kstevens Date 2003-07-02 Time 07:21 Rev Time 0.75
Received By kstevens Date 2003-07-02 Time 07:21 Sent To  
Notes
2003-07-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 1, ADMIN. CODE
  
 1) SHT D-1 DEMO NOTES #6 NOT FOUND,
 PLEASE CLAIRFY.
 2) SHT A-1 3 DRINKING FOUNTAINS REQUIRED
 ONLY 2 SHOWN. TABLE 403.1 - ALSO SEE
 SECTION 410.1.
 3) SHT P-1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS REQUIRED BY SECTION
 604.9 SHALL BE LOCATED NEAR THE FIXTURE
 IN AN "EFFECTIVE RANGE" NOT IN THE CEIL-
 ING AT THE TOP OF THE DROP. PDI-WH 201
 AND MANUF. INSTALL. INSTRUCTIONS.
 4) SHT P-1 GENERAL NOTES #16 - AIR
 CHAMBERS ARE NOT APPROVED. REMOVE REFER-
 ENCE. SECTION 604.9
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692