Plan Review Details - Permit 03061279
Plan Review Stops For Permit 03061279
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-09 Cont ID  
Sent By hpiskura Date 2003-07-09 Time 12:39 Rev Time 0.00
Received By hpiskura Date 2003-07-09 Time 12:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-22 Cont ID  
Sent By dpalmer Date 2003-07-22 Time 09:22 Rev Time 0.33
Received By dpalmer Date 2003-07-22 Time 09:22 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-02 Cont ID  
Sent By pkrauss Date 2003-07-21 Time 13:29 Rev Time 0.75
Received By dpalmer Date 2003-07-02 Time 12:40 Sent To  
Notes
2003-07-02 00:00:00*********** UNSAT *******************
  
 PLANS OK, ONLY SUBMITTED ONE SET FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT SECOND SET.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-07-21 Cont ID  
Sent By pkrauss Date 2003-07-21 Time 13:29 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-11 Cont ID  
Sent By mcarsill Date 2003-07-11 Time 10:15 Rev Time 0.00
Received By mcarsill Date 2003-07-11 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-22 Cont ID  
Sent By csiegber Date 2003-12-22 Time 11:39 Rev Time 0.00
Received By csiegber Date 2003-12-22 Time 11:38 Sent To M
Notes
2003-12-22 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-24 Cont ID  
Sent By shernand Date 2003-06-24 Time 10:19 Rev Time 0.00
Received By shernand Date 2003-06-24 Time 10:19 Sent To  
Notes
2003-06-24 00:00:00ADDED TO PACKET IN BOX #24, SUBMITTAL
 OF MISSING PAGE, OK PER LMARTINEZ.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-17 Cont ID  
Sent By shernand Date 2003-06-17 Time 14:45 Rev Time 0.00
Received By shernand Date 2003-06-17 Time 14:45 Sent To  
Notes
2003-06-17 00:00:00COMM BOARD #24

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2003-12-30 Time 07:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-21 Cont ID  
Sent By csiegber Date 2003-12-22 Time 11:39 Rev Time 0.55
Received By pkrauss Date 2003-07-21 Time 13:09 Sent To P
Notes
2003-07-21 00:00:00PROVISO:
  
 PLAN SHEET M-3 HVAC KEY NOTES #2, DUCT
 SMOKE DETECTOR IN RETURN AIR.PLEASE
 NOTE AS PER 2001 FBC(M)606.2.1, DUCT
 SMOKE DETECTORS SHALL BE LOCATED IN THE
 SUPPLY AIR DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-07-11 Cont ID  
Sent By pkrauss Date 2003-07-11 Time 08:10 Rev Time 0.55
Received By pkrauss Date 2003-07-11 Time 07:33 Sent To  
Notes
2003-07-11 00:00:00PLAN CHECK:
  
 PLANS APPROVED, PLEASE PROVIDE 2 SIGNED,
 SEALED AND DATED SET OF PLANS WITH
 PERMIT APPLICATION.PLEASE PROVIDE
 MANUFACTURER SUBMITTAL DATA ON THE
 NEW EQUIPMENT THAT IS TO BE INSTALLED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-07-02 Cont ID  
Sent By pkrauss Date 2003-07-22 Time 12:54 Rev Time 0.25
Received By kstevens Date 2003-07-02 Time 07:42 Sent To  
Notes
2003-07-02 00:00:00NO PLUMBING PLANS SUBMITTED - NO PLUMB-
 ING WORK BEING DONE

Review Stop Z ZONING
Rev No 1 Status N Date 2003-07-21 Cont ID  
Sent By pkrauss Date 2003-07-21 Time 13:29 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***