| Plan Review Stops For Permit 03061182 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-07-21 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-07-21 |
Time |
09:28 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
2003-07-21 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2003-07-21 00:00:00 | ADJUSTED VALUE PER SBCCI; PROCESSED FOR | | | ISSUE OF PERMIT; ADJUSTED FEES & RADON |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2003-07-15 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2003-07-10 |
Time |
18:08 |
Rev Time |
3.00 |
| Received By |
lhatten |
Date |
2003-07-12 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2003-07-15 00:00:00 | REVIEWED & STAMPED PLANS 07/12/2003 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2003-07-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2003-06-28 |
Time |
12:54 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-07-09 |
Time |
07:09 |
Sent To |
P |
|
| Notes |
| 2003-07-09 00:00:00 | ********** PROVISO ************* | | | | | | 1)NOTE: PLEASE MOVE SD INTO MASTER | | | BEDROOM. | | | | | | 2)NOTE: PLEASE SHOW LOCATION OF SERVICE | | | ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE REVISED PLAN | | | BEFORE ROUGH. | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-08-15 |
|
|
Cont ID |
|
| Sent By |
dbaxter |
Date |
2003-08-15 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
dbaxter |
Date |
2003-08-15 |
Time |
13:39 |
Sent To |
P |
|
| Notes |
| 2003-08-15 00:00:00 | TO KSTEVENS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-07-17 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-17 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-17 |
Time |
13:45 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-07-08 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-08 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-08 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2003-07-08 00:00:00 | SUBMITTAL OF PRODUCT APPROVALS ADDED TO | | | APPLICATION PACKET. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-06-17 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-06-19 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-17 |
Time |
10:34 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-09-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-09-23 |
Time |
06:45 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2003-09-23 |
Time |
06:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-07-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-21 |
Time |
07:31 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2003-07-21 |
Time |
07:13 |
Sent To |
|
|
| Notes |
| 2003-07-21 00:00:00 | PROVISO: | | | | | | 1.PLANS INDICATE MAKE-UP AIR FOR THE | | | GARAGE COMING FROM THE HOUSE.MAKE-UP | | | AIR FOR GARAGE SHALL COME FROM THE | | | OUTDOORS NOT THE RESIDENTS. | | | | | | 2.PROVIDE CALCULATIONS FOR COMBUSTION | | | AIR FOR THE LAUNDRY ROOM ON THE JOBSITE | | | AT TIME OF INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-07-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-19 |
Time |
10:47 |
Rev Time |
0.25 |
| Received By |
hmoser |
Date |
2003-07-10 |
Time |
18:08 |
Sent To |
B |
|
| Notes |
| 2003-07-10 00:00:00 | PLAN DENIED | | | NO DUCTSIZE CFM CANSIZE ON PLAN | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2003-08-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-08-16 |
Time |
11:01 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-08-16 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2003-08-16 00:00:00 | REVISION OK - SANT. RISER DIAGRAM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-07-19 |
|
|
Cont ID |
|
| Sent By |
dbaxter |
Date |
2003-08-15 |
Time |
13:39 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-07-19 |
Time |
10:47 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2003-07-10 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-17 |
Time |
13:46 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2003-07-10 |
Time |
16:49 |
Sent To |
M |
|
| Notes |
| 2003-07-10 00:00:00 | NO PLUMBING INFORMATION. RISER DIAGRAM | | | REQUIRED WITH PLUMBER'S APPLICATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
R |
Date |
2003-06-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-09 |
Time |
07:21 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2003-06-28 |
Time |
12:54 |
Sent To |
E |
|
| Notes |
| 2003-06-28 00:00:00 | NO RISER DIAGRAM. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-06-19 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-17 |
Time |
10:34 |
Rev Time |
1.00 |
| Received By |
mmclean |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
|
|