Plan Review Details - Permit 03061181
Plan Review Stops For Permit 03061181
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-21 Cont ID  
Sent By lhatten Date 2003-08-21 Time 08:42 Rev Time 1.00
Received By lhatten Date 2003-08-20 Time 08:40 Sent To  
Notes
2003-08-21 00:00:00GOT ALL PRODUCT APPROVALS & DENSITY
 PAPERS 08/19/2003

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-07 Cont ID  
Sent By kstevens Date 2003-08-16 Time 14:57 Rev Time 3.00
Received By lhatten Date 2003-07-27 Time 16:10 Sent To  
Notes
2003-08-07 00:00:00REVIEWED & STAMPED PLANS 07/27/2003

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-22 Cont ID  
Sent By btrobaug Date 2004-03-22 Time 16:06 Rev Time 0.50
Received By btrobaug Date 2004-03-22 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-15 Cont ID  
Sent By btrobaug Date 2003-08-15 Time 09:42 Rev Time 0.50
Received By btrobaug Date 2003-08-15 Time 09:42 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-07-02 Cont ID  
Sent By alange Date 2003-08-15 Time 08:17 Rev Time 1.00
Received By btrobaug Date 2003-07-02 Time 06:31 Sent To M
Notes
2003-07-02 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~`
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE #2 GROUNDING ELECTRODE CONDUCTOR
 MUST BE CONTINUOUS PER 250-64(C),REMOVE
 THE #4.
  
 2} PLEASE SHOW THE LOCATION OF THE
 SERVICE EQUIPMENT ON THE PLANS.
  
 3} THE HALLWAY OFF THE GARAGE NEEDS A
 RECEPTACLE TO COMPLY WITH 210.52(H).
  
 4} THE BREAKFAST ROOM,BEDROOM #3, FAMILY
 ROOM,LIVING ROOM ALL NEED RECEPTACLES
 ADDED TO COMPLY WITH 210.52(A).
  
 5} THE KITCHEN NEEDS RECEPTACLES TO
 COMPLY WITH 210.52.(C).
  
  
 6} BATH ROOM #4 MUST COMPLY WITH
 210.52(D).
  
 7} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 09:38 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 09:38 Sent To P
Notes
2004-03-23 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-13 Time 14:41 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 14:41 Sent To M
Notes
2004-01-13 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-09-23 Time 14:39 Rev Time 0.00
Received By csiegber Date 2003-09-23 Time 14:39 Sent To P
Notes
2003-09-23 00:00:00TO KS BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-15 Cont ID  
Sent By alange Date 2003-08-15 Time 08:16 Rev Time 0.00
Received By alange Date 2003-08-15 Time 08:16 Sent To E
Notes
2003-08-15 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-25 Cont ID  
Sent By shernand Date 2003-06-25 Time 10:43 Rev Time 0.00
Received By shernand Date 2003-06-25 Time 10:43 Sent To  
Notes
2003-06-25 00:00:00SUBMITTAL FOR MECHANICAL ADDED TO ORIGIN
 AL APPLICATION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-17 Cont ID  
Sent By mmclean Date 2003-06-19 Time 15:17 Rev Time 0.00
Received By shernand Date 2003-06-17 Time 10:33 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-23 Cont ID  
Sent By pkrauss Date 2004-01-23 Time 14:12 Rev Time 0.33
Received By pkrauss Date 2004-01-23 Time 13:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-06 Cont ID  
Sent By csiegber Date 2004-01-13 Time 14:41 Rev Time 0.25
Received By pkrauss Date 2003-07-06 Time 11:41 Sent To B
Notes
2003-07-06 00:00:00PROVISO:
  
 SUBMIT REVISED PLANS INDICATING MISSING
 DUCT SIZES PRIOR TO ROUGH INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-03-24 Cont ID  
Sent By kstevens Date 2004-03-24 Time 12:57 Rev Time 0.50
Received By kstevens Date 2004-03-24 Time 12:57 Sent To  
Notes
2004-03-24 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-10-06 Cont ID  
Sent By csiegber Date 2004-03-23 Time 09:38 Rev Time 0.50
Received By kstevens Date 2003-10-06 Time 17:19 Sent To  
Notes
2003-10-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN. PLEASE SUBMIT A
 SANT. RISER DIAGRAM THAT REFLECTS THE
 FLOOR PLAN. 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-08-18 Cont ID  
Sent By csiegber Date 2003-09-23 Time 14:39 Rev Time 0.33
Received By kstevens Date 2003-08-18 Time 11:14 Sent To  
Notes
2003-08-18 00:00:00REVISION REQUIRED - LAUNDRY SINK & WASH
 MACHINE ON DIFFERENT WALLS - SEPARATE
 STACKS REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-08-16 Cont ID  
Sent By kstevens Date 2003-08-16 Time 14:57 Rev Time 0.33
Received By kstevens Date 2003-08-16 Time 14:57 Sent To B
Notes
2003-08-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS, CHAPTER
 ONE.
  
 1) COMMENT FROM PREVIOUS REVIEW NOT
 ADDRESSED.
 1) WASH MACHINE AND LAUNDRY SINK ARE
 NOT ON THE SAME WALL. SEPARATE STACKS
 ARE REQUIRED. (SEE RED LINE CORRECTIONS
 WASH MACHINE NOT CALLED OUT ON RISER.
 A CLEANOUT IS REQUIRED ON W/M STACK 4'
 ABOVE FLOOR FOR ACCESS.)-MANY PIPE
 SIZES NOT SHOWN- MANY FIXTURES NOT
 CALLED OUT ON RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-28 Cont ID  
Sent By btrobaug Date 2003-08-15 Time 09:42 Rev Time 0.50
Received By jleech Date 2003-06-28 Time 12:09 Sent To E
Notes
2003-06-28 00:00:00DENIED;
 SANITARY RISER DIAGRAM NOT TO CODE.
 1.W/M AND L/T ARE NOT ON THE SAME WALL
 TWO STACKS REQUIRE.
 2.BATH TWO, SHR IS NOT VENTED.
 3.BIDET IS NOT VENTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2003-06-23 Cont ID  
Sent By mmclean Date 2003-06-23 Time 15:25 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-06-19 Cont ID  
Sent By shernand Date 2003-06-17 Time 10:33 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
2003-06-19 00:00:006/19/03 DENIED, SURVEY DOES NOT MATCH
 APPLICATION CALL CONT MM