| 2003-07-28 00:00:00 | DENIED BY BUILDING |
| | |
| | 1)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) REVISE NOTE #11 UNDER PLAN NOTES ON |
| | C1 TO INCLUDE AREAS IN THE WIND BORNE |
| | DEBRIS REGIONS WHICH REQUIRE IMPACT |
| | PROTECTION FOR GLAZED OPENINGS. SEE |
| | FBC 1606.1.4 |
| | |
| | 4) REVISE NOTE #15 UNDER FRAMING NOTES |
| | ON C1 TO SPECIFY THAT HIGH RIB METAL |
| | LATH IS REQUIRED TO BE ATTACHED AT EACH |
| | RIB (4"O.C.) PER ASTM C 1063. |
| | |
| | 5) INDICATE ON THE PLANS THAT THE GLASS |
| | BLOCK AT THE TUB IN THE MASTER BATHROOM |
| | IS REQUIRED TO HAVE A MINIMUM UNIFORM |
| | FACE THICKNESS OF 0.25" AS REQUIRED BY |
| | FBC 2405.2.2(5) FOR GLAZING IN HAZARDOUS |
| | LOCATIONS. |
| | |
| | 6) THE BONUS ROOM DOES NOT HAVE AN |
| | EMERGENCY EGRESS WINDOW AS REQUIRED BY |
| | FBC 1005.4. INDICATE ON THE PLANS THAT |
| | THIS ROOM IS NOT TO BE USED AS A |
| | SLEEPING ROOM. |
| | |
| | 7) THE ELEVATIONS DO NOT CORRESPOND TO |
| | THE FLOOR PLANS. THEY ARE REVERSED. |
| | PLEASE CORRECT. |
| | |
| | 8) SPECIFY THE LENGTH/EMBEDDMENT DEPTH |
| | OF THE 1/2" ANCHOR BOLTS FOR THE GARAGE |
| | DOOR BUCKS ON A4. |
| | |
| | 9) REVISE THE SLIDING GLASS DOOR BUCK |
| | DETAIL ON A4 TO CLARIFY THAT THE TAPCONS |
| | ARE TO FASTEN THROUGH THE BUCKS INTO THE |
| | STRUCTURAL SUBSTRATE. |
| | |
| | 10) REVISE THE TRUSS CONECTOR SCHEDULE |
| | ON A6 TO VALUES THAT DO NOT INCLUDE A |
| | ONE-THIRD INCREASE FOR THE STEEL |
| | CALCULATIONS, WHICH IS NO LONGER ALLOWED |
| | BY FBC 1609.4. SEE THE 2003 USP CATALOG. |
| | |
| | 11) REVISE THE UPLIFT VALUES FOR THE |
| | CONNECTORS LISTED IN DETAILS 2, 13 AND |
| | 14 ON A5. SEE 2003 USP CATALOG. |
| | |
| | 12) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SLIDING GLASS DOORS (THE ONE THAT WAS |
| | SUBMITTED HAS EXPIRED) |
| | |
| | 13) PLEASE CORRECT THE EXPOSURE CATEGORY |
| | LISTED ON C1. EXPOSURE D IS FOR AREAS |
| | EXPOSED TO ONE MILE OF OPEN WATER. THE |
| | CORRECT CATEGORY IS B. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |