Plan Review Details - Permit 03061157
Plan Review Stops For Permit 03061157
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-08-06 Cont ID  
Sent By rmcdouga Date 2003-08-06 Time 12:28 Rev Time 2.50
Received By rmcdouga Date 2003-08-06 Time 12:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-28 Cont ID  
Sent By alange Date 2003-08-04 Time 16:16 Rev Time 4.00
Received By rmcdouga Date 2003-07-28 Time 07:49 Sent To  
Notes
2003-07-28 00:00:00DENIED BY BUILDING
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) REVISE NOTE #11 UNDER PLAN NOTES ON
 C1 TO INCLUDE AREAS IN THE WIND BORNE
 DEBRIS REGIONS WHICH REQUIRE IMPACT
 PROTECTION FOR GLAZED OPENINGS. SEE
 FBC 1606.1.4
  
 4) REVISE NOTE #15 UNDER FRAMING NOTES
 ON C1 TO SPECIFY THAT HIGH RIB METAL
 LATH IS REQUIRED TO BE ATTACHED AT EACH
 RIB (4"O.C.) PER ASTM C 1063.
  
 5) INDICATE ON THE PLANS THAT THE GLASS
 BLOCK AT THE TUB IN THE MASTER BATHROOM
 IS REQUIRED TO HAVE A MINIMUM UNIFORM
 FACE THICKNESS OF 0.25" AS REQUIRED BY
 FBC 2405.2.2(5) FOR GLAZING IN HAZARDOUS
 LOCATIONS.
  
 6) THE BONUS ROOM DOES NOT HAVE AN
 EMERGENCY EGRESS WINDOW AS REQUIRED BY
 FBC 1005.4. INDICATE ON THE PLANS THAT
 THIS ROOM IS NOT TO BE USED AS A
 SLEEPING ROOM.
  
 7) THE ELEVATIONS DO NOT CORRESPOND TO
 THE FLOOR PLANS. THEY ARE REVERSED.
 PLEASE CORRECT.
  
 8) SPECIFY THE LENGTH/EMBEDDMENT DEPTH
 OF THE 1/2" ANCHOR BOLTS FOR THE GARAGE
 DOOR BUCKS ON A4.
  
 9) REVISE THE SLIDING GLASS DOOR BUCK
 DETAIL ON A4 TO CLARIFY THAT THE TAPCONS
 ARE TO FASTEN THROUGH THE BUCKS INTO THE
 STRUCTURAL SUBSTRATE.
  
 10) REVISE THE TRUSS CONECTOR SCHEDULE
 ON A6 TO VALUES THAT DO NOT INCLUDE A
 ONE-THIRD INCREASE FOR THE STEEL
 CALCULATIONS, WHICH IS NO LONGER ALLOWED
 BY FBC 1609.4. SEE THE 2003 USP CATALOG.
  
 11) REVISE THE UPLIFT VALUES FOR THE
 CONNECTORS LISTED IN DETAILS 2, 13 AND
 14 ON A5. SEE 2003 USP CATALOG.
  
 12) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SLIDING GLASS DOORS (THE ONE THAT WAS
 SUBMITTED HAS EXPIRED)
  
 13) PLEASE CORRECT THE EXPOSURE CATEGORY
 LISTED ON C1. EXPOSURE D IS FOR AREAS
 EXPOSED TO ONE MILE OF OPEN WATER. THE
 CORRECT CATEGORY IS B.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-07 Cont ID  
Sent By jleech Date 2003-06-28 Time 13:45 Rev Time 0.33
Received By dpalmer Date 2003-07-07 Time 07:21 Sent To M
Notes
2003-07-07 00:00:00************ PROVISO/REVISION***********
  
 1)NOTE: PLEASE SEE MISSING SD OUTSIDE
 MASTER BEDROOM. NFPA-72 8-1
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GRND FROM MAIN DISC TO PANEL. SIZE PER
 250-122
  
 3)NOTE: PLEASE SEE MISSING MAIN DISC
 ON PLAN AS SHOWN ON RISER DIAGRAM.
  
 4)NOTE: PLEASE SEE MISSIN REQ`D LT IN
 MASTER BATHRROM WATER CLOSET AREA.
 210-70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-17 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:19 Rev Time 0.00
Received By csiegber Date 2004-02-17 Time 16:18 Sent To M
Notes
2004-02-17 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 16:16 Rev Time 0.00
Received By alange Date 2003-08-04 Time 16:16 Sent To B
Notes
2003-08-04 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-18 Cont ID  
Sent By mmclean Date 2003-06-19 Time 14:58 Rev Time 0.00
Received By shernand Date 2003-06-18 Time 10:59 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-01 Cont ID  
Sent By pkrauss Date 2004-03-01 Time 12:08 Rev Time 0.33
Received By pkrauss Date 2004-03-01 Time 11:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-08 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:19 Rev Time 0.50
Received By hmoser Date 2003-07-08 Time 19:37 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-28 Cont ID  
Sent By jleech Date 2003-06-28 Time 13:45 Rev Time 0.33
Received By jleech Date 2003-06-28 Time 13:45 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-19 Cont ID  
Sent By shernand Date 2003-06-18 Time 10:59 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***