Plan Review Details - Permit 03061039
Plan Review Stops For Permit 03061039
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-09 Cont ID  
Sent By hpiskura Date 2003-07-09 Time 11:37 Rev Time 0.00
Received By hpiskura Date 2003-07-09 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-08-27 Cont ID  
Sent By dpalmer Date 2003-08-27 Time 19:28 Rev Time 0.33
Received By dpalmer Date 2003-08-27 Time 19:28 Sent To  
Notes
2003-08-27 00:00:00********** NOTES REDLINED ***********
  
 1)NOTE: PLANS ARE MISSING CIRCUITING
 FOR 2 RECETS, ALSO EM/ EXTS NOT SHOWN
 PER 700.12E

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-23 Cont ID  
Sent By dpalmer Date 2003-07-23 Time 13:01 Rev Time 0.50
Received By dpalmer Date 2003-07-23 Time 12:58 Sent To  
Notes
2003-07-23 00:00:00********** PROVISO/ REVISION *******
  
 1)NOTE: PLEASE SEE REDLINED PLANS FOR
 ITEMS MISSING AND THAT ARE REQ'D UNDER
 NEC.
 SIGN CIRCUIT REQ'D PER 600-5
 SHOW WINDOW RECEPTS REQ'D UNDER 210.62
 CIRCUITING FOR EM/EXT LTS 700-12E
  
 PLEASE REVISE PLANS AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW BEFORER ROUGH
 ELECTRICAL INSPECTION.
 PLEASE INLCUDE ANY OTHER REVISIONS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-07-21 Cont ID  
Sent By dpalmer Date 2003-07-21 Time 14:19 Rev Time 0.33
Received By dpalmer Date 2003-07-21 Time 14:19 Sent To  
Notes
2003-07-21 00:00:00*************** UNSAT *****************
  
 PLEASE SEE NOTES FROM FIRST REVIEW.
 PLEASE ADDRESS SAME NOTES.
  
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-19 Cont ID  
Sent By dpalmer Date 2003-06-19 Time 15:15 Rev Time 0.50
Received By dpalmer Date 2003-06-19 Time 15:15 Sent To  
Notes
2003-06-19 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE SHOW AND INCLUDE ALL
 CIRCUITING ON PLANS AND CORRELATE WITH
 A PANEL SCHEDULE TO BE SUBMITTED.
  
 2)NOTE: PLEASE CIRCUIT EM/EXT LTS PER
 700-12E
  
 3)NOTE: PLEASE INCLUDE INFORMATION ON
 TITLE BLOCK OF ARCH. AS REQ`D UNDER FS
 AND FAC 481 & 61G1-16.004 LICENSE # ETC.
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT REQ`D PER 600-5
  
 5)NOTE: PLEASE SHOW "SHOW" DISPLAY
 REQ`D RECEPTS 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-09-02 Cont ID  
Sent By nmccray Date 2003-09-02 Time 15:56 Rev Time 0.00
Received By nmccray Date 2003-09-02 Time 15:56 Sent To  
Notes
2003-09-02 00:00:00REVISION DATED FOR 8/25/03

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-25 Cont ID  
Sent By mcarsill Date 2003-07-25 Time 15:38 Rev Time 0.00
Received By mcarsill Date 2003-07-25 Time 15:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-07-10 Cont ID  
Sent By shernand Date 2003-07-10 Time 09:51 Rev Time 0.00
Received By shernand Date 2003-07-10 Time 09:51 Sent To  
Notes
2003-07-10 00:00:00OKAY PER MIKE CARSILLO

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-26 Cont ID  
Sent By csiegber Date 2003-08-26 Time 13:34 Rev Time 0.00
Received By csiegber Date 2003-08-26 Time 13:34 Sent To  
Notes
2003-08-26 00:00:00ON COMM BD #29

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-21 Cont ID  
Sent By shernand Date 2003-07-21 Time 09:03 Rev Time 0.00
Received By shernand Date 2003-07-21 Time 09:03 Sent To  
Notes
2003-07-21 00:00:00COMM BOARD #26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:55 Rev Time 0.00
Received By shernand Date 2003-06-13 Time 16:55 Sent To  
Notes
2003-06-13 00:00:00COMM BOARD #15

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-09-03 Cont ID  
Sent By lmartine Date 2003-09-03 Time 16:25 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-09-03 00:00:00OK TO APPROVE, ENGINEERS SEAL WAS
 APPLIED LM

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-09-03 Cont ID  
Sent By pkrauss Date 2003-08-28 Time 06:34 Rev Time 0.25
Received By dbaxter Date 2003-08-28 Time 06:34 Sent To  
Notes
2003-08-28 00:00:00DENIED:
  
 PLEASE NOTE ONLY ONE COPY OF THE
 MECHANICAL PLANS SUBMITTED ARE SEALED.
 PLEASE SEAL THE SECOND SET OF
 MECHANICAL PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-26 Cont ID  
Sent By pkrauss Date 2003-07-26 Time 11:37 Rev Time 0.40
Received By pkrauss Date 2003-07-26 Time 11:34 Sent To  
Notes
2003-07-26 00:00:00ADDING 1 DROP TO EXISTING SPACE/EXISTING
 EQUIPMENT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-07-07 Cont ID  
Sent By pkrauss Date 2003-07-07 Time 07:55 Rev Time 0.35
Received By pkrauss Date 2003-07-07 Time 07:55 Sent To  
Notes
2003-07-07 00:00:00DENIED:
 INSUFFICIENT INFORMATION -
 1.PLEASE PROVIDE INFORMATION ON THE
 "TREATMENT" ROOM.WILL ADDITIONAL
 EXHAUST BE NEEDED FOR CHEMICALS OMITTING
 NOXIOUS FUMES?
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-30 Cont ID  
Sent By kstevens Date 2003-07-30 Time 11:31 Rev Time 0.50
Received By kstevens Date 2003-07-30 Time 11:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By kstevens Date 2003-07-01 Time 09:27 Rev Time 0.50
Received By kstevens Date 2003-07-01 Time 09:27 Sent To  
Notes
2003-07-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS TO FBC,
 CHAPTER 1, ADMIN. CODE
 FBC-2001 CHAPTER 11
  
 1) SECTION 104.2.1 SUBMIT A SANITARY
 RISER DIAGRAM AND A WATER RISER DIAGRAM.
 SHOW ALL PIPE SIZES, TYPE OF MATERIAL,
 VENTING, AND WATER HAMMER ARRESTORS ECT.
 2) SUBMIT DETAIL FOR TOILET ROOM SHOWING
 CLEAR FLOOR SPACE, (11-4.16.2), HEIGHT,
 (11-4.16.3), GRAB BARS, (1104.16.4),
 FLUSH CONTROLS, (11-4.16.5) FOR THE W/C.
 W/C SHALL BE LOCATED 18" FROM CENTER OF
 FIXTURE TO SIDE WALL. SHOW CLEAR FLOOR
 SPACE, (11-4.19.3), HEIGHT, (11-4.19.2),
 EXPOSED PIPES AND SURFACES, (11-4.19.4),
 AND FAUCETS, (11-4.19.5).
 3) IF NOT EXISTING, AN RPZ BACKFLOW IS
 REQUIRED ON WATER SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692