| Plan Review Stops For Permit 03061039 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2003-07-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-07-09 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-07-09 |
Time |
11:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-08-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-08-27 |
Time |
19:28 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-08-27 |
Time |
19:28 |
Sent To |
|
|
| Notes |
| 2003-08-27 00:00:00 | ********** NOTES REDLINED *********** | | | | | | 1)NOTE: PLANS ARE MISSING CIRCUITING | | | FOR 2 RECETS, ALSO EM/ EXTS NOT SHOWN | | | PER 700.12E |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-07-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-23 |
Time |
13:01 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-07-23 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2003-07-23 00:00:00 | ********** PROVISO/ REVISION ******* | | | | | | 1)NOTE: PLEASE SEE REDLINED PLANS FOR | | | ITEMS MISSING AND THAT ARE REQ'D UNDER | | | NEC. | | | SIGN CIRCUIT REQ'D PER 600-5 | | | SHOW WINDOW RECEPTS REQ'D UNDER 210.62 | | | CIRCUITING FOR EM/EXT LTS 700-12E | | | | | | PLEASE REVISE PLANS AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW BEFORER ROUGH | | | ELECTRICAL INSPECTION. | | | PLEASE INLCUDE ANY OTHER REVISIONS. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-07-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-21 |
Time |
14:19 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-07-21 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2003-07-21 00:00:00 | *************** UNSAT ***************** | | | | | | PLEASE SEE NOTES FROM FIRST REVIEW. | | | PLEASE ADDRESS SAME NOTES. | | | | | | PLEASE SUBMIT FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-06-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-06-19 |
Time |
15:15 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-06-19 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2003-06-19 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW AND INCLUDE ALL | | | CIRCUITING ON PLANS AND CORRELATE WITH | | | A PANEL SCHEDULE TO BE SUBMITTED. | | | | | | 2)NOTE: PLEASE CIRCUIT EM/EXT LTS PER | | | 700-12E | | | | | | 3)NOTE: PLEASE INCLUDE INFORMATION ON | | | TITLE BLOCK OF ARCH. AS REQ`D UNDER FS | | | AND FAC 481 & 61G1-16.004 LICENSE # ETC. | | | | | | 4)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | SIGN CIRCUIT REQ`D PER 600-5 | | | | | | 5)NOTE: PLEASE SHOW "SHOW" DISPLAY | | | REQ`D RECEPTS 210-62 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2003-09-02 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-09-02 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-09-02 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2003-09-02 00:00:00 | REVISION DATED FOR 8/25/03 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-07-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-07-25 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-07-25 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2003-07-10 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-10 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-10 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2003-07-10 00:00:00 | OKAY PER MIKE CARSILLO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-08-26 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-08-26 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-08-26 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2003-08-26 00:00:00 | ON COMM BD #29 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-07-21 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-21 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-21 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2003-07-21 00:00:00 | COMM BOARD #26 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-06-13 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-13 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-13 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2003-06-13 00:00:00 | COMM BOARD #15 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2003-09-03 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2003-09-03 |
Time |
16:25 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-09-03 00:00:00 | OK TO APPROVE, ENGINEERS SEAL WAS | | | APPLIED LM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2003-09-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-08-28 |
Time |
06:34 |
Rev Time |
0.25 |
| Received By |
dbaxter |
Date |
2003-08-28 |
Time |
06:34 |
Sent To |
|
|
| Notes |
| 2003-08-28 00:00:00 | DENIED: | | | | | | PLEASE NOTE ONLY ONE COPY OF THE | | | MECHANICAL PLANS SUBMITTED ARE SEALED. | | | PLEASE SEAL THE SECOND SET OF | | | MECHANICAL PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-07-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-26 |
Time |
11:37 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-07-26 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2003-07-26 00:00:00 | ADDING 1 DROP TO EXISTING SPACE/EXISTING | | | EQUIPMENT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-07-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-07 |
Time |
07:55 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-07-07 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2003-07-07 00:00:00 | DENIED: | | | INSUFFICIENT INFORMATION - | | | 1.PLEASE PROVIDE INFORMATION ON THE | | | "TREATMENT" ROOM.WILL ADDITIONAL | | | EXHAUST BE NEEDED FOR CHEMICALS OMITTING | | | NOXIOUS FUMES? | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-07-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-30 |
Time |
11:31 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-07-30 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-07-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-01 |
Time |
09:27 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-07-01 |
Time |
09:27 |
Sent To |
|
|
| Notes |
| 2003-07-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 AMENDMENTS TO FBC, | | | CHAPTER 1, ADMIN. CODE | | | FBC-2001 CHAPTER 11 | | | | | | 1) SECTION 104.2.1 SUBMIT A SANITARY | | | RISER DIAGRAM AND A WATER RISER DIAGRAM. | | | SHOW ALL PIPE SIZES, TYPE OF MATERIAL, | | | VENTING, AND WATER HAMMER ARRESTORS ECT. | | | 2) SUBMIT DETAIL FOR TOILET ROOM SHOWING | | | CLEAR FLOOR SPACE, (11-4.16.2), HEIGHT, | | | (11-4.16.3), GRAB BARS, (1104.16.4), | | | FLUSH CONTROLS, (11-4.16.5) FOR THE W/C. | | | W/C SHALL BE LOCATED 18" FROM CENTER OF | | | FIXTURE TO SIDE WALL. SHOW CLEAR FLOOR | | | SPACE, (11-4.19.3), HEIGHT, (11-4.19.2), | | | EXPOSED PIPES AND SURFACES, (11-4.19.4), | | | AND FAUCETS, (11-4.19.5). | | | 3) IF NOT EXISTING, AN RPZ BACKFLOW IS | | | REQUIRED ON WATER SERVICE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|