Plan Review Details - Permit 03061031
Plan Review Stops For Permit 03061031
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-06-23 Cont ID  
Sent By alange Date 2004-06-23 Time 11:43 Rev Time 0.25
Received By alange Date 2004-06-23 Time 11:43 Sent To  
Notes
2004-06-23 00:00:00WINOW SUBMITTAL OK PER DR

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-15 Cont ID  
Sent By rmcdouga Date 2003-09-15 Time 10:51 Rev Time 3.00
Received By rmcdouga Date 2003-09-15 Time 10:51 Sent To  
Notes
2003-09-15 00:00:00PROVISO
  
 1) SUBMIT A REVISED SITE PLAN THAT
 MATCHES THE SURVEY.
  
 2) SUBMIT A SIGNED AND SEALED LETTER
 FROM THE ARCHITECT TO ACCOMPANY THE SITE
 SPECIFIC PRODUCT APPROVAL FORM.
  
 3) HURRICANE PANELS WILL BE UNDER A
 SEPARATE PERMIT.
  
 4) SUBMIT REVISED SHEETS SPECIFYING THE
 LINTELS OR BEAMS TO BE USED BETWEEN THE
 SLIDING GLASS DOORS AND THE ARCHED FIXED
 GLASS WINDOWS IN THE LIVING ROOM THAT
 WERE CHANGED TO COMPLY WITH FBC TABLE
 600 ISSUES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-08-15 Cont ID  
Sent By mmclean Date 2003-09-15 Time 10:27 Rev Time 2.00
Received By rmcdouga Date 2003-08-06 Time 13:08 Sent To  
Notes
2003-08-06 00:00:00DENIED
  
 1) ONLY ITEMS 1,2 AND 21 FROM THE FIRST
 REVIEW COMMENTS HAVE BEEN ADDRESSED. THE
 OTHER TWENTY ITEMS MUST BE CORRECTED
 BEFORE A PERMIT WILL BE ISSUED.
  
 PLEASE CALL IF YOU HAVE ANY QUESTIONS.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-23 Cont ID  
Sent By alange Date 2003-08-04 Time 16:15 Rev Time 6.00
Received By rmcdouga Date 2003-07-23 Time 13:30 Sent To  
Notes
2003-07-23 00:00:00DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) CITY OF W.P.B. IS IN THE WIND BOURNE
 DEBRIS REGION WHICH REQUIRES IMPACT
 PROTECTION ON GLAZED OPENINGS. PLEASE
 REVISE NOTE #11 UNDER PLAN NOTES ON C1.
  
 4) ASTM C 1063 REQUIRES HIGH RIB LATH TO
 BE FASTENED AT EVERY RIB (4"O.C.).
 PLEASE REVISE NOTE #15 UNDER FRAMING
 NOTES ON C1.
  
 5)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE INTERNAL PRESSURE
 COEFFICIENT ON PLANS.
  
 6) THE LIVING ROOM WALL AT THE RIGHT
 ELEVATION EXCEEDS THE 40% OF WALL AREA
 ALLOWED AS OPENINGS BY FBC TABLE 600.
 (95.98 SQFT ALLOWED / 138.45 SQFT OF
 OPENINGS)
  
 7) THE ELEVATIONS ON A4 AND A5 SHOW A
 SMALL DETACHED GARAGE AT THE FRONT OF
 THE STRUCTURE THAT IS NOT INDICATED
 ANYWHERE ELSE ON THE PLANS. PLEASE
 CLARIFY.
  
 8) THE SECOND FLOOR WOOD FRAME WALL AND
 FLOOR TRUSS SYSTEM AT THE SOUTH SIDE OF
 THE STRUCTURE THAT ARE WITHIN 3 FEET OF
 THE PROPERTY LINE ARE REQUIRED TO BE ONE
 HOUR FIRE RATED ASSEMBLIES BASED ON
 INTERIOR AND EXTERIOR FIRE EXPOSURE.
 PROVIDE DETAIL DRAWING INDICATING
 SYSTEMS THAT WILL BE USED. SEE FBC TABLE
 600.
  
 9) SITE PLAN ON S1 DOES NOT COORESPOND
 WITH THE SURVEY. PLEASE CORRECT.
  
 10) FBC CHAPTER 11 REQUIRES AT LEAST ONE
 BATHROOM ON HABITABLE GRADE WITH A DOOR
 THAT HAS A 29" CLEAR OPENING. THE DOOR
 TO THE TOILET FACILITIES DOES NOT MEET
 THIS REQUIREMENT. PLEASE CORRECT.
  
 11) SPECIFY THE LENGTH/EMBEDMENT DEPTH
 OF THE 1/2" ANCHOR BOLTS ON THE GARAGE
 DOOR JAMB DETAIL ON A4.
  
 12) FBC 1609.4 NO LONGER ALLOWS THE ONE
 THIRD INCREASE FOR STEEL CALCULATIONS.
 REVISE TRUSS CONNECTOR SCHEDULE ON A10
 TO VALUES THAT DO NOT INCLUDE THE
 INCREASE. SEE THE 2003 USP CATALOG.
  
 13) DETAIL 27 ON A14 SPECIFIES A SEMCO
 HANGER. SEMCO WAS PURCHASED BY USP.
 PLEASE SPECIFY AN APPROPRIATE MASONRY
 HANGER FROM THE CURRENT CATALOG.
  
 14) REVISE CONNECTION DETAILS 2 AND 3 ON
 A14 TO VALUES WITH NO INCREASE IN STEEL
 CALCS. SEE 2003 USP CATALOG.
  
 15) REVISE VALUES FOR THE"USP" USC
 CONNECTOR WITH 4 BOLTS IN DETAIL 7 ON
 A14. SEE 2003 USP CATALOG.
  
 16) UPDATE THE SEMCO HANGER SPECIFIED IN
 DETAIL 23 ON A14 TO APPROPRIATE HANGER
 FROM CURRENT CATALOG.
  
 17) THE ATTIC ACCESS SPECIFIED IN THE
 GARAGE IS LOCATED BELOW THE FLOOR
 TRUSSES. PLEASE CLARIFY.
  
 18) INDICATE ON DETAIL 5 ON A14, THE
 TUBE STEEL HEADER, THE THICKNESS OF THE
 TUBE STEEL WALLS, THE TUBE DIMENSIONS,
 THE WELD TYPE, ETC.
  
 19) SOME OF THE LINE DRAWINGS AT THE
 OPENINGS AND ROOF OVERHANG ARE MISSING
 ON SHEET A8.
  
 20) ON SHEET A7 THE DETAIL FOR THE TUBE
 STEEL HEADER (5 ON A14) IS INDICATED AT
 THE DINING ROOM WINDOWS (#31 & #32).
 HOWEVER,IT IS NOT LABELED ON THE PLAN AS
 IT IS AT THE TWO OTHER OPENINGS AND THE
 ELEVATION DOES NOT INDICATE THE 4" SPACE
 BETWEEN THESE WINDOWS. PLEASE CLARIFY.
  
 21) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE OUTSWING DOOR AT P.R.
 - SLIDING GLASS DOORS (ONE SUBMITTED HAS
 EXPIRED)
 - DOUBLE FRENCH DOORS AT SECOND FLOOR
 BEDROOM/DEN
  
 22) THE KEY PLAN AND INSTALLATION
 SCHEDULE THAT WAS SUBMITTED DOES NOT
 CORRESPOND TO THE PLANS. SUBMIT A KEY
 PLAN AND INSTALLATION SCHEDULE. SPECIFY
 THE ANCHORS THAT WILL BE USED AND THEIR
 SPACINGS. NOTE: SECOND FLOOR REQUIRES
 ANCHORS FOR WOOD IN SOME LOCATIONS.
  
 23) SITE SPECIFIC PRODUCT APPROVAL FOR
 BUTT GLAZING IS NOT ACCEPTABLE. THE FORM
 IS REQUIRED TO BE SEALED BY THE DESIGNER
 OF RECORD OR A SIGNED AND SEALED LETTER
 REFERENCING THE SPECIFIC PRODUCT,
 LOCATION OF PROJECT, ETC. THE FORM IS
 REQUIRED TO LIST THE SPECIFIC SITE WHERE
 THE PRODUCT WILL BE INSTALLED. THE
 INFORMATION THAT IS LISTED ON THE FORM
 IS REQUIRED TO BE FOR THE PRODUCT THAT
 IS TO BE INSTALLED. THE INFORMATION ON
 THE FORM THAT WAS SUBMITTED IS NOT FOR
 THE ASSEMBLY THAT WILL BE INSTALLED.
 SUBMIT ALL SUBSTANTIATING DATA,
 CALCULATIONS, RATIONAL ANALYSIS AND TEST
 DATA THAT YOU ARE USING TO DETERMINE
 THAT THIS BUTT GLASS ASSEMBLY WILL
 COMPLY WITH FBC 2406.2, 1606 AND 1707.4.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-06-30 Cont ID  
Sent By jleech Date 2003-06-28 Time 10:32 Rev Time 0.50
Received By btrobaug Date 2003-06-30 Time 08:10 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-28 Cont ID  
Sent By csiegber Date 2004-06-28 Time 15:53 Rev Time 0.00
Received By csiegber Date 2004-06-28 Time 15:53 Sent To P
Notes
2004-06-28 00:00:00TO GAS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-10 Cont ID  
Sent By csiegber Date 2003-09-10 Time 14:01 Rev Time 0.00
Received By csiegber Date 2003-09-10 Time 14:01 Sent To B
Notes
2003-09-10 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-04 Cont ID  
Sent By alange Date 2003-08-04 Time 16:15 Rev Time 0.00
Received By alange Date 2003-08-04 Time 16:15 Sent To B
Notes
2003-08-04 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-16 Cont ID  
Sent By mmclean Date 2003-06-18 Time 14:47 Rev Time 0.00
Received By shernand Date 2003-06-16 Time 13:26 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-01 Cont ID  
Sent By btrobaug Date 2003-06-30 Time 08:48 Rev Time 0.25
Received By pkrauss Date 2003-07-01 Time 08:00 Sent To B
Notes
2003-07-01 00:00:00MECHANICAL PERMIT 03061042

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-28 Cont ID  
Sent By csiegber Date 2004-06-28 Time 15:53 Rev Time 0.33
Received By jleech Date 2003-06-28 Time 10:31 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-09-15 Cont ID  
Sent By mmclean Date 2003-09-15 Time 10:27 Rev Time 0.00
Received By mmclean Date   Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-06-18 Cont ID  
Sent By shernand Date 2003-06-16 Time 13:26 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
2003-06-18 00:00:006/18/03 DENIED, NEED COPY OF SURVEY WITH
 HOUSE OUTLINED AND ALL SETBACKS CALL
 CONTR MM