Review Stop P PLUMBING
Rev No 2 Status P Date 2003-06-27 Cont ID  
Sent By kstevens Date 2003-06-27 Time 15:18 Rev Time 1.50
Received By kstevens Date 2003-06-27 Time 15:18 Sent To  
Notes
2003-06-27 00:00:00 
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-21 Cont ID  
Sent By shernand Date 2003-06-26 Time 09:27 Rev Time 1.00
Received By kstevens Date 2003-06-21 Time 07:32 Sent To  
Notes
2003-06-21 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) SECTION 404.3 PLASTIC PIPE, TUBING, &
 FITTINGS SHALL BE USED OUTSIDE UNDER-
 GROUND ONLY.
 2) SECTION 404.10 VENT REQUIRED FOR
 SLEEVE.
 3. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 4. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS