Plan Review Details - Permit 03061027
Plan Review Stops For Permit 03061027
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-03 Cont ID  
Sent By btrobaug Date 2003-07-01 Time 17:07 Rev Time 1.00
Received By sthyng Date 2003-07-03 Time 08:29 Sent To  
Notes
2003-07-03 00:00:00*****PROVISO******
 SUBMIT A REVISION
 SPECIFYING ATTACHMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-06-27 Time 15:56 Rev Time 0.50
Received By btrobaug Date 2003-07-01 Time 16:07 Sent To B
Notes
2003-07-01 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THIS ELECTRICAL PERMIT IS ISSUED TO
 ALLOW WORK TO PROCEED.ELECTRICAL FLOOR
 PLANS INDICATING THE AREAS OF WORK AND
 SHOWING COMPLIANCE WITH THE 2002 NEC,ARE
 TO BE SUBMITTED FOR REVIEW PRIOR TO
 ROUGH ELECTRICAL INSPECTION.THESE
 REVIEWED PLANS WILL BE POSTED ON THE
 JOB SITE AT THE TIME OF INSPECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-06-27 Time 15:56 Rev Time 0.00
Received By shernand Date 2003-06-27 Time 15:56 Sent To E
Notes
***NONE***