Plan Review Details - Permit 03060845
Plan Review Stops For Permit 03060845
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-11-29 Cont ID  
Sent By sthyng Date 2003-11-29 Time 16:38 Rev Time 1.50
Received By sthyng Date 2003-11-29 Time 16:18 Sent To P
Notes
2003-11-29 00:00:00PROVISO - SUBMIT GABLE VENT PRODUCT
 APPROVAL BEFORE INSTALLATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-14 Cont ID  
Sent By csiegber Date 2003-11-24 Time 16:21 Rev Time 1.50
Received By sthyng Date 2003-11-14 Time 11:16 Sent To  
Notes
2003-11-14 00:00:00*****CORRECTIONS*****
  
 SAMANTHA HILL (THYNG)
 BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SEPARATE PERMITS REQUIRED.
  
 3.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 4.)PROVISO WILL BE ISSUED THAT IF A
 GABLE VENT IS INSTALLED, A PRODUCT
 APPROVAL WILL BE SUBMITTED.
  
 5.)HAVE THE NEW REVISED PLANS
 APPROVED BY THE HISTORIC PRESERVATION
 DEPARTMENT.
  
 6.)ADDITIONAL FEES DUE, RADON, SEE
 BZ231379 THAT WAS PREVIOUSLY IN
 PACKAGE.
  
 7.)WHEN RETURNING TO CONTRUCTION
 SERVICES, FILL OUT REVISION/SUBMITTAL
 FORM AND SUBMIT AS A SUBMITTAL (NO
 FEE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-23 Cont ID  
Sent By btrobaug Date 2003-11-13 Time 16:25 Rev Time 3.00
Received By sthyng Date 2003-09-23 Time 08:03 Sent To  
Notes
2003-09-23 00:00:00*****CORRECTIONS******
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLIATION.233-5025
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)THE NEW EXTERIOR DOOR AT THE NEW
 DECK HAS CONFLICTING NOTES - ONE SAYS
 3060 SC, THE OTHER SAYS 3068 FRENCH
 DOOR.REVISE.
  
 5.)THE EAST WALL SECTION AND THE
 ELEVATIONS SPECIFY 3/4" STUCCO. VERTICAL
 APPLICATION OF STUCCO OVER WIRE LATH
 IS REQUIRED TO BE 3 COAT (7/8"), FBC
 2504.2.2, ASTM C1063.
  
 6.)2-SKA WALL SECTION, SIMPSON MTS12
 SHOWS A 1\\" NAIL.REVISE.
  
 7.)ENERGY CALCS REQUIRED, FBC13-103.1.
 2.SUBMIT TWO COPIES.SIGN THE OWNER/
 AGENT LINE OF THE ENERGY CALC AS WELL AS
 THE PREPARER LINE.
  
 8.)THE BOTTOM PLATE IS TO BE PRESSURE
 TREATED OR NATURALLY DURABLE WOOD,
 FBC2304.4.
  
 9.)MSTAM24 SHOULD USE 5 1/4" TITEN
 SCREWS (NOT 4 1/2"), REFER TO SIMPSON
 2003 CATALOG (2-SKA AND 1-A3).
  
 10.)SPECIFY FLOOR JOIST ATTACHMENT.
  
 11.)ENERGY CALCS WERE NOT SUBMITTED.
 PLEASE NOTE THAT IF A SHORT FORM 600C
 IS SUBMITTED, MINIMUM ATTIC UNDER AIR
 INSULATION IS R30.R19 IS SHOWN ON THE
 WALL SECTION 1-A3 AND SKA2.
  
 12.)A GABLE VENT IS SHOWN ON THE
 ELEVATION.IF THIS IS OPERABLE, SUBMIT
 TWO COPIES OF A PRODUCT APPROVAL.
  
 13.)THE PT 2X8 BOLTS ARE SHOWN WITH A
 1/2" DIAMETER ON 1-A3, NO SIZE ON 2-SKA.
 SHOW DIAMETER AND LENGTH ON BOTH.
  
 14.)FLOOR JOISTS LOCATED LESS THAN 18"
 TO THE EARTH SHALL BE PT OR NATURALLY
 DURABLE WOOD, FBC2304.3.4.
  
 15.)HANDRAILS SHALL BE PROVIDED ON
 BOTH SIDES OF THE RAMP, FBC1013.7.IT
 APPEARS TO HAVE TWO HANDRAILS ON THE
 SITE PLAN, MAKE A NOTE ON THE ELEVATION
 OR ELSEWHERE ON THE ARCHITECTURALS.
 ALSO SHOW HEIGHT.
  
 16.)NEW REVISED PLANS ARE TO BE
 STAMPED BY THE HISTORIC PRESERVATION
 DEPARTMENT BEFORE RESUBMITTAL.
  
 17.)FEES DUE, RADON, $.96.PAY AT
 CASHIER WITH ATTACHED BZ231379.
  
 18.)PROVIDE TWO COPIES OF PRODUCT
 APPROVALS FOR THE EXTERIOR DOOR.ROOF
 PRODUCT APPROVALS MAY BE SUBMITTED NOW
 OR WITH THE ROOF PERMIT APPLICATION.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-13 Cont ID  
Sent By btrobaug Date 2003-11-13 Time 16:25 Rev Time 0.50
Received By btrobaug Date 2003-11-13 Time 15:56 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-11-12 Time 12:00 Rev Time 0.50
Received By btrobaug Date 2003-09-17 Time 12:06 Sent To P
Notes
2003-09-17 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A RISER DIAGRAM FOR THE
 NEW SERVICE PER 215.5.
  
 NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT PER 210.63.MUST BE
 INSTALLED DUE TO CONDENSER RELOCATION.
  
 THE BATHROOM CICUIT MUST COMPLY WITH
 210.11(C)(3).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-11-24 Cont ID  
Sent By csiegber Date 2003-11-24 Time 16:21 Rev Time 0.00
Received By csiegber Date 2003-11-24 Time 16:21 Sent To B
Notes
2003-11-24 00:00:00TO ST DESK/RESUB-NO FEE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-11-29 Cont ID  
Sent By sthyng Date 2003-11-29 Time 16:19 Rev Time 0.00
Received By sthyng Date 2003-11-12 Time 11:59 Sent To  
Notes
2003-11-12 00:00:00TO BT DESK/3RD RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-09-12 Time 12:20 Rev Time 0.00
Received By sthyng Date 2003-09-12 Time 12:20 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-09 Cont ID  
Sent By mmclean Date 2003-09-12 Time 10:51 Rev Time 0.00
Received By csiegber Date 2003-09-09 Time 10:00 Sent To Z
Notes
2003-09-09 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-02 Cont ID  
Sent By csiegber Date 2003-09-02 Time 10:02 Rev Time 0.00
Received By csiegber Date 2003-09-02 Time 10:02 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 10:06 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 10:06 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-09-19 Cont ID  
Sent By kstevens Date 2003-09-19 Time 13:23 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-03 Cont ID  
Sent By sthyng Date 2003-12-03 Time 19:35 Rev Time 0.00
Received By sthyng Date 2003-12-03 Time 19:35 Sent To  
Notes
2003-12-03 00:00:00REDLINES CORRECTED BY ARCHITECT
 CHECKED OK PER PS

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-19 Cont ID  
Sent By sthyng Date 2003-11-29 Time 16:39 Rev Time 1.00
Received By kstevens Date 2003-09-19 Time 13:23 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2003-09-12 Cont ID  
Sent By mmclean Date 2003-09-12 Time 10:51 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-09-12 00:00:009/12/03 OK PER SHIRLEY MM

Review Stop Z ZONING
Rev No 2 Status F Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-09-09 Time 10:00 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-09-03 00:00:009/3/03 DENIED, 2ND CHECKLIST - DECK MUST
 BE 3' IN HEIGHT TO ENCROACH IN A
 REQUIRED SETBACK CALLED CONTR TOM
 KONRARY FILE K MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-06-13 Cont ID  
Sent By csiegber Date 2003-09-02 Time 10:02 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-06-13 00:00:006/13/03 DENIED, DECK MUST BE 3'FT IN
 HEIGHT TO ENCROACH IN A REQUIRED SET
 BACK MM