| 2003-06-17 00:00:00 | *************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE 210-52B-2, 210-11C-1 |
| | SMALL APPLIANCE CIRCUITS IN KITCHEN |
| | SHALL NOT SERVE OTHER LOADS. |
| | PANEL SCHEDULE SHOWS GARBAGE ETC. |
| | |
| | 2)NOTE: PLEASE LIST ALL THE REQ`D ARC- |
| | -FAULT PROTECTED CIRCUITS PER 210-12 |
| | |
| | 3)NOTE: PLEASE CLARIFY SOME MISSING |
| | RECEPTS PER 210-52 2',6',12' RULE. |
| | |
| | 4)NOTE: PLEASE SHOW AN ELECTRICAL RISER |
| | DIAGRAM FOR SERVICE. METER/MAIN/ SUB |
| | PANEL/CONDCUIT/SIZE/CONDUCTORS/GROUNDING |
| | ETC. 215-5 |
| | |
| | 5)NOTE: PLEASE SEE PLANS FOR MEANS OF |
| | EGRESS LIGHTING REQ`D PER 210-70 INSIDE |
| | ROOMS/ EGRESS TO OUTSIDE ETC. |
| | SHOW IF EITHER RECEPT WILL BE SWITCH |
| | OR LT OUTLETS?CONTROLS FOR BATH LTS |
| | |
| | 6)NOTE: PLEASE SHOW FRONT AND REAR RECEP |
| | TS PER 2210-52E |
| | |
| | 7)NOTE: PLEASE SEE 210-52D/210-11-C3 |
| | FOR BATH RECEPTS TO BE A MIN OF 20A AND |
| | #12 AWG. |
| | |
| | 8)NOTE: PLEASE SEE MISSING KITCHEN |
| | COUNTERSPACE RECEPT PER 210-52C1 |
| | 12" OF SPACE NEXT TO FRIG. |
| | |
| | 9)NOTE: PLEASE SEE NFPA-72 2-2.1.1.1, |
| | 8-4.1.2 REQ`D INSIDE AND OUTSIDE ALL |
| | BEDROOMS. 3' FROM KITCHENS AND BATHS. |
| | |
| | 10)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | |
| | PLEASE VERIFY SIZE OF HEATSRIP. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |