Plan Review Details - Permit 03060838
Plan Review Stops For Permit 03060838
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-03 Cont ID  
Sent By jwitmer Date 2003-07-03 Time 19:39 Rev Time 4.25
Received By jwitmer Date 2003-07-03 Time 19:39 Sent To  
Notes
2003-07-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03060838
 ADD: 203 S TAMARIND AVE
 CONT: TRI-COUNTY RAIL CONTRACTORS
 TEL: (954)520-8861
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DEMIED
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2) CITY AMENDMENT 104.2.1.3 QUALITY OF
 BUILDING PLANS SHALL BE DRAWM TO A
 MINIMUM OF 1/8"= 1'-0".
  
 3) CITY AMENDMENT 105.3 BUILDINGS THAT
 QUALIFY FOR A RESIDENT INSPECTOR.
 (3) WHERE THE CONCRETE DESIGN IS BASED
 ON COMPRESSIVE STRENGTH OF (F'C) IN
 EXCESS OF 3,000 POUNDS PER SQ IN.
  
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 5) FIRE DISTRICT F 102.1 THIS BUILDING
 IN A FIRE DISTRICT AND MUST MEET ALL THE
 CRITERIA.
  
 6) THIS STRUCTURE ALSO IS LOCATED IN A
 HISTORICAL DISTRICT AND BE APPROVED
 BEFORE THE ISSUANCE OF PLANS.
  
 7) DISCREPANCY IN CODE SUMMARY, PLANS
 INDICATE (3) STRUCTURES NOT (1),
 504 BUILDINGS LOCATED ON THE SAME LOT.
 A PROPERTY LINE SHALL BE ASSUMED BETWEEN
 THEM.
 THE OTHER ISSUE TO TRY TO TAKE AREA
 INCREASES BETWEEN BETWEEN THE 2 PLAT-
 FORMS IT CAN NOT BE TAKEN AT 100% SINCE
 THERE IS LESS THAN 60' BETWEEN PLATFORMS
  
 8) SHEET SJ-S001 WIND ANYLSIS:
 EXPOSURE C ACTUALLY IN A B CATORGORY,
  
 THE OTHER ISSUE IS MISSING THE INTERNAL
 PRESSURE COEFFICIENT, ASCE 7-98, SEE
 TABLE 6-7 FOR ENCLOSED, PARTIALLY
 ENCLOSED AND OPEN BUILDINGS.
 THE PLATFORMS BEING AN OPEN TYPE OF
 BUILDING, AND THE OVERPASS & TOWER BEING
 PARTIALLY ENCLOSED (+.55/-.55)
  
 9)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 THIS CODE SECTION WILL DEPEND ON HOW YOU
 CLASSIFY THE OVERPASS, TOWERS AND TICKET
 BOOTH.
  
 10)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) WINDOWS
 B)EXTERIOR DOORS
 C) ROOFING ASSEMBLIES
  
 11) MISSING INFORMATION 1606.1.7
 (5) COMPONENTS & CLADDING THE POS & NEG
 DESIGN PRESSURES ON OPENINGS.
 IF THE OVERPASS IS DESIGNED AS PARTIALLY
 OPEN, HOW WILL THE TOWERS TAKE THE ADDI-
 TIONAL PRESSURES, HOW WILL THE GLASS
 FRAMES SEPERATING THE ELEVATOR AND STAIR
 WELL TO TAKE THESSE PRESSURES?
  
 12) SIDEWALKS (OVERPASS)
 SECTION 1604.9 SIDEWALKS(ELEVATED)
 SIDEWALK (OVERPASS) 1604.9 SIDEWALKS
 CODE SUMMARY ONLY FOR STAIR,LOBBY, AND
 LANDINGS, NO MENTION OF,SIDEWALKS:
 SHALL BE DESIGNED TO CARRY EITHER A
 UNIFROMLY DISTRUBITED LOAD OF 200 PSF OR
 A CONCENTRATED LOAD OF 8,000LBS ON A
 SPACE 2 1/2 SQ FT AND PLACED IN ANY POS-
 ITION, WHICHEVER WILL PRODUCE THE GREAT-
 ER STRESSES. THIS DOES NOT APPLY TO
 SIDEWALKS ON GRADE.
  
 13) 3003.1.4 ELEVATORS SHALL NOT BE IN A
 COMMON ENCLOSING SHAFT WITH A STAIRWAY,
 AND THE PATH OF TRAVEL FROM ONE FLIGT OF
 STAIRS TO THE NEXT SHALL NOT SHALL NOT
 PASS DIRECTLY IN FRONT OF THE ELEVATOR
 DOOR.
  
 14) MACHINE ROOM 3003.7.1 THE MEANS OF
 EGRESS SHALL NOT BE THROUGH RESTROOMS,
 DRESSING ROOMS OR TENANT OCCUPIED SPACE.
 THE LOBBY IS A TENANT OCCUPIED SPACE.
  
 15) STRETCHER REQUIREMENT, 3003.4.1
 TRAVEL BETWEEN TERMINAL LANDING AND TOP
 LANDING EXCEEDS 25'.
  
 16)3003.6.3 THE AREA OF THE VENTS
 SHALL BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
  
 17) 3003.3 SIGNAGE MISSING THE COMPLETE
 PACKAGE FOR ELEVATOR & HANDICAPPED
 SIGNS. SIGN & GRAPHS ARE INDICATED ON
 THE TITLE PAGE BUT MISSING.
  
 18)11.4.3.11AREAS OF RESCUE ASSISTANCE
 INDICATE LOCATION AND CONSTRUCTION TYPE
 FOR AREAS OF REFUGE, INDICATE ON PLAN
 WHICH CASE USED (1-7).
  
 19)11-4.3.11.2 STAIRWAY WIDTH, EACH
 STAIRWAY ADJACENT TO AN AREA OF RESCUE
 SHALL HAVE A MINIMUM CLEAR WIDTH OF
 48" BETWEEN HANDRAILS. THIS ALSO
 INCLUDES ALL RAMPS!!!
  
 20) PROVIDE INFORMATION AS TO YOUR STAIR
 DESIGN? IF STAIR IS ENCLOSED WHERE IS
 THE RATED DOORS, TABLE 705.1.2 ALSO INDI
 CATES THE NEED OF A 1 HR RATING ON THE
 ELEVATOR SHAFT, (LESS THAN 4 STORIES).
  
 IF THE DESIGN IS TO BE CONSIDERED AND ,
 EXTERIOR STAIR TOWER 1006.2.2 THE PROB-
 LEM OF THE ASSUMED PROPERTY LINE BETWEEN
 STRUCTURES, STAIRWAYS SHALL BE LOCATED
 AT LEAST 10'-0" FROM ADJACENT PROPERTY
 LINES OR ASSUMED PROPERTY LINES FROM
 BUILDINGS ON THE SAME LOT.
  
 21) SHEET SJ-A036 INDICATES THE WIRE
 MESH GUARDRAIL SYSTEM BUT NO INFORMATION
 ABOUT SYSTEM,
 1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 22) PLANS ARE TO SMALL TO SEE A THROUGH
 PLAN REVIEW CANNOT BE ACCOMPLISHED AT
 THIS TIME THESE QUESTIONS HAVE TO BE
 ANSWERED TO BE ABLE TO COMPLETE THIS RE-
 VIEW.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-27 Cont ID  
Sent By dpalmer Date 2003-06-27 Time 14:51 Rev Time 1.00
Received By dpalmer Date 2003-06-27 Time 14:51 Sent To  
Notes
2003-06-27 00:00:00*************** UNSAT ****************
  
 1)NOTE: ALL PLANS ARE TO BE SIGNED,DATED
 AND SEALED BY ENGINEER OF RECORD.471.025
 61G15-23.002
  
 2)NOTE: PLEASE SHOW/CLARIFY WHERE AND
 HOW TRANSFORMERS ARE BEING GROUNDED.
 250-30
  
 3)NOTE: PLEASE SHOW BLDG FOOTER STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM. 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-06-13 Cont ID  
Sent By mamini Date 2003-06-13 Time 16:25 Rev Time 1.00
Received By mamini Date 2003-06-13 Time 16:25 Sent To  
Notes
2003-06-13 00:00:00PASSED WITH PROVISOS:
 1. CONNECTION OF WATER SERVICE TO THE
 TOWERS DO NOT MATCH AS SHOWN ON SHEET
 SJ-P005 PLUMBING, PLEASE COORDINATE.
 2. BACKFLOW, FIRE HYD.,VALVES, CLEAN OUT
 MUST BE PER CITY OF WPB PUBLIC UTILITIES
 REQUIREMENTS, PLEASE CONTACT 659-8040,
 MANNY GONZALEZ.
 3. POLLUTION/ EROSION PLANS MUST BE
 INSTALLED IN FIELD PRIOR TO ANY EARTH/
 CONSTRUCTION WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-08 Cont ID  
Sent By mcarsill Date 2003-07-08 Time 12:21 Rev Time 0.00
Received By mcarsill Date 2003-07-08 Time 12:21 Sent To  
Notes
2003-07-08 00:00:001) FIRE HYDRANTS TO COMPLY WITH UTILITY
 AND FIRE RESCUE STANDARDS.
  
 2) WHAT PURPOSE DOES THE NEW 48" WIDE
 GATE AND THE NEW 20' WIDE SLIDING GATE
 DO.
  
 3) TACTILE SIGNAGE REQUIRED AT STAIRS.
  
 4) ALL SHAFTS SHALL BE MARKED SHAFTWAY.
  
 5) BUILDING IS LOCATED IN THE CITY FIRE
 LIMITS. CERTAIN RESTRICTIONS APPLY.
  
 6) PANIC BUSHBUTTON PROVIDES WHAT
 PURPOSE.
  
 7) PLEASE EXPLAIN PURPOSE OF OPENING
 WITHIN EXIT STAIR.
  
 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR WIRE MESH BARRIER.
  
 9) DOOR SCHEDULE INDICATES NO RATED
 DOORS. WHY
  
 10) ALL NEW STAIRS AND RAMPS SHALL
 HAVE HANNDRAILS ON BOTH SIDES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-19 Cont ID  
Sent By shernand Date 2003-06-19 Time 11:18 Rev Time 0.00
Received By shernand Date 2003-06-19 Time 11:18 Sent To  
Notes
2003-06-19 00:00:00RETURNED TO BOX #19 FROM PLANNING DEPT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-19 Cont ID  
Sent By shernand Date 2003-06-19 Time 10:24 Rev Time 0.00
Received By shernand Date 2003-06-19 Time 10:24 Sent To R
Notes
2003-06-19 00:00:00ROXANNE MANNING IN PLANNING DEPT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 14:44 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 14:44 Sent To  
Notes
2003-06-12 00:00:00COMM BOARD #19

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-06-19 Cont ID  
Sent By pkrauss Date 2003-06-19 Time 15:55 Rev Time 0.20
Received By pkrauss Date 2003-06-19 Time 15:55 Sent To  
Notes
2003-06-19 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PROVIDE PLANS WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By kstevens Date 2003-07-01 Time 08:51 Rev Time 0.75
Received By kstevens Date 2003-06-30 Time 18:57 Sent To  
Notes
2003-07-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
  
 1) SHT SJ-P007 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, AND 1107 AND ALL SUB-
 SECTIONS. SHOW LOCATIONS OF ALL SECOND-
 ARY ROOF DRAINS.
 2) SHT SJ-P005 DRINKING FOUNTAINS SHALL
 DRAIN TO SANITARY NOT STORM. SECTIONS
 701.2 & 701.3
 3) SHT SJ-L003 PLUMBING CONTRACTOR SHALL
 INSTALL RPZ BACKFLOW FOR IRRIGATION
 CONTRACTOR. SEPARATE PERMIT REQUIRED FOR
 IRRIGATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692