Plan Review Details - Permit 03060814
Plan Review Stops For Permit 03060814
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 09:53 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 09:53 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-13 Cont ID  
Sent By pkrauss Date 2003-08-13 Time 07:43 Rev Time 0.45
Received By pkrauss Date 2003-08-13 Time 07:43 Sent To  
Notes
2003-08-13 00:00:00PROVISO:
  
 PROVIDE INFORMATION ON THE RETURN AIR.
 RETURN OR TRANSFER AIR REQUIRED FROM
 THE OFFICE AREA WHERE THE FULL LOUVERED
 DOOR IS LOCATED TO THE REST OF THE
 OFFICE SPACE (2001 FBC(M) 601.4 BALANCED
 AIR RETURN).PLEASE INDICATE GRILLED &
 DUCT SIZE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-19 Cont ID  
Sent By pkrauss Date 2003-06-17 Time 07:10 Rev Time 0.25
Received By pkrauss Date 2003-06-17 Time 07:09 Sent To  
Notes
2003-06-17 00:00:00AS PER CONVERSATION WITH EAGLE MECH.
 EXTENDING DUCT AND ADDING 2 SIDE WALL
 GRILLES. RELOCATING EXISTING DIFUSERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.