Plan Review Details - Permit 03060725
Plan Review Stops For Permit 03060725
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-08 Cont ID  
Sent By btrobaug Date 2003-11-10 Time 09:29 Rev Time 1.50
Received By sthyng Date 2003-11-08 Time 13:35 Sent To E
Notes
2003-11-08 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)THE ORIGINAL APPLICATION AND
 OWNER/BUILDER AFFIDAVIT ARE NO LONGER
 IN THE PACKAGE.ALL DOCUMENTS ARE TO
 REMAIN IN THE PACKAGE TO AVOID DELAYS
 IN PROCESSING THE PERMIT.IF YOU CANNOT
 FIND THE ORIGINAL APPLICATION, FILL OUT
 A NEW APPLICATION.THE COPY WILL NOT
 SUFFICE AS THE SIGNATURE OF THE
 CONTRACTOR IS ON THE BACK.ALSO FILL
 OUT A NEW OWNER/BUILDER AFFIDAVIT.
  
 2.)THE NOTICE OF COMMENCEMENT HAS
 EXPIRED (DID NOT COMMENCE WORK WITHIN
 90 DAYS)FS713.13.THE SAME DOCUMENT CAN
 BE REFILED WITH THE CLERK OF COURTS.
  
 3.)ADDITIONAL PERMITS REQUIRED.
  
 4.)WHEN RESUBMITTING, SUBMIT OLD
 SHEETS.
  
 5.)SMOKE DETECTORS REQUIRED IN
 EXISTING HOUSE AS PER FBC3401.7.1.2,
 FBC905.2.2.
  
 6.)ADDITIONAL FEES DUE (VALUE
 ADJUSTMENT, RADON), SEE ATTACHED BZ
 233264.
  
 7.)THE SOILS REPORT RECOMMENDS
 CONSTRUCTION JOINTS.HAVE THE
 STRUCTURAL ENGINEER READ THE SOILS
 REPORT AND REVISE THE PLAN AS NECESSARY.
  
 8.)THE ELEVATIONS SHOW 3/4" PLYWOOD
 ROOF SHEATHING; THE DETAILS SHOW 5/8.
  
 9.)THE WINDOW ANCHOR DETAIL IS TO
 COMPLY WITH FBC1707.4.4.2.
  
 10.) SUBMIT TWO COPIES OF THE SURVEY.
 ONE IS A PARTIAL COPY TAPED TO THE
 OTHER AND DOES NOT CONTAIN THE LEGAL
 DESCRIPTION.
  
 11.) SUBMIT A SECOND COPY OF THE
 SLIDING GLASS DOOR PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-30 Cont ID  
Sent By pkrauss Date 2003-11-05 Time 15:25 Rev Time 2.50
Received By sthyng Date 2003-06-30 Time 18:24 Sent To E
Notes
2003-06-30 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDITIONAL PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE ORIGINAL RECEIPT
 ATTACHED TO THE APPLICATION.233-5025
  
 4.)THE WALL SECTION DOES NOT SHOW
 INSULATION OR DRYWALL.
  
 5.)THE TYPICAL SAFEGUARD NOTES REFERS
 TO THE INCORRECT BUILDING CODE.
  
 6.)PROVIDE A SURVEY AND A SITE PLAN
 FOR THIS JOB.ZONING REVIEW REQUIRED.
  
 7.)FIRESTOP REQUIRED FBC705.3.
  
 8.)AN IMPROVEMENT OF GREATER THAN 25%
 MUST COMPLY WITH FBC3401.7.1.2.SHOW
 THE FOLLOWING FOR THE EXISTING HOUSE:
 FRONT DOOR TO COMPLY WITH FBC 1004.
 EMERG.EGRESS FOR BEDROOMS, FBC1005.4.
 BATHROOM TO COMPLY WITH FBC11-11(1)
 SAFETY GLASS REQUIREMENTS, FBC2405.1.
 SMOKE DETECTORS TO COMPLY FBC905.2.2.
  
 9.)DETAILS A AND F SHOW 5/8" PLYWOOD,
 DETAIL D IS 3/4".
  
 10.) FOR THE 2X4 LEDGER, DETAIL F, WHAT
 IS THE SPACING FOR THE ATTACHMENT?
  
 11.) PROVIDE A DETAIL FOR THE CONCRETE
 COLUMNS ON THE BALCONY.
  
 12.)ADDITIONAL FEES REQUIRED, $90.30.
  
 13.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 14.)THE LIGHTS ON THE ELEVATIONS ON
 TOP OF THE CONCRETE COLUMNS ARE NOT ON
 THE ELECTRIC PLAN.
  
 15.)PROVIDE TWO COPIES OF PRODUCT
 APPROVALS FOR THE EXTERIOR DOOR.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-10 Cont ID  
Sent By btrobaug Date 2003-11-10 Time 09:29 Rev Time 0.50
Received By btrobaug Date 2003-11-10 Time 09:29 Sent To B
Notes
2003-11-10 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 SEE NOTES FROM THE PREVIOUS REVIEW,NONE
 WERE ADDRESSED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2003-11-10 Time 08:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-07-01 Cont ID  
Sent By sthyng Date 2003-11-08 Time 13:58 Rev Time 0.50
Received By btrobaug Date 2003-07-01 Time 14:21 Sent To M
Notes
2003-07-01 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE REVISE PLANS TOREFLECT THE
 FOLLOWING ADDITIONS FOR CODE COMPLIANCE
 AND RESUBMIT FOR REVIEW PRIOR TO ANY
 ELECTRICAL INSPECTIONS.
  
 1} PLEASE NOTE THAT ALL LOW VOLTAGE MUST
 BE PART OF THE PLAN SUBMITTED IF IT IS
 TO BE INCLUDED WITH THE PERMIT
 APPLICATION,OR A SEPERATE PERMIT AND
 DRAWINGS MUST BE SUBMITTED.
  
 2} A GFI RECEPTACLE MUST BE INSTALLED AT
 THE REAR OF THE RESIDENCE TO COMPLY
 WITH 210.52(E).
  
 3} PLEASE NOTE ADDED RECEPTACLES IN THE
 FAMILY ROOM TO COMPLY WITH 210.52(A).
  
 4} SHOW AN EGRESS LIGHT PER 210.70 AND
 NOTE HOW SWITCHED.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-10 Cont ID  
Sent By mmclean Date 2003-11-18 Time 09:53 Rev Time 0.00
Received By sthyng Date 2003-11-10 Time 10:11 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-31 Cont ID  
Sent By lsmith Date 2003-10-31 Time 10:59 Rev Time 0.00
Received By lsmith Date 2003-10-31 Time 10:59 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-17 Cont ID  
Sent By shernand Date 2003-06-17 Time 10:19 Rev Time 0.00
Received By shernand Date 2003-06-17 Time 10:19 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-11 Cont ID  
Sent By shernand Date 2003-06-11 Time 11:24 Rev Time 0.00
Received By shernand Date 2003-06-11 Time 11:24 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-05 Cont ID  
Sent By pkrauss Date 2003-11-05 Time 15:24 Rev Time 0.20
Received By pkrauss Date 2003-11-05 Time 15:18 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-07-07 Cont ID  
Sent By lsmith Date 2003-10-31 Time 10:59 Rev Time 0.35
Received By pkrauss Date 2003-07-07 Time 12:36 Sent To P
Notes
2003-07-07 00:00:00DENIED:
  
 ENERGY CALCULATIONS SUBMITTED INDICATE
 2920 SQ FT OF CONDITIONED SPACE AND
 THE EQUIPMENT INDICATES ONLY 2 1/2 TONS
 OF AIR.PLEASE CLARIFY IF THE 2 1/2
 TON UNIT IS FOR THE ENTIRE HOUSE OR IS
 THERE ANOTHER UNIT THAT IS NOT INDICATED
 ON PLAN OR ENERGY CALCS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-07-07 Cont ID  
Sent By pkrauss Date 2003-07-07 Time 12:50 Rev Time 0.25
Received By kstevens Date 2003-07-07 Time 12:59 Sent To  
Notes
2003-07-07 00:00:00NO PLUMBING PLANS SUBMITTED - NO PLUMB-
 ING WORK BEING DONE.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-18 Cont ID  
Sent By sthyng Date 2003-11-10 Time 10:11 Rev Time 0.00
Received By mmclean Date 2003-11-18 Time 09:53 Sent To I
Notes
***NONE***