Plan Review Details - Permit 03060510
Plan Review Stops For Permit 03060510
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-22 Cont ID  
Sent By alange Date 2003-07-22 Time 14:19 Rev Time 0.00
Received By alange Date 2003-07-22 Time 14:19 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 10:14 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 10:14 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-28 Cont ID  
Sent By kstevens Date 2003-07-28 Time 18:21 Rev Time 0.50
Received By kstevens Date 2003-07-28 Time 18:21 Sent To  
Notes
2003-07-28 00:00:00PASSED/PROVISO - SINK SHALL COMPLY WITH
 11-4.24 AND ALL SUBSECTIONS

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-17 Cont ID  
Sent By alange Date 2003-07-22 Time 14:20 Rev Time 0.75
Received By kstevens Date 2003-06-17 Time 13:04 Sent To  
Notes
2003-06-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SECTION 909.1 ONLY THE FIXTURES WITH-
 IN THE BATHROOM GROUP SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN.
 ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT.
 2) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1.
 3) SECTION 104.2.1 A WATER RISER DIAGRAM
 IS REQUIRED. WATER HAMMER ARRESTORS REQ-
 UIRED BY SECTION 604.9 (DISH WASHER, ICE
 MAKER, WASH MACHINE) SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN CEILING AT TOP OF DROP.
  
 REVIEW BY KEN STEVENS