Plan Review Details - Permit 03060502
Plan Review Stops For Permit 03060502
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-19 Cont ID  
Sent By hpiskura Date 2003-06-19 Time 09:42 Rev Time 0.00
Received By hpiskura Date 2003-06-19 Time 08:27 Sent To Z
Notes
2003-06-19 00:00:00PHASES IIB AND IIC, SHEETS A1 CITE THE
 1997 SBC, PLEASE REVISE FOR 2001 FBC
 AND ENSURE COMPLIANCE WITH SAME.
  
 THE HC PARKING SIGNAGE SHOULD INCLUDE
 THE FINE AMOUNT ($250 IN WPB) TO COMPLY
 WITH FBC 11-4.6.4 IE "PENALTY"

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-19 Cont ID  
Sent By dpalmer Date 2003-06-19 Time 07:17 Rev Time 1.00
Received By dpalmer Date 2003-06-19 Time 07:17 Sent To  
Notes
2003-06-19 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AND SHOW WIND
 LOADS FOR LIGHT POLES. PER FBC 140MPH
  
 2)NOTE :PLEASE PROVIDE SECOND GROUND ROD
 AT SERVICE.
  
 3)NOTE: PLEASE CLARIFY SERVICE RATED
 DISC AT LIGHTING CONTROL PANEL?
  
 4)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAIN(S). 110-9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-06-13 Cont ID  
Sent By mamini Date 2003-06-13 Time 10:46 Rev Time 1.00
Received By mamini Date 2003-06-13 Time 10:45 Sent To  
Notes
2003-06-13 00:00:00PASSED WITH PROVISOS:
 1. EXISTING WOOD POWER POLE AS SHOWN ON
 SHEET C-3 AT STA. APPROX. 18+40 SHOULD
 BE RELOCATED / REMOVED, PLEASE VERIFY.
 2. M.O.T. PLANS MUST BE SUBMITTED FOR
 OUR REVIEW AND APPROVAL PRIOR TO
 COMMENCEMENT OF THE PROJECT.
 3. TACTILE SURFACE AT ALL DESIGNATED
 H.C RAMP AND WALKS MUST BE PROVIDED.
 4. POLLUTION /EROSION PLANS MUST BE
 ISTALLED IN FIELD PRIOR TO COMMENCEMENT
 OF THE WORK AND MUST BE IN WORKING
 CONDITION THROUGHOUT THE TIME OF
 CONSTRUCTION.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-06-16 Cont ID  
Sent By nmccray Date 2003-06-16 Time 13:45 Rev Time 0.00
Received By nmccray Date 2003-06-16 Time 13:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 11:06 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 11:06 Sent To  
Notes
2003-06-26 00:00:00CALLED TO P/U FOR CORR.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-09 Cont ID  
Sent By mmclean Date 2003-06-26 Time 09:49 Rev Time 0.00
Received By shernand Date 2003-06-09 Time 15:29 Sent To  
Notes
2003-06-09 00:00:00COMM BOARD #17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-06-19 Cont ID  
Sent By hpiskura Date 2003-06-19 Time 09:47 Rev Time 0.00
Received By hpiskura Date 2003-06-19 Time 09:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-14 Cont ID  
Sent By kstevens Date 2003-06-14 Time 12:25 Rev Time 0.33
Received By kstevens Date 2003-06-14 Time 12:10 Sent To  
Notes
2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 ADMIN CODE, CHAPTER
 1, & AMENDMENTS.
  
 SECTION 104.2.1 - PLAN COVER SHEET CALLS
 FOR 5 IRRIGATION SHEETS. SHEET 5 HAS NOT
 BEEN SUBMITTED. PLEASE CLAIRFY
  
 INDICATE IF FOUNTAIN IS DECORATIVE OR
 WILL IT BE A PLAY TYPE FOUNTAIN? IF
 IT WILL BE A PLAY TYPE THE PLANS SHALL
 BE ROUTED TO THE HEALTH DEPT. PRIOR TO
 SUBMITTING FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-26 Cont ID  
Sent By hpiskura Date 2003-06-19 Time 09:48 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
2003-06-26 00:00:006/25/03 OK TO PASS PER ANGELLA JONES-
 VANN MM