Plan Review Details - Permit 03060500
Plan Review Stops For Permit 03060500
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-30 Cont ID  
Sent By rbrown Date 2003-06-30 Time 08:24 Rev Time 0.00
Received By rbrown Date 2003-06-30 Time 08:24 Sent To Z
Notes
2003-06-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES)
  
 2) SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, EXTERNAL DOORS AND ROOFING.
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 4) FBC 3502SHEET S-3, STRUCTURAL NOTES
 CODES AND STANDARDS NOTE #2A AND
 CONCRETE NOTE #3 REFER TO ACI 318/1995
 EDITION, FOR REINFORCED CONCRETE, THIS
 REFERENCE SHOULD BE ACI 318-99 PER
 FLORIDA BUILDING CODE.
  
 5) FBC 1606WIND PRESSURES ON WINDOWS
 AND DOORS.GENERAL NOTE #2 ON SHEET A7
 (ALSO DESIGN PARAMETERS ON SHEET S-3)
 REFER TO 'THE ELEVATIONS' FOR WIND LOADS
 ON THE WINDOWS.THE WIND PRESSURES ON
 THE WINDOWS AND DOORS ARE NOT SHOWN ON
 THE ELEVATIONS. AMEND/ANNOTATE THE PLANS
  
 6) FBC 1606.2.4ROOF TRUSS UPLIFT
 REACTIONS.NOTE #4 ON SHEET S-2 STATES
 THAT TRUSS CONNECTIONS SHALL BE DESIGNED
 BY THE WOOD TRUSS ENGINEER.THE TRUSS
 UPLIFT REACTIONS SHALL BE STATED ON THE
 PLANS BEFORE A PERMIT CAN BE ISSUED.
  
 7) FBC 1606.2.4SHEET S-4, TRUSS TIE-
 DOWN SCHEDULE.TRUSS ANCHOR MARKS M & N
 ARE SPECIFIED AS 'HUGHES' USC.'HUGHES'
 IS NO LONGER A SUPPLIER OF TRUSS ANCHORS
 IF THE INTENDED MANUFACTURER/REFERENCE
 IS 'USP' USC, PLEASE NOTE THAT THE
 STATED ALLOWABLE UPLIFTS EXCEED THOSE
 GIVEN IN THE 2003 USP CATALOGUE.AMEND
 THE SCHEDULE.
  
 8) FBC 1606.2.4SHEET S-5, SECTIONS
 1 & 3.NO MANUFACTURER IS GIVEN FOR THE
 'A35' CLIP AND 'H2.5' CLIP (ASSUMED TO
 BE SIMPSON REFERENCES).AMEND THE PLAN
 TO STATE THE MANUFACTURER OF THESE
 ANCHORS AS THEY DO NOT APPEAR IN THE
 TRUSS ANCHOR SCHEDULE ON SHEET S-4.
  
 9) FBC* TABLE 2306.1PLYWOOD SHEATHING
 FASTENERS, SHEET S-3, WOOD NOTE #5.THE
 NOTE SHOULD BE AMENDED TO REFER TO THE
 SHEET S-5 SECTIONS 1, 2, 4 & 5 FOR
 SHEATHING FASTENERS SINCE THIS
 INFORMATION IS NOT GIVEN ON THE 'FRAMING
 PLANS' AS STATED.
  
 10) FBC 2405.2THE GLAZING IN EACH
 ALUMINUM/GLASS FRENCH DOOR AND SIDELITE
 IS IN A 'HAZARDOUS LOCATION' AND
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 11) FBC* 104.2.1THE SIDELITES ADJACENT
 ALUMINUM/GLASS FRENCH DOORS ARE SHOWN ON
 THE WINDOW SCHEDULE AS MARK 'C' WHICH IS
 4'-10" HIGH, BUT THE SOUTH AND EAST
 ELEVATIONS SHOW 7' SIDE LITES.PLEASE
 CLARIFY/AMEND THE PLANS.
  
 12) FBC 11-4.13.6MANEUVERING CLEARANCE
 AT DOORS. DOOR 107/5 SHALL HAVE AT LEAST
 18" CLEARANCE BETWEEN THE LEADING EDGE
 OF THE DOOR AND THE ADJACENT CLASSROOM
 117 WALL ON THE PULL SIDE OF THE DOOR
 (REF: FIG. 25A).AMEND/ANNOTATE THE
 PLAN TO SHOW THE DIMENSION.
  
 13) FBC 11-4.22.4W.C.GRAB BARS,
 SHEET A8, DETAIL 6C.THE FRONT END OF
 THE SIDE GRAB BAR SHALL BE AT LEAST 54"
 FROM THE REAR WALL (REF: FIG. 29B).
 ALSO, THE PLANS SHALL STATE THE GRAB BAR
 DIAMETER AND SPACING FROM THE SUPPORTING
 WALL.
  
 14) FBC 11-4.19.2LAVATORY CLEARANCES.
 SHEET A8, DETAIL 6A.ANNOTATE THE PLANS
 TO DEMONSTRATE COMPLIANCE WITH THE KNEE
 AND TOE CLEARANCE REQUIREMENTS (REF:
 FIG 31).
  
 15) FBC 11-4.15DRINKING FOUNTAIN.
 AMEND/ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE WITH THE REQUIREMENTS FOR
 SPOUT LOCATION/HEIGHT AND WHEELCHAIR
 APPROACH CLEARANCES (REF: FIG. 27).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-19 Cont ID  
Sent By dpalmer Date 2003-06-19 Time 08:06 Rev Time 1.50
Received By dpalmer Date 2003-06-19 Time 08:06 Sent To  
Notes
2003-06-19 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL HAVE A DIRECT AFFECT ON
 ELECTRICAL PLANS.
  
 2)NOTE: PLEASE SEE 700-12E FOR CIRCUIT-
 ING OF EM/EXT LTS.
 ALSO ONLY SHOWN ON ONE CIRCUIT?
  
 3)NOTE: PLEASE PROVIDE IN GROUNDING
 NOTE, TO FOOTER STEEL PER 250-50
  
 4)NOTE: PLEASE SEE FIRE NOTE FOR "CHILD
 PROOF " RECEPTS. AND PROVIDE NOTE ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-06-13 Cont ID  
Sent By mamini Date 2003-06-13 Time 14:24 Rev Time 1.00
Received By mamini Date 2003-06-13 Time 14:24 Sent To  
Notes
2003-06-13 00:00:00FAILED:
 1. A SEPARATE BACKFLOW PREVENTER IN
 1 1/2" WATER LINE IS REQUIRED.
 2. PROPOSED SITE MUST BE DESIGNED FOR
 STORM WARTER PER CITY REQUIREMENT AND
 CRITERIA, PLEASE INCLUDE PERVIOUS AND
 IMPERVIOUS AREA FOR TOTAL SITE.
 3. POLLUTION/EROSION PLANS MUST BE ADDED
 TO CIVIL/SITE PLAN.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-13 Cont ID  
Sent By mcarsill Date 2003-06-13 Time 08:21 Rev Time 0.00
Received By mcarsill Date 2003-06-13 Time 08:21 Sent To  
Notes
2003-06-13 00:00:001) PLEASE EXPLAIN 1/8" FIRE LINE NOTE
 ON WATER AND WASTEWATER PLANS.
  
 2) TAMPER SWITCHES, CHAIN AND LOCK
 REQUIRED ON OS&Y FOR FIRE LINE.
  
 3) WRONG LIFE SAFETY CODE REFERENCED
 ON LS1. SHOULD READ NFPA 101, 2000
 EDITION.
  
 4) BATHROOM AND CLOSET DOORS SHALL BE
 ABLE TO BE UNLOCKED FROM OUTSIDE IN
 AN EMERGENCY.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 6) ALL EXIT DOORS SHALL BE EQUIPPED
 WITH PANIC HARDWARE.
  
 7) LS1 DOES NOT DISPLAY ENOUGH SMOKE
 DETECTORS.
  
 8) PLANS DO NOT INDICATE PROPOSED HOURS
 OF OPERATION, AND PROPOSED AGES OF
 CHILDREN.
  
 9) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS.
  
 10) PROVIDE FLAMESPREAD DETAILS ON
 ACCORDIAN WALL.
  
 11) PROTECTIVE COVERS REQUIRED FOR
 ELECTRICAL OUTLETS.
  
 12) IT APPEARS THAT ONLY ONE EMERGENCY
 LIGHT WAS PRESENT ON E2. MORE ARE
 NEEDED.
  
 13) EXIT SIGNS MISSING IN CLASSROOM # 1.
  
 14) SEPARATE PLANS AND PERMITS FOR
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
 15) WHAT TYPE OF COOKING WILL BE DONE.
  
 16) MORE DETAILS REQUIRED ON FP1.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-09 Cont ID  
Sent By shernand Date 2003-06-09 Time 15:06 Rev Time 0.00
Received By shernand Date 2003-06-09 Time 15:06 Sent To  
Notes
2003-06-09 00:00:00COMM BOARD #48

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-06-17 Cont ID  
Sent By pkrauss Date 2003-06-17 Time 10:14 Rev Time 2.00
Received By pkrauss Date 2003-06-17 Time 10:14 Sent To  
Notes
2003-06-17 00:00:00DENIED:PLAN CHECK
  
 1.PLEASE PROVIDE INFORMATION ON THE
 HOURS OF OPERATION.
  
 2.INDICATE AGES OF CHILDREN IN EACH
 CLASSROOM. WHAT WILL BE THE APPROXIMATE
 LENGTH OF STAY IN THE CLASSROOM.
  
 3.PLAN SHEET M-3 VENTILATION RATES,
 AS PER 2001 FBC(M) 403.3 & ASHRAE 62-89
 INDICATE THE VENTILATION SYSTEM SHALL BE
 DESIGNED TO SUPPLY THE REQUIRED RATE OF
 VENTILATION AIR CONTINUOUSLY DURING THE
 PERIOD THE SPACE IS OCCUPIED.THE
 NOTE ON PLAN SHEET M-3 INDICATES THE
 VARIABLE VENTILATION RATES ARE ONE-HALF
 OF THE SPECIFIED RATE - THE CLASSROOM
 AREA AND OFFICE AREAS ARE INDICATED.
 UNDER THE O.A. CALCS SHOWN ON PLAN M-3
 INDICATE ONLY THE CONFERENCE & FOOD
 PREPARATION AREA AS INTERMITTENT
 OCCUPANCY.PLEASE CLARIFY
  
 3.PLEASE INDICATE WHAT TYPE OF
 PREPARATION WILL BE DONE IN FOOD PREP.
 AREA.(PLEASE INDICATE IF A STOVE WITH
 OVEN WILL INSTALLED).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-14 Cont ID  
Sent By kstevens Date 2003-06-14 Time 11:15 Rev Time 2.00
Received By kstevens Date 2003-06-14 Time 11:15 Sent To  
Notes
2003-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 ADMIN. CODE, CHAPTER
 1 & AMENDMENTS.
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURE REQUIREMENTS PER TABLES 1003.1 AND
 403.1
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE TO SEE IF THERE WILL BE A RE-
 QUIRED GREASE TRAP. WASTE ORD. #2938-96
 (561) 837-4074
 3) SHT C-1 RPZ BACKFLOW REQUIRED ON
 WATER SERVICE. 608.13.2
 4) SHT A2 TOILET ROOMS, SHOW CLEAR FLOOR
 SPACE AND TURNING CIRCLE FOR ALL TOILET
 ROOMS.
 5) SHT A2 SHOW CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES INCLUDING DRINKING
 FOUNTAINS AND CLASSROOM SINKS ECT.
 6) SHT A8 DETAIL 6(A), SECTION 11-4.16.5
 FLUSH CONTROLS SHALL BE MOUNTED ON THE
 WIDE SIDE OF THE TOILET AREAS, MAXIMUM
 44" ABOVE FLOOR.
 7) SUBMIT DETAIL FOR ACCESSIBLE DRINKING
 FOUNTAIN PER 11-4.15 AND ALL SUBSECTIONS
 8) SHT P-1 PLUMBING NOTES #'S 1 & 2,
 CODE ADOPTED IN THE FBC-2001 PLUMBING,
 NOT STANDARD CODE. PLEASE UPDATE REFER-
 ENCES.
 9) SHT P-1 PLUMBING NOTES #5, AIR CHAMB-
 ERS ARE NOT APPROVED. PLEASE DELETE FROM
 REFERENCE.
 10) SHT P-1 PLUMBING NOTES #10, AN RPZ
 BACKFLOW IS REQUIRED FOR CHILLER MAKE-UP
 WATER. VACUUM BREAKER IS NOT THE CORRECT
 APPLICATION. SECTION 608.13
 11) SHT P-1 WATER HEATER DETAIL. THERMAL
 EXPANSION CONTROL IS REQUIRED. SECTION
 607.3.2
 12) SHT P-2 WATER RISER DETAILS 4/P-2 &
 5/P-2, AIR CHAMBERS SHOWN ON RISER AT
 FIXTURE P-3 NOT APPROVED. SEC 604.9
 13) SHT P-2 3 COMPARTMENT SINK IN FOOD
 PREP AREA SHALL BE INDIRECT WASTE. SEC
 802.1
 14) SHT P-2 FLOOR PLAN & SANT. RISER
 DIAGRAM. SINKS FROM CLASS ROOM #4 SHALL
 TIE IN DOWNSTREAM OF FIXTURES IN THE
 TOILET ROOM. 909.1
 15) INDICATE IF CHILDREN'S FIXTURES WILL
 BE USED IN ANY OF THE TOILET ROOMS.
 FURTHER COMMENTS MIGHT BE ADDED TO THE
 NEXT REVIEW DEPENDING ON REPLY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By rbrown Date 2003-06-30 Time 11:14 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-07-01 00:00:00DENIED CORNER SIDE SETBACK MUST BE 12.5


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved