| 2003-06-30 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03060496 |
| | ADD: 215 S OLIVE AVE |
| | CONT: RAYMOND NORDINE |
| | TEL: (561)252-1662 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) F 103.1 EXISTING BUILDINGS WITHIN THE |
| | FIRE DISTRICT. |
| | AN EXISTING BUILDING SHALL NOT BE HERE- |
| | AFTER BE INCREASED IN HEIGHT OR AREA |
| | UNLESS IT IS OF THE TYPE OF CONSTRUCTION |
| | PERMITTED FOR NEW BUILDINGS WITHIN THE |
| | FIRE DISTRICT OR IS ALTERED TO COMPLY |
| | WITH THE REQUIREMENTS FOR SUCH TYPE OF |
| | CONSTRUCTION. NOR SHALL ANY BUILDING BE |
| | HEREAFTER EXTENDED ON ANY SIDE, NOR |
| | SQUARE FOOTAGE OR FLOORS ADDED WITHIN |
| | THE EXISTING BUILDING UNLESS SUCH MODIF- |
| | ICATIONS ARE OF A TYPE OF CONSTRUCTION |
| | PERMITTED FOR NEW BUILDINGS WITHIN THE |
| | FIRE DISTRICT.A-2 NOTE 18. |
| | |
| | 2) 1012.1.4 DURING ITS SWING, ANY DOOR |
| | IN A MEANS OF EGRESS SHALL LEAVE UNOBSTR |
| | UCTED AT LEAST ONE HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, |
| | OR LANDING, NOR PROJECT MORE THAN 7" IN- |
| | TO THE REQUIRED WIDTH OF AN AISLE, CORRI |
| | DOR, PASSAGEWAY OR LANDING, WHEN FULLY |
| | OPEN, SEE ENTRY DOOR (A).FIFTH FLOOR |
| | LANDING OF MAIN STAIR. |
| | |
| | 3)SHEET A-4 STAIR PLAN TO ROOF DETAIL(2) |
| | INDICATES A 8" RISE, 1007.3.` MAXIMUM OF |
| | 7"RISE, TREADS A MINIMUM OF 11". |
| | |
| | 4)1015.2 HEIGHT. GUARDRAILS SHALL |
| | FORM A VERTICAL PROTECTIVE BARRIER NOT |
| | LESS THAN 42" HIGH. |
| | 1015.3 OPENINGS. OPEN GUARDRAILS |
| | SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| | MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| | SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| | RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| | REJECT THE PASSAGE OF 2" DIAMETER |
| | SPHERE. |
| | |
| | 5) SOUTH TENANT INDICATES A WORK/ LOFT |
| | WITH THE FOURTH FLOOR BEING BUSINESS, |
| | THE BATHROOM IS ELEVATED FROM THE MAIN |
| | FLOOR BY THREE RISERS, PROVIDE INFORMA- |
| | TION FOR VERTICAL ACCESSIBILITY.11-4.1.6 |
| | |
| | 6) THIS SAME BATHROOM REQUIRES A FLOOR |
| | THE SAME LEVELAAS THE BATH, 1007.2.4., |
| | IF THIS IS CONSIDERED BUSINESS. NO EXCEP |
| | TION AS IN R-3. |
| | |
| | 7) SPIRAL STAIRWAY: PROVIDE MANUFACTURER |
| | INFORMATION, THAT THE SPIRAL STAIR COM- |
| | PLIES WITH ALL SECTIONS OF 1007.8.2.3 & |
| | 1007.8.3. STAIRWAY & HANDRAIL & GUARD- |
| | RAIL SYSTEMS. |
| | |
| | 8) SHEET S-1 LIVE LOADS, ARE TO BE TAKEN |
| | FOR THE OCCUPANCY THE FOURTH FLOOR IS |
| | CONSIDERED THE WORK FLOOR OF THE WORK/ |
| | LIVE LOFT THE FLOOR LIVE LOAD MINIMUM |
| | FOR OFFICE IS 50 PSF WITHOUT FILE |
| | CABINETS ? THE FIFTH FLOOR FOR LIVING |
| | AREAS SHOULD BE 40 PSF ONLY SLEEPING |
| | ROOMS IS 30 PSF. NO MENTION AS TO THE |
| | LOADING FOR THE ATTIC STORAGE PSF? |
| | |
| | 9)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | MISSING THE DESIGN WIND PRESSURES FOR |
| | THE NEW ROOF SYSTEM,SEE FIGURE 1606.2(C) |
| | FOR INTERIOR ZONES, EDGE AND ZONE 3. |
| | PROVIDE THE MEAN ROOF HEIGTH? |
| | ALSO GIVE PRESSURES FOR THE NEW EXTERIOR |
| | DOOR AND SKYLIGHTS? |
| | |
| | 10)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING REPORTS FOR |
| | A) EXTERIOR DOOR |
| | B) SKYLIGHTS |
| | C) ROOFING ASSEMBLIES (FIRE DISTRICT) |
| | PROVIDE MAN SPEC FOR ROOF AND INSU |
| | LATION FOR FIRE TYPE A OR B AND |
| | ATTACHMENT. |
| | |
| | 11)TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 12)1006.1.3.1 PENETRATIONS INTO AND |
| | THROUGH A STAIRWAY ENCLOSURE ASSEMBLY |
| | ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, DUCTWORK AND EQUIPMENT NECESSARY |
| | FOR THE INDEPENDENT STAIR PRESSURIZATION |
| | SPRINKLER PIPING, STANDPIPES AND ELECTRI |
| | CALCONDUIT SERVING THE STAIRWAY AND |
| | TERMINATING AT A STEEL BOX NOT EXCEEDING |
| | 16 SQ IN. SUCH PENETRATIONS SHALL BE PRO |
| | TECTED IN ACCORDANCE WITH 705.4 |
| | |
| | 13)1503.4 ROOF DRAINS UNLESS ROOFS ARE |
| | SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF |
| | DRAINS SHALL BE INSTALLED AT THE LOWEST |
| | POINT OF THE ROOF. WHERE REQUIRED FOR |
| | ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED |
| | AS DETERMINED BY THE ROOF SLOPE AND CON- |
| | TRIBUTING ROOF AREA. |
| | |
| | 14)1503.4.2 OVERFLOW DRAINS SHALL BE |
| | THE SAME SIZE AS ROOF DRAINS, INSTALLED |
| | WITH THE INLET FLOW LINE LOCATED 2" |
| | ABOVE THE LOWEST POINT OF THE ROOF LINE. |
| | OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| | 4"IN HEIGTH AND SHALL BE PLACED IN WALLS |
| | OR PARARETS WITH THE INLET FLOW LINE |
| | NOT LESS THAN 2" ABOVE THE ROOF SURFACE. |
| | |
| | 15)1511.7 ROOF MOUNTED MECHANICAL UNIT |
| | S SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGTH IN ACCORDANCE WITH TABLE 1511.7. |
| | |
| | 16)3003.6.2 VENTS SHALL BE LOCATED |
| | BELOW THE FLOOR OR FLOORS AT THE TOP OF |
| | THE HOISTWAY, AND SHALL BE EITHER DIR- |
| | ECTLY TO THE OUTER AIR OR THROUGH NON- |
| | COMBUSTIBLE DUCTS TO THE OUTER AIR. |
| | |
| | 17)3003.6.3 THE AREA OF THE VENTS |
| | SHALL BE NOT LESS THAN 3 SQ FT FOR EACH |
| | ELEVATOR CAR, WHICHEVER IS GREATER. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |