Plan Review Details - Permit 03060274
Plan Review Stops For Permit 03060274
Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2005-12-05 Cont ID  
Sent By shill Date 2005-12-05 Time 11:45 Rev Time 0.50
Received By shill Date 2005-12-05 Time 11:45 Sent To  
Notes
2005-12-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 STAIR SUBMITTAL
  
 1.)ALL SUBMITTALS ARE TO BE REVIEWED
 BY DESIGNER OF RECORD.
  
 2.)SEE SHEETS 10 AND 16.THE HANDRAIL
 EXTENSION AT THE TOP OF THE STAIRS IS TO
 BE PARALLEL WITH THE FLOOR SURFACE,
 FBC11-4.9.4(2), FBC1007.5.5.
  
 3.)PLEASE CLARIFY AS TO WHY THE
 HANDRAIL EXTENSION DETAIL ON SHEET 11 IS
 NOT THE SAME AS SHEET 10, WHICH IS
 COMPLIANT.SEE FBC11-4.9.4, FBC FIGURE
 19.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2005-12-05 Cont ID  
Sent By shill Date 2005-12-05 Time 11:30 Rev Time 0.50
Received By shill Date 2005-12-05 Time 11:30 Sent To  
Notes
2005-12-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FIREPROOFING SUBMITTAL
  
 1.)ALL SUBMITTALS ARE TO BE REVIEWED
 BY DESIGNER OF RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2005-10-03 Cont ID  
Sent By shill Date 2005-10-03 Time 09:25 Rev Time 0.50
Received By shill Date 2005-10-03 Time 09:25 Sent To  
Notes
2005-10-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE SEALED DETAIL HAS A PHOTOPCY OF
 A SIGNATURE.THIS IS NOT ACCEPTABLE AS
 PER FBPE.IF YOU DISAGREE, PLEASE
 CONTACT FBPE FOR CLARIFICATION AND
 PROVIDE ME WITH THE NAME OF AN
 INDIVIDUAL WHO I CAN SPEAK WITH.
 OTHERWISE, SUBMIT ONLY SIGNED, SEALED
 AND DATED ORIGINALS.
  
 2.)THE TITLE BLOCK IS NOT IN
 COMPLIANCE WITH FAC61G15-23.002. IT IS
 MISSING THE FOLLOWING:CA NUMBER FOR
 THE FIRM, PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE
 DOCUMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2005-07-12 Cont ID  
Sent By shill Date 2005-07-12 Time 17:10 Rev Time 0.50
Received By shill Date 2005-07-12 Time 17:10 Sent To PC
Notes
2005-07-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE DETAIL PREPARED BY ONM&J WAS A
 PHOTOCOPY.ALL DOCUMENTS SUBMITTED FOR
 PUBLIC RECORD PREPARED BY AN ENGINEER
 ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2005-07-12 Cont ID  
Sent By shill Date 2005-07-12 Time 17:02 Rev Time 0.50
Received By shill Date 2005-07-12 Time 17:02 Sent To PC
Notes
2005-07-12 00:00:00FLOOR & ROOF TRUSS ENGINEERING
 LINTON TRUSS/JULIUS LEE PE
  
 GLASS SHOPS PREPARED BY F BENNARDO PE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 09:59 Rev Time 1.00
Received By shill Date 2005-06-09 Time 09:59 Sent To PC
Notes
2005-06-09 00:00:00S1 - S5 (NOTE - NO CHANGES ON S1 - S3)
 DATED 5/23/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-05-19 Cont ID  
Sent By shill Date 2005-05-19 Time 15:00 Rev Time 0.50
Received By shill Date 2005-05-19 Time 15:00 Sent To PC
Notes
2005-05-19 00:00:00****CORRECTIONS****
 TRUSS SUBMITTAL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE ATTCHED FROM THE SIMPSON
 CATALOG.THE LOADS ON THE CONNECTOR
 SCHEDULE PROVIDED ARE HIGHER THAN THE
 CATALOG.ALSO, WHAT IS THE LAST COLUMN,
 WIND (133)?
  
 2.)APPARENTLY THE EOR HAS REDLINED THE
 FLOOR LOADING.THE LOADING REQUIRED BY
 EOR IS HIGHER THAN THE LOADS INDICATED
 IN THE ENGINEERING.
  
 3.)A TITLE BLOCK IS REQUIRED ON THE
 TRUSS ENGINEERING, FAC61G15-23.002.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-03-25 Cont ID  
Sent By shill Date 2005-03-25 Time 16:47 Rev Time 1.00
Received By shill Date 2005-03-25 Time 16:47 Sent To PC
Notes
2005-03-25 00:00:00TRUSS ENGINEERING
 PARTIAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-04-06 Cont ID  
Sent By shill Date 2004-04-06 Time 15:35 Rev Time 2.00
Received By shill Date 2004-04-06 Time 15:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-01-29 Cont ID  
Sent By shill Date 2004-01-28 Time 15:25 Rev Time 4.00
Received By shill Date 2004-01-28 Time 15:25 Sent To  
Notes
2004-01-28 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LISTS IN REGARDS TO
 PRODUCT APPROVALS.ANY TEST REPORTS
 REQUIRED BUT NOT SUBMITTED WILL REQUIRE
 SEPARATE PERMITS.
  
 2.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED (90 DAYS WITHOUT COMMENCING
 WORK), FS713.13.THIS MAY BE PROVIDED
 AT TIME OF PERMIT ISSUANCE.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 4.)SEE PREVIOUS LIST, ITEM #5.THE
 PLANS STILL SHOW CASEMENT WINDOWS.
 SEE THE WINDOW SPRINKLER DOCUMENTATION;
 FIXED GLASS ONLY ALLOWED.
  
 5.)SEE ATTACHED NOTICE IN REGARDS TO
 FS553.80(2)(B).A 4X FEE HAS BEEN
 CHARGED (REQUEST FOR SPRINKLER PLANS
 NOT ADDRESSED THREE TIMES).SEE ITEM
 #5 ABOVE.THIS IS THE SECOND TIME THAT
 THIS CORRECTION HAS BEEN MADE.A
 SECOND 4X FEE WILL BE CHARGED IF THIS
 IS NOT ADDRESSED ON THE NEXT REVIEW.
 SEE ATTACHED BZ235301.
  
 6.)BEFORE RESUBMITTING, HAVE ANY
 REVISED SHEETS STAMPED BY THE HISTORIC
 PRESERVATION DIVISION.
  
 7.)THE HYDRAULIC CALCULATIONS ARE
 REQUIRED TO HAVE THE ENGINEER'S
 INFORMATION INCLUDED ON THE COVER
 SHEET.
  
 8.)THE MODEL WS SPRINKLER HEAD IS
 REQUIRED TO BE A MINIMUM OF 6' FROM
 STANDARD SPRINKLER HEADS, SEE 2ND FLOOR
 PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-11-07 Cont ID  
Sent By hpiskura Date 2003-11-07 Time 08:33 Rev Time 0.00
Received By hpiskura Date 2003-11-07 Time 08:33 Sent To  
Notes
2003-11-07 00:00:00THIS IS THE FOURTH REQUEST FOR THE
 DESIGN INFORMATION OF THE FIRE
 PROTECTION SYSTEM TO BE PROVIDED THE
 PLANS.
  
 THE CARRIBBEAN FIRE & ASSOCIATES
 HYDRAULIC CALCULATIONS DO NOT COMPRISE
 A DESIGN.SEE NFPA 13-99 CHAPTER 8,
 SECTION 8-1.1.1 AND THE FLORIDA
 ADMINISTRATIVE CODE CHAPTER 61G15-32
 RESPONSIBILITY RULES OF PROFESSIONAL
 ENGINEERS CONCERNING THE
 DESIGN OF FIRE PROTECTION SYSTEMS.
  
 THE PLANS DO NOT REFLECT ACCOMODATION OF
 THE TYCO/CENTRAL SPRINKLER HEADS AS
 DESCRIBED IN THE TWO CUT SHEETS
 PROVIDED.
  
 AN ACCEPTABLE INSTALLATION METHOD IS
 THAT CONTAINED IN THE NER REPORT #516
 AND THE MANUFACTURER'S PUBLISHED
 INSTRUCTIONS.
  
 SOME OF THE EXISTING CONFLICTS ARE:
 1) OPERABLE WINDOWS, THE DESIGN REQUIRES
 FIXED GLASS.
 2) HORIZONTAL MULLIONS, THE DESIGN DOES
 NOT ALLOW THEM.
 3) DELUGE HEADS ON THE EXTERIOR AND
 INCLUDED IN THE MOST DEMANDING AREA OF
 THE HYDRAULIC CALCUALATIONS.
  
 SEE NOTES #2 & #6 ON THE 8/26/03 LIST.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-08-26 Cont ID  
Sent By hpiskura Date 2003-08-26 Time 15:13 Rev Time 0.00
Received By hpiskura Date 2003-08-26 Time 15:13 Sent To  
Notes
2003-08-26 00:00:001THE REQUESTED SIGNED SEALED AND
 DATED SURVEY HAS NOT BEEN PROVIDED.
  
 2THIS IS THE THIRD REQUEST FOR THE
 FIRE SPRINKLER PROTECTION DESIGN.THE
 ARCHITECT'S LETTER DATED 8/18/03
 DECLARING COMMENTS 1, 2 & 3 ARE THE
 CONTRACTOR'S RESPONSIBILITY IS NOT
 WITHSTANDING.FLORIDA STATUTE 553.80
 (2) (B) REQUIRES A FEE TO BE PAID OF
 FOUR TIMES THE AMOUNT OF THE PLAN
 REVIEW PORTION EACH TIME AFTER THE
 THIRD REVIEW. THIS IS IN ADDITION TO
 ANY OTHER FEES THAT MAY BE DUE.SEE
 THE ATTACHED NOTICE AND FBC 104.3.1.1
 #5.
  
 3THIS IS THE THIRD REQUEST FOR THE
 FIRE DESIGN NUMBER OF THE "NEW"
 EXTERIOR MASONRY WALLS AND INFILL AREAS.
 THE ARCHITECTS CITATION FOR THE
 EXISTING WALLS IS NOTED.SEE FBC
 701.5.1.
  
 4AS PREVIOUSLY NOTED, FBC TABLE 600
 REQUIRES "THREE" HOUR FIRE RATING FOR
 EXTERIOR WALLS LOCATED 0' - 3' FROM A
 COMMON PROPERTY LINE FOR TYPE V
 CONSTRUCTION, NOT THE DECLARED TWO HOUR.
 PLEASE REVISE AS NECESSARY AND SEE ITEM
 #3 ABOVE.
  
 5WITH THE ABOVE FIRE SPRINKLER DESIGN
 INFORMATION INCLUDE THE LISTING, TEST
 DATA FOR THE HEADS THAT WILL PROVIDE A
 TWO HOUR FIRE RATEDOPENING PROTECTION.
  
 6COMMENTS IN THE TWO PREVIOUS LISTS
 REMAIN WITH REGARDS TO IMPACT FEES,
 NOA'S FOR THE DOORS, WINDOWS AND ROOF
 COVERINGS, AND THE PROPRIETARY MASONRY
 IN THE U905DESIGN.THESE ARE NOT
 CAUSE FOR REJECTION BUT ADVISORY TO THE
 CONTRACTOR AND OWNER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-29 Cont ID  
Sent By hpiskura Date 2003-07-29 Time 09:57 Rev Time 0.00
Received By hpiskura Date 2003-07-29 Time 09:57 Sent To  
Notes
2003-07-29 00:00:001THE PROPERTY SURVEY'S PROVIDED ARE
 NOT SIGNED AND SEALED.PLEASE PROVIDE
 COPIES WITH ORIGINAL SIGNATURE AND
 EMBOSSED SEAL.
  
 2AS NOTED IN THE PREVIOUS CODE
 COMMENTS THE FIRE SPRINKLER SYSTEM
 DESIGN IS REQUIRED TO BE ON THE PERMIT
 PLANS.SEE FBC 104.3.1.1, #5.
  
 3THE ARCHITECT'S RESPONSE MEMO DATED
 7/18/03 REFERENCING A MEETING WITH THE
 BUILDING OFFICIAL IMPLIES THAT AN
 APPROVAL WAS GRANTED AT THAT TIME.IT
 WAS AND IS THE BUILDING OFFICIAL'S
 INTENTION THAT ANY CODE VARIANCES MAY
 COME ONLY THROUGH THE CITY'S
 CONSTRUCTION BOARD OF ADJUSTMENTS AND
 APPEALS FOR WHICH THERE IS AN
 OUTSTANDING APPLICATION DATED 3/03.
  
 THEREFORE THE TABLE 600 ISSUES REMAIN
 TO BE RESOLVED AS WELL AS THE
 EXTERIOR WALL RATINGS.
  
 4THE ORIGINAL PERMIT APPLICATION IS
 NOT INCLUDED WITH THE RE-SUBMITTED
 PLANS.
  
 5AS PREVIOULSY NOTED, THIS PROJECT IS
 SUBJECT IMPACT FEES COLLECTED BY THE
 COUNTY PRIOR TO PERMIT ISSUE.
  
 6SHEET A9.2, DESIGN # U905 REQUIRES
 THE BLOCK MANUFACTURER TO BE A UL
 CERTIFICATE HOLDER.PLEASE VERIFY THIS
 WITH YOUR VENDOR AND PROVIDE
 DOCUMENTATION TO THIS OFFICE.
  
 7IF TEST AND/OR NOTICE OF ACCEPTANCE
 REPORTS ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION FOR THE WINDOWS,
 DOORS AND ROOF COVERING, SEPARATE
 PERMITS, PLANS AND FEES WILL BE
 REQUIRED FOR THAT PORTION OF THE WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-08 Cont ID  
Sent By hpiskura Date 2003-07-08 Time 09:44 Rev Time 0.00
Received By hpiskura Date 2003-07-02 Time 13:52 Sent To  
Notes
2003-07-08 00:00:001 PLEASE PROVIDE A RECENT PROPERTY
 SURVEY TO DETERMINE LOCATION OF
 ADDITION AND ALTERATIONS.
  
 2THE ADDITION IS SUBJECT TO IMPACT
 FEES COLLECTED BY THE COUNTY.THE
 PERMIT PLANS MUST BE STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 CALL 561-233-5025 FOR MORE INFORMATION.
  
 3THE PERMIT PLANS MUST HAVE THE FIRE
 SPRINKLER DESIGN INFORMATION ON THEM.
 SEE FBC 104.3.1.1.
  
 4THE EAST AND WEST SIDES OF THIS
 BUILDING ARE ZERO LOT LINE SETBACK AND
 FBC TABLE 600 DOES NOT ALLOW ANY
 OPENINGS.PLEASE REVISE AS NECESSARY.
  
 5THE SOUTH SIDE, (ALLEY), PROPERTY
 LINE IS MEASURED FROM THE CENTER OF THE
 ALLEY.PLEASE REVISE THAT ELEVATION TO
 BE IN ACCORDANCE WITH FBC TABLE 600 AND
 FBC 705.1.
  
 6THE FRONT AND PROPOSED REAR DOORS
 APPEAR TO SWING OVER THE PUBLIC RIGHT
 OF WAY.SEE FBC 3203.
  
 7SHOW THE METHOD OF COMPLIANCE FOR
 FBC 1803.2 FOR THE FOUNDATION WORK IN
 THE PROXIMITY OF THE ADJACENT BUILDINGS.
  
 8FBC TABLE 600 REQUIRES A THREE HOUR
 FIRE RATING FOR EXTERIOR BEARING WALLS
 LOCATED 0'-3' FROM A PROPERTY LINE IN
 TYPE V CONSTRUCTION.PLEASE SHOW THE
 FIRE DESIGN NUMBER FOR THESE WALLS TO
 BE CONSTRUCTED AND MODIFIED. SEE FBC
 701.5.1.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-10-27 Cont ID  
Sent By dpalmer Date 2003-10-27 Time 16:35 Rev Time 1.00
Received By dpalmer Date 2003-10-27 Time 16:35 Sent To  
Notes
2003-10-27 00:00:00PASSED , PENDING FIRE REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-09-08 Cont ID  
Sent By dpalmer Date 2003-09-08 Time 14:18 Rev Time 0.50
Received By dpalmer Date 2003-09-08 Time 14:18 Sent To  
Notes
2003-09-08 00:00:00********** NOTE ***************
  
 PLEASE SEE FIRE REVIEW COMMENTS.
 SD'S MUST BE 3'FROM KITCHEN DOOR/OPENING
 WHICH THEY APPEAR TO BE. NFPA-72 2-5.2.1
 .6. PLEASE GET WITH MIKE CARSILLO ON
 SD PLACEMENT AND PERHAPS HEAT DETECTORS
 PERMITTTED IN SD'S PLACE?
  
 ELECTRICAL PLANS SEEM TO BE OK.
 PLEASE SEE RISER, SHOWS ALL SUB PANELS
 AS 125A,PANELS ARE SHOWN AS 100A AND 42
 CIRCUIT. PLEASE CORRELATE RISER AND
 PANELS. PLEASE ALSO NOTE, 100A AND 125A
 PANELS DO NOT COME W/ 42 CIRCUITS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION,
 PLEASE SEE FIRE COMMENTS FOR ELEC SHEETS
 PLEASE SEE THAT ELECTRICAL PLANS FOR THE
 MOST PART ARE OK.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
 PLEASE CALL FOR ANY QUESTIONS ABOUT SD'S
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-07-29 Cont ID  
Sent By dpalmer Date 2003-07-29 Time 18:00 Rev Time 0.75
Received By dpalmer Date 2003-07-29 Time 18:00 Sent To  
Notes
2003-07-29 00:00:00************** UNSAT *****************
  
 PLEASE ADDRESS COMMENTS BELOW. PLANS
 ARE COMING BACK FOR OTHER REVIEWERS.
  
 1)NOTE: PLEASE SEE 3W/ SQ FT STILL SHOWN
 AS ROUNDING DOWN ON UNITS B&C,
 PLEASE ALSO SEE LOAD FOR DRYER SHOWN
 AT 3KW. PLEASE SEE MIN PER 220-18
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-24 Cont ID  
Sent By dpalmer Date 2003-06-23 Time 08:00 Rev Time 0.75
Received By dpalmer Date 2003-06-23 Time 08:00 Sent To  
Notes
2003-06-23 00:00:00************ UNSAT ***************
  
 PLEASE SEE COMMENTS FROM FIRE PLAN
 REVIEW FOR POSSIBLE COMENTS THAT WILL
 HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 1)NOTE: MISSING SMOKE DETECTORS AS REQ`D
 INSIDE AND OUTSIDE SLEEPING RMS.
 NFPA-72 8-1
  
 2)NOTE: PLEASE SEE SOME RECEPTS MISSING
 PER 210-52
  
 3)NOTE: PLEASE SHOW ALL RECEPT SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED. 210-8-A6
  
 4)NOTE: PLEASE SEE 210-11C1 FOR A MIN
 OF TWO SMALL APPL CIRCUITS REQ`D.
 EACH AT 1500VA
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS. 210-12
  
 6)NOTE:PLEASE SUBMIT AIC RATINGS FOR
 MAIN AND SUB MAINS. 110-9/215-5
  
 7)NOTE: PLEASE SEE THAT LIGHTING LOAD
 FIGURED FOR UNITS ARE FIGURED TO 3WATTS
 PER SQFT, HOWEVER SOME SHOWN ROUNDING
 DOWN. ROUNDING UP IS PERMITTED, HOWEVER
 ROUNDING DOWN IS NOT.
  
 8)NOTE: PLEASE SEE 600-5 FOR MIN SIGN
 CIRCUIT REQ`D .
  
 9)NOTE: PLEASE SHOW REQ'D SHOW WINDOW
 RECEPTS PER 210-62
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS THAT HAVE AN AFFECT ON ELECTR-
 -ICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2004-01-21 Cont ID  
Sent By mamini Date 2004-01-21 Time 11:12 Rev Time 0.50
Received By mamini Date 2004-01-21 Time 11:11 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2003-10-29 Cont ID  
Sent By mamini Date 2003-10-29 Time 10:37 Rev Time 1.00
Received By mamini Date 2003-10-29 Time 10:37 Sent To  
Notes
2003-10-29 00:00:00FAILED:
 1. PLEASE REFER TO THE REVIEW COMMENTS
 DATED 8-27-03, SEE ATTACHED.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-08-27 Cont ID  
Sent By mamini Date 2003-08-27 Time 09:56 Rev Time 1.00
Received By mamini Date 2003-08-27 Time 09:56 Sent To  
Notes
2003-08-27 00:00:00FAILED:
 1. SHEET P-1 AND P-2 REFERS TO CIVIL
 DRAWING FOR EXACT LOCATION FOR
 CONNECTIONS AND CONTINUATION OF SANITARY
 , STORM WATER AND DOMESTIC WATER, NO
 CIVIL PLANS HAS BEEN PROVIDED.
 2. PLEASE NOTE THAT ANY NEW CONNECTIONS
 TO CITY SERVICES REQUIRES APPROVAL FROM
 PUBLIC UTILITIES & ENGINEERING,659-8040
 3. BACKFLOW ASSEMBLY MUST BE LOCATED ON
 PROPERTY AND LOACTION MUST BE APPROVED
 BY PUBLIC UTILITIES & ENGINEERING,
 659-8040.
 4. SHEET P-1, FIRST FLOOR PLAN-SANITARY,
 NOTE THAT STORM DRAIN LEADER SHUOLD BE
 CONNECTED TO STORM DRAINAGE AND
 SANITARY DRAIN TO SANITARY SYSTEMS,
 PLEASE VERIFY.
 5. KEYNOTES, NUMBRING THROUGHOUT THE
 BUILDING FROM FLOOR TO FLOOR NOT
 CONSISTENCE, SHEET P-1 AND P-2, PLEASE
 VERIFY.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-07-08 Cont ID  
Sent By mamini Date 2003-07-08 Time 10:27 Rev Time 0.50
Received By mamini Date 2003-07-08 Time 10:27 Sent To  
Notes
2003-07-08 00:00:00FAILED:
 1. PLEASE STATE IF GARBAGE IS TO BE
 PICKED UP BY THE CITY OR IF IT IS
 PRIVATE PICKUP, IF TO BE PICKED UP BY
 THE CITY THEN THE CITY REQUIREMENTS MUST
 BE MET. SEE ATTACHED.
 2. DOORS FOR THE DUMPSTER AS PROPOSED
 COULD NOT SWING OPEN INTO THE PUBLIC
 R.O.W.
 3. DUMPSTER AS PROPOSED MUST BE APPROVED
 BY THE SANITATION DEPARTMENT 659-8048
 EXT. 2273 , JOHNNY THOMAS.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2004-04-01 Cont ID  
Sent By mcarsill Date 2004-04-01 Time 15:47 Rev Time 0.00
Received By mcarsill Date 2004-04-01 Time 15:47 Sent To  
Notes
2004-04-01 00:00:001) FIRE ALARM CIRCUITS TO BE CLASS A
 OR FULLY ADDRESSABLE.
  
 2) ANY ELECTRONIC LOCKING DEVICES SHALL
 MEET THE REQUIREMENTS OF NFPA 101,
 CHAPTER SEVEN.
  
 3) FIRE SPRINKLER SYSTEM INSTALLATION
 SHALL MEET THE REQUIRMENTS OF NFPA 13,
 1999 EDITION. A FIRE DEPARTMENT
 CONNECTION IS REQUIRED.
  
 4) ARCHITECTURAL PLANS INDICATES THAT
 EXTERIOR COVERED AREA TO BE FULLY
 SPRINKLERED. THE SPRINKLER PLANS
 DO NOT SUGGEST IT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2004-01-08 Cont ID  
Sent By mcarsill Date 2004-01-08 Time 17:36 Rev Time 0.00
Received By mcarsill Date 2004-01-08 Time 17:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-10-31 Cont ID  
Sent By mcarsill Date 2003-10-30 Time 16:45 Rev Time 0.00
Received By mcarsill Date 2003-10-30 Time 16:45 Sent To  
Notes
2003-10-30 00:00:001) FIRE ALARM NOTES # 11 INDICATES
 A SUPERVISORY SIGNAL UPON ACTIVATION
 OF DUCT SMOKE DETECTORS. ACTIVATION
 OF ANY DUCT SMOKE DETECTOR SHALL
 CAUSE THE FIRE ALARM SYSTEM TO ACTIVATE.
  
 2) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION.
  
 3) FIRE ALARM CIRCUITS SHALL BE CLASS A
 OR FULLY ADDRESSABLE.
  
 4) SECURITY LOCKS CONNECTED TO THE
 FIRE ALARM SYSTEM SHALL COMPLY WITH
 EITHER ACCESS CONTROL OR DELAYED
 EGRESS REQUIREMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-09-04 Cont ID  
Sent By mcarsill Date 2003-09-04 Time 15:45 Rev Time 0.00
Received By mcarsill Date 2003-09-04 Time 15:45 Sent To  
Notes
2003-09-04 00:00:001) TACTILE SIGNAGE REQUIRED AT STAIRS.
  
 2) ALL SHAFTWAYS THAT PERSONS CAN FALL
 INTO MUST BE MARKED "SHAFTWAY" WITH
 6" HIGH LETTERS.
  
 3) SIGNS ARE REQUIRED AT ELEVATORS
 DO NOT USE ELEVATORS IN THE EVENT OF
 A FIRE.
  
 4) SINCE FIRE ALARM PERMITS ARE EXPECTED
 AFTER AUGUST 1, 2003, THE FIRE ALARM
 SYSTEM IS EXPECTED TO MEET UL LISTED
 FOR CENTRAL STATION SERVICE SINCE THE
 PERMIT APPLICATION WILL FALL AFTER
 THE AUGUST 1, 2003, IMPLEMENTATION DATE.
  
 5) IT APPEARS THAT SMOKE DETECTORS ARE
 INSTALLED IN THE KITCHENS. SMOKE
 DETECTORS ARE NOT INSTALLED IN KITCHENS
 AREAS. IT DOES APPEAR THAT THE DESIGNER
 IS TRYING TO MEET THE INTENT OF
 SMOKE DETECTORS INSIDE AND OUTSIDE
 THE SLEEPING ROOMS BUT WHAT PREVENTS
 FALSE OR NUISANCE ALARMS. ALSO ARE
 THESE SMOKE DETECTORS SINGLE STATION
 AS REQUIRED OR ARE THEY PLANNED TO
 BE CONNECTED TO THE FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-08-11 Cont ID  
Sent By nmccray Date 2003-08-11 Time 14:23 Rev Time 0.00
Received By nmccray Date 2003-08-11 Time 14:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By mcarsill Date 2003-07-01 Time 07:36 Rev Time 0.00
Received By mcarsill Date 2003-07-01 Time 07:36 Sent To  
Notes
2003-07-01 00:00:001) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 2) SUITABLE EXITS ARE TO BE PROVIDED
 DURING DEMOLITION, RENOVATION AND
 CONSTRUCTION ACTIVITIES.
  
 3) PLEASE INDICATE LOCATIONS OF ALL
 SMOKE DETECTORS CONTAINED WITHIN THE
 APARTMENTS. ELECTRIC POWERED SMOKE
 DETECTORS ARE REQUIRED INSIDE AND
 OUTSIDE OF ALL SLEEPING ROOMS.
  
 4) PLEASE PROVIDE MORE DETAILS ON NOTE
 19 ON PAGE A3.1. "PROVIDE TWO HOUR
 FIRE SPRINKLER HEADS (1 EXTERIOR, 1
 INTERIOR) ABOVE EACH WINDOW.
  
 5) PLEASE PROVIDE A NOTE ABOUT EGRESS
 WINDOWS. PLEASE EXPLAIN EXEPTIONS THAT
 YOU ARE USING.
  
 6) NO FIRE SPRINKLER PLANS PROVIDED.
  
 7) A KNOX-BOX WILL BE REQUIRED.
  
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-11-17 Cont ID  
Sent By adarroug Date 2005-11-17 Time 13:28 Rev Time 0.00
Received By adarroug Date 2005-11-17 Time 13:28 Sent To B
Notes
2005-11-17 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-09-30 Cont ID  
Sent By adarroug Date 2005-09-30 Time 15:49 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 15:49 Sent To B
Notes
2005-09-30 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-07-26 Cont ID  
Sent By adarroug Date 2005-07-26 Time 11:07 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 11:07 Sent To M
Notes
2005-07-26 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 15:58 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 15:58 Sent To B
Notes
2005-07-12 00:00:00TO "SHILL" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 14:44 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 14:44 Sent To P
Notes
2005-07-06 00:00:00TO "P" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 08:49 Rev Time 0.00
Received By shill Date 2005-06-08 Time 08:49 Sent To B
Notes
2005-06-08 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-05-17 Cont ID  
Sent By adarroug Date 2005-05-17 Time 16:43 Rev Time 0.00
Received By adarroug Date 2005-05-17 Time 16:43 Sent To B
Notes
2005-05-17 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-25 Cont ID  
Sent By adarroug Date 2005-03-25 Time 11:33 Rev Time 0.00
Received By adarroug Date 2005-03-25 Time 11:33 Sent To B
Notes
2005-03-25 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-03-31 Cont ID  
Sent By alange Date 2004-03-31 Time 16:14 Rev Time 0.00
Received By alange Date 2004-03-31 Time 16:14 Sent To  
Notes
2004-03-31 00:00:00TO COMMERCIAL BOARD #59

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 13:43 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 13:43 Sent To  
Notes
2003-12-30 00:00:00TO COMM BD#63

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 14:52 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 14:52 Sent To  
Notes
2003-10-24 00:00:00TO COMM BD#62

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-08-25 Time 13:44 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 13:44 Sent To  
Notes
2003-08-25 00:00:00ON COMM BD #38

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-23 Cont ID  
Sent By alange Date 2003-07-23 Time 10:44 Rev Time 0.00
Received By alange Date 2003-07-23 Time 10:43 Sent To  
Notes
2003-07-23 00:00:00IN COMM BOX #48

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-05 Cont ID  
Sent By shernand Date 2003-06-05 Time 11:30 Rev Time 0.00
Received By shernand Date 2003-06-05 Time 11:30 Sent To  
Notes
2003-06-05 00:00:00COMM BOARD #33

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-08-01 Cont ID  
Sent By prafter Date 2005-08-01 Time 08:10 Rev Time 0.50
Received By prafter Date 2005-08-01 Time 08:10 Sent To  
Notes
2005-08-01 00:00:00MECH. PLAN REVIEW:
  
 A/C REV. #6 R.T.U. CURB DWTAIL.
  
 PR 8/1/05.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-11-18 Cont ID  
Sent By pkrauss Date 2003-11-18 Time 08:50 Rev Time 0.45
Received By pkrauss Date 2003-11-18 Time 08:46 Sent To  
Notes
2003-11-18 00:00:00PROVISO:
 PLEASE NOTE THE LOCATION OF THE FRESH
 AIR INTAKE IN RELATION TO THE DUMPSTER.
 AS PER 2001 FBC(M) INTAKE OPENINGS SHALL
 BE LOCATED A MINIMUM OF 10 FT FROM ANY
 NOXIOUS CONTAMINANT (ALLEYS, PARKING LOT
 & LOADING DOCKS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-09-23 Cont ID  
Sent By pkrauss Date 2003-09-23 Time 13:19 Rev Time 0.35
Received By pkrauss Date 2003-09-23 Time 13:05 Sent To  
Notes
2003-09-23 00:00:00PROVISO:
 PLEASE PROVIDE OUTSIDE CALCULATIONS FOR
 THE FIRST FLOOR "SALES SPACE 10" WITH
 RESUBMITTAL.
  
 PLEASE PROVIDE INFORMATION ON THE FIRST
 FLOOR IN RESPECT TO VENTILATION.
 MINIMUM VENTILATION REQUIRED EVEN THOUGH
 BUILD-OUT OF THE FIRST FLOOR WILL BE
 ADDRESSED UNDER A SEPARATE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-08-12 Cont ID  
Sent By pkrauss Date 2003-08-12 Time 07:57 Rev Time 0.40
Received By pkrauss Date 2003-08-12 Time 07:44 Sent To  
Notes
2003-08-12 00:00:00DENIED:
  
 ONE SET OF PLANS IS MISSING PLAN SHEETS
 M-3 AND M-4.PLEASE PROVIDE TWO
 COMPLETE SET OF PLANS FOR REVIEW.
 PLANS ARE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-26 Cont ID  
Sent By hmoser Date 2003-06-26 Time 19:28 Rev Time 1.50
Received By hmoser Date 2003-06-26 Time 19:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-07-19 Cont ID  
Sent By jleech Date 2005-07-19 Time 13:53 Rev Time 1.00
Received By jleech Date 2005-07-19 Time 13:53 Sent To  
Notes
2005-07-19 00:00:00REVISED PAGE P-1 RWL'S TO GO OUT BACK
 INSTEAD OF THE FRONT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-07 Cont ID  
Sent By kstevens Date 2003-08-07 Time 16:39 Rev Time 1.50
Received By kstevens Date 2003-08-07 Time 16:39 Sent To  
Notes
2003-08-07 00:00:00PASSED/PROVISO
  
 EMERGENCY STORM RISER PIPE SIZES TO RE-
 FLECT PIPE SIZES SHOWN ON SHEET P-1

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-25 Cont ID  
Sent By kstevens Date 2003-06-25 Time 09:31 Rev Time 2.75
Received By kstevens Date 2003-06-24 Time 12:37 Sent To  
Notes
2003-06-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 CHAP. 1, AMENDMENTS
 ADMIN CODE
 FHA-98 DESIGN MANUAL
 FBC-2001 MECHANICAL
  
 1) SHT A2.1 FIRST FLOOR PLAN DETAIL #1.
 PER TABLE 403.1 A UNISEX TOILET ROOM
 COMPLYING WITH 11-4.22 AND A DRINKING
 FOUNTAIN ARE REQUIRED.
 2) SHT A2.1 SECOND FLOOR PLAN DETAIL #2,
 PER TABLE 403.1 AUTOMATIC CLOTHES WASHER
 CONNECTION REQUIRED. (ALSO SEE FOOTNOTE
 "F").
 3) SHT A5.1 SHOW CLEAR FLOOR SPACE ON
 TYPICAL TOILET ROOM PLAN DETAIL #1, AND
 TYPICAL KITCHEN PLAN DETAIL #3 PER FHA
 DESIGN MANUAL PAGE 7.43
 4) SHT A5.1 DETAIL #1 INDICATE MEASURE-
 MENT OFF TUB AND LAV TO CENTER LINE OF
 W/C. MINIMUM 18" REQUIRED OFF 1 FIXTURE
 OR THE OTHER AND MINIMUM OPENING REQUIR-
 ED IS 33". PLEASE SHOW OPENING SIZE.
 SEE FIGURES 1, 2, OR 3 PAGE 7.43 DESIGN
 MANUAL
 5) SHT P-1 DETAIL #03, SUBMIT CALCULAT-
 IONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS PER SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. CHECK OF NORTH SECTION OF
 ROOF SCALES OUT 47.83 FT TIMES 24.83 FT
 EQUALS 1,188 SQ.FT. NOT COUNTING 1/2
 AREA OF VERTICAL WALLS, INCLUDING PARA-
 PETS. (SECTION 1106.4). PLAN SHOWS 1,109
 SQ.FT. PLEASE CLAIRFY. SHOW CALCULATIONS
 FOR EACH AREA, NORTH, CENTER , & SOUTH.
 ALSO SHOW AREAS OF ROOF THAT DRAIN ONTO
 THE ROOF SECTIONS FROM ABOVE, I.E.
 STAIRWAYS & MECHANICAL ROOMS ECT. SECT-
 ION 1106.2
 6) SHT P-1 DETAIL #2, SECOND FLOOR SANT.
 STATES "EWH DRAIN LINE PROVIDE TRAP"
 PLEASE CLAIRFY, IS THIS A CONDENSATE
 LINE OR THE PAN DRAIN LINE FOR THE
 ELECTRIC WATER HEATER?
 7) SHT P-4 WATER ISOMETRIC, AIR CHAMBERS
 ARE NOT APPROVED. (TUB/SHOWER VALVES).
 DELETE FROM RISERS. WATER HAMMER ARREST-
 ORS AT WATER HEATERS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING. PDI-WH201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 8) SUBMIT RISER DIAGRAM FOR EMERGENCY
 PAN DRAINS FOR WATER HEATERS. SHOW PIPE
 SIZE AND INDICATE TYPE OF MATERIAL.
 SECTION 504.8, 504.8.1, & 504.8.2.
 9) SHT P-6 PLUMBING SPECIFICATIONS #2-M
 ADOPTED CODE IS FBC-2001 PLUMBING, NOT
 STANDARD CODE 1999 EDITION. CHANGE REF-
 ERENCE. - #3-L AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM REFERENCE. SECTION
 604.9- #4-F AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM REFERENCE.
 10) INDICATE ON PLANS IF SPECIFICATION
 "A" OR "B" WILL BE FOLLOWED FOR THE
 BATHROOMS IN EACH UNIT. PAGES 7.34 &
 7.35FHA DESIGN MANUAL.
 11) ARCHITECTURAL SHEETS - 61G1-16.004
 FIRM LICENSES NUMBER IS REQUIRED ON THE
 TITLE BLOCK
 12) SHT P-3 CONDENSATE DRAIN ISOMETRIC.
 UNABLE TO FIND THE REST OF THE CONDENS-
 ATE RISER DIAGRAM REFERED TO ON THE
 MECHANICAL PLANS. SUBMIT A COMPLETE
 CONDENSATE RISER DIAGRAM SHOWING ALL
 PIPE SIZES AND MATERIAL USED.
 13) SHT M-1 CONDENSATE FROM ROOF UNITS
 SHOW SOME DRAINING TO THE ROOF DRAINS,
 AND OTHERS DRAINING TO THE SECONDARY
 ROOF DRAINS. ALL SHALL DRAIN TO THE
 ROOF DRAINS. SECTION M307.2.1(3).
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-27 Cont ID  
Sent By mmclean Date 2003-06-27 Time 15:29 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-06-27 00:00:006/27/03 PASS PER ANTHIA MM