Plan Review Details - Permit 03060241
Plan Review Stops For Permit 03060241
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-15 Cont ID  
Sent By jwitmer Date 2003-07-15 Time 07:40 Rev Time 0.75
Received By jwitmer Date 2003-07-15 Time 07:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By jwitmer Date 2003-07-01 Time 13:19 Rev Time 1.00
Received By jwitmer Date 2003-07-01 Time 13:19 Sent To  
Notes
2003-07-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03060241
 ADD: 2450 METROCENTRE
 CONT: MJS CONSTRUCTION
 TEL: (561)512-7722
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) ROOMS 101 & 115 ARE INDICATED AS
 EXITS, WITH EXIT SIGNS IN THE ROOM, WILL
 THESE OFFICES EVER BE LOCKED? 1001.1.3
 MEANS OF EGRESS SHALL CONSIST OF CONTIN-
 UOUS AND UNOBSTRUCTED PATH OF TRAVEL TO
 THE EXTERIOR OF THE BUILDING.
  
 2) HANDICAPPED RESTROOM STALL, 11-4.2.3
 INDICATE AN UNOBSTRUCTED TURNING SPACE.
  
 3)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By dpalmer Date 2003-07-17 Time 12:39 Rev Time 0.50
Received By dpalmer Date 2003-07-17 Time 12:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-06-16 Cont ID  
Sent By dpalmer Date 2003-06-16 Time 12:37 Rev Time 0.50
Received By dpalmer Date 2003-06-16 Time 12:37 Sent To  
Notes
2003-06-16 00:00:00NOTES REDLINED FOR CIRCUITING OF EM/ EXT
 LTS. 700-12E.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By mcarsill Date 2003-07-17 Time 16:10 Rev Time 0.00
Received By mcarsill Date 2003-07-17 Time 16:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By mcarsill Date 2003-07-01 Time 07:45 Rev Time 0.00
Received By mcarsill Date 2003-07-01 Time 07:45 Sent To  
Notes
2003-07-01 00:00:001) WHERE DOES THE EXIT SIGN FROM HALL
 110 DIRECT PERSONS.
  
 2) HOW DO PERSONS LOCATE THE EXIT DOOR
 IN OFFICE 101. WHAT DIRECTS THEM.
  
 3) HOW ARE THE EXIT DOORS IN EXECUTIVE
 OFFICE 115 AND 101 MAINTAINED FROM BEING
 BLOCKED WITH FURNITURE.
  
 4) ANY EMERGENCY LIGHTS IN HALL 110.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-09 Cont ID  
Sent By shernand Date 2003-07-09 Time 15:34 Rev Time 0.00
Received By shernand Date 2003-07-09 Time 15:34 Sent To  
Notes
2003-07-09 00:00:00COMM BOARD #27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-06-04 Time 13:27 Rev Time 0.00
Received By shernand Date 2003-06-04 Time 13:27 Sent To  
Notes
2003-06-04 00:00:00COMM BOARD #30

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-02 Cont ID  
Sent By pkrauss Date 2003-07-02 Time 15:26 Rev Time 0.40
Received By pkrauss Date 2003-07-02 Time 15:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-22 Cont ID  
Sent By kstevens Date 2003-07-22 Time 07:53 Rev Time 0.75
Received By kstevens Date 2003-07-21 Time 16:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-07-17 Cont ID  
Sent By kstevens Date 2003-07-17 Time 10:11 Rev Time 0.50
Received By kstevens Date 2003-07-17 Time 10:11 Sent To  
Notes
2003-07-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW.
 1) SHOW CLEAR FLOOR SPACE FOR ALL HDCP
 FIXTURES PER11-4.18.3, AND 11-4.24.5
 2) INDICATE HEIGHT FOR HDCP URNAL PER
 11-4.18.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-23 Cont ID  
Sent By kstevens Date 2003-06-23 Time 14:17 Rev Time 1.00
Received By kstevens Date 2003-06-23 Time 14:17 Sent To  
Notes
2003-06-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 1 SHOW CLEAR FLOOR SPACE FOR
 REQUIRED HDCP FIXTURES PER SECTIONS
 11-4.16.2, 11-4.18.3, 11-4.19.3 & 11-4.
 24.5. ALSO SHOW 5' TURNING CIRCLES IN
 TOILET ROOMS. (NOT REQUIRED IN STALLS)
 2) SHT 1 INDICATE HEIGHT FOR URNAL PER
 SECTION 11-4.18.2
 3) SHT 5 SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. EXISTIN TOILET
 ROOM, (#117), NOT SHOWN ON RISER DIAG.
 ONLY 3 W/C'S ARE SHOWN IN WOMENS TOILET
 ROOM. ONLY 2 LAVS ARE SHOWN IN WOMENS
 TOILET ROOM. ONLY 1 LAV SHOWN IN MENS
 TOILET ROOM, (#106). TWO TRAPS UPSTREAM
 OF URINALS, ARE THEY FLOOR DRAINS??
 ON STACK WITH NEW SINK AND EXISTING SINK
 THERE IS ANOTHER EXISTING SINK AND AN
 EXISTING LAV THAT ARE NOT SHOWN ON THE
 FLOOR PLAN.ALL 5 LAVS SHALL BE SHOWN
 DOWNSTREAM OF UNINALS.
 2) SUBMIT A WATER RISER DIAGRAM. SHOW
 ALL WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9. LOCATE ARRESTORS NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT AT
 THE TOP OF THE DROPS IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION IN-
 STRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692