| Plan Review Stops For Permit 03060236 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-07-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-07-21 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-07-21 |
Time |
10:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-07-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2003-07-08 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-07-08 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2003-07-08 00:00:00 | THE COMBINATION OF CORRIDORS SHOWN ON | | | SHEET 3 AS HALLWAY 114 AND HALLWAY 116 | | | IS A DEAD END CORRIDOR GREATER THAN | | | TWENTY FEET IN LENGTH AND IS | | | PROHIBITTED BY FBC TABLE 1004 FOR GROUP | | | B OCCUPANCIES.PLEASE REVISE AS | | | NECESSARY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-22 |
Time |
11:02 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-10-22 |
Time |
11:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-08-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-08-04 |
Time |
12:47 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-08-04 |
Time |
12:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-07-21 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-07-31 |
Time |
15:42 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-07-21 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2003-07-21 00:00:00 | *********** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE THAT ONLY ONE | | | REVISED ELECTRICAL SHEET 5EWAS | | | SUBMITTED. | | | | | | 2)NOTE: PLEASE SHOW THE ATTACHMENT FOR | | | TRANSFORMERS AS REQUESTED ON ORIG REVIEW | | | COMMENTS.250-30 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-06-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-06-23 |
Time |
06:50 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-06-23 |
Time |
06:50 |
Sent To |
|
|
| Notes |
| 2003-06-24 00:00:00 | 1)NOTE: PLEASE ALSO SEE CLEARANCE REQ` | | | MENTS FOR MDP AND TRANSFORMER PER 110-26 | | 2003-06-23 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY AND SHOW CONNECT- | | | -ION FOR TRANSFORMERS PER 250-30. | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | @ 125% MIN. (LIGHTING) 215-3/230-42 ETC. | | | SHOW LOAD CALCS.220-3,220-10,220-13 ETC | | | 3)NOTE: PLEASE SHOW SEE MIN SIZING FOR | | | EQUIPMENT GROUNDING CONDUCTORS FOR 30A | | | OCP. 250-122 SOME SHOWN AS #12`S, AND | | | SHOULD BE #10 MIN. | | | | | | 4)NOTE: PLEASE SEE 200A DISCONNECTS FOR | | | HA AND TVSS. IN ELECTRICAL ROOM DIAGRAM | | | SHOWS 200A DISC'C W/ 200A OCP. HOWEVER | | | ELECTRICAL RISER DIAGRAM SHOWS 200A | | | DISC'S W/ 125A OCP? PLEASE CORRELATE. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | THAT MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2003-10-29 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-10-29 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-10-29 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2003-10-29 00:00:00 | REVISION DATED 10-02-03 OK |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-07-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-07-25 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-07-25 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-07-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-07-01 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-07-01 |
Time |
07:33 |
Sent To |
|
|
| Notes |
| 2003-07-01 00:00:00 | 1) ONLY ONE EXIT SIGN IS SHOWN OVER AN | | | EXTERIOR DOOR. PLEASE EXPLAIN TWO EXITS | | | WHEN ONLY ONE IS SHOWN. | | | | | | 2) PLEASE EXPLAIN KIDS GATE AREA. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-07-31 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-07-31 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2003-07-31 |
Time |
15:42 |
Sent To |
E |
|
| Notes |
| 2003-07-31 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-07-17 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-17 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-17 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2003-07-17 00:00:00 | COMM BOARD #25 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-06-20 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-20 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-20 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2003-06-20 00:00:00 | COMM BOARD #34 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-07-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-07-07 |
Time |
09:57 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2003-07-07 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2003-07-07 00:00:00 | PROVISO:MECHANICAL PERMIT 03061650 | | | | | | 1.DUCT SMOKE DETECTOR SHALL BE | | | INSTALLEDIN THE SUPPLY DUCT NOT IN | | | THE RETURN AS DEPICTED ON PLAN SHEET | | | AC-1. 2001 FBC(M) 606.2.1. | | | | | | 2.FAN SHUTDOWN WITH NOTIFICATION | | | REQUIRED AT FINAL.2001 FBC(M) 606.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-07-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-29 |
Time |
07:10 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-07-28 |
Time |
16:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-07-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-10 |
Time |
13:11 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-07-10 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2003-07-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT 7 WOMENTS & MENS RESTROOM ELEVAT- | | | IONS, W/C SHALL BE 18" FROM CENTERLINE | | | OF FIXTURE TO WALL. SHOW ON DETAIL. FIG | | | 28 | | | 2) SHT 7 MENS RESTROOM ELEVATION, URNAL | | | HEIGHT TO COMPLY WITH 11-4.18.2. SHOW ON | | | DETAIL. | | | 3) SHOW CLEAR FLOOR SPACE FOR ALL HDCP | | | FIXTURES. 11-4.16.2, 4.18.3, 4.19.3, AND | | | 4.24.5. | | | 4) MINIMUM FIXTURE TABLE 403.1 AND SHT | | | T PLUMBING FIXTURE CALCULATIONS CALLS | | | FOR A DRINKING FOUNTAIN. NOTE SHOWN. | | | 1 DRINKING FOUNTAIN REQUIRED. ALSO SEE | | | SECTION 410.1 | | | 5) SHT 2-P 3/4" WATER LINE TO CHILLER, | | | RPZ BACKFLOW REQUIRED. | | | 6) RPZ BACKFLOW REQUIRED FOR WATER SERV- | | | ICE TO SPACE. BACKFLOW SHALL BE LOCATED | | | MAXIMUM OF 4' ABOVE FLOOR FOR SERVICE & | | | TESTING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|