Plan Review Details - Permit 03060236
Plan Review Stops For Permit 03060236
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-21 Cont ID  
Sent By hpiskura Date 2003-07-21 Time 10:05 Rev Time 0.00
Received By hpiskura Date 2003-07-21 Time 10:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-08 Cont ID  
Sent By hpiskura Date 2003-07-08 Time 16:13 Rev Time 0.00
Received By hpiskura Date 2003-07-08 Time 16:13 Sent To  
Notes
2003-07-08 00:00:00THE COMBINATION OF CORRIDORS SHOWN ON
 SHEET 3 AS HALLWAY 114 AND HALLWAY 116
 IS A DEAD END CORRIDOR GREATER THAN
 TWENTY FEET IN LENGTH AND IS
 PROHIBITTED BY FBC TABLE 1004 FOR GROUP
 B OCCUPANCIES.PLEASE REVISE AS
 NECESSARY.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-10-22 Cont ID  
Sent By dpalmer Date 2003-10-22 Time 11:02 Rev Time 0.33
Received By dpalmer Date 2003-10-22 Time 11:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-04 Cont ID  
Sent By dpalmer Date 2003-08-04 Time 12:47 Rev Time 1.00
Received By dpalmer Date 2003-08-04 Time 12:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-07-21 Cont ID  
Sent By alange Date 2003-07-31 Time 15:42 Rev Time 0.75
Received By dpalmer Date 2003-07-21 Time 15:16 Sent To  
Notes
2003-07-21 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE THAT ONLY ONE
 REVISED ELECTRICAL SHEET 5EWAS
 SUBMITTED.
  
 2)NOTE: PLEASE SHOW THE ATTACHMENT FOR
 TRANSFORMERS AS REQUESTED ON ORIG REVIEW
 COMMENTS.250-30
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-23 Cont ID  
Sent By dpalmer Date 2003-06-23 Time 06:50 Rev Time 1.00
Received By dpalmer Date 2003-06-23 Time 06:50 Sent To  
Notes
2003-06-24 00:00:001)NOTE: PLEASE ALSO SEE CLEARANCE REQ`
 MENTS FOR MDP AND TRANSFORMER PER 110-26
2003-06-23 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY AND SHOW CONNECT-
 -ION FOR TRANSFORMERS PER 250-30.
  
 2)NOTE: PLEASE SHOW ALL CONTINOUS LOADS
 @ 125% MIN. (LIGHTING) 215-3/230-42 ETC.
 SHOW LOAD CALCS.220-3,220-10,220-13 ETC
 3)NOTE: PLEASE SHOW SEE MIN SIZING FOR
 EQUIPMENT GROUNDING CONDUCTORS FOR 30A
 OCP. 250-122 SOME SHOWN AS #12`S, AND
 SHOULD BE #10 MIN.
  
 4)NOTE: PLEASE SEE 200A DISCONNECTS FOR
 HA AND TVSS. IN ELECTRICAL ROOM DIAGRAM
 SHOWS 200A DISC'C W/ 200A OCP. HOWEVER
 ELECTRICAL RISER DIAGRAM SHOWS 200A
 DISC'S W/ 125A OCP? PLEASE CORRELATE.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-10-29 Cont ID  
Sent By nmccray Date 2003-10-29 Time 10:35 Rev Time 0.00
Received By nmccray Date 2003-10-29 Time 10:35 Sent To  
Notes
2003-10-29 00:00:00REVISION DATED 10-02-03 OK

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-25 Cont ID  
Sent By mcarsill Date 2003-07-25 Time 15:41 Rev Time 0.00
Received By mcarsill Date 2003-07-25 Time 15:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-07-01 Cont ID  
Sent By mcarsill Date 2003-07-01 Time 07:33 Rev Time 0.00
Received By mcarsill Date 2003-07-01 Time 07:33 Sent To  
Notes
2003-07-01 00:00:001) ONLY ONE EXIT SIGN IS SHOWN OVER AN
 EXTERIOR DOOR. PLEASE EXPLAIN TWO EXITS
 WHEN ONLY ONE IS SHOWN.
  
 2) PLEASE EXPLAIN KIDS GATE AREA.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 15:42 Rev Time 0.00
Received By alange Date 2003-07-31 Time 15:42 Sent To E
Notes
2003-07-31 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 15:36 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 15:36 Sent To  
Notes
2003-07-17 00:00:00COMM BOARD #25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-20 Cont ID  
Sent By shernand Date 2003-06-20 Time 10:34 Rev Time 0.00
Received By shernand Date 2003-06-20 Time 10:34 Sent To  
Notes
2003-06-20 00:00:00COMM BOARD #34

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-07-07 Cont ID  
Sent By pkrauss Date 2003-07-07 Time 09:57 Rev Time 1.00
Received By pkrauss Date 2003-07-07 Time 09:57 Sent To  
Notes
2003-07-07 00:00:00PROVISO:MECHANICAL PERMIT 03061650
  
 1.DUCT SMOKE DETECTOR SHALL BE
 INSTALLEDIN THE SUPPLY DUCT NOT IN
 THE RETURN AS DEPICTED ON PLAN SHEET
 AC-1. 2001 FBC(M) 606.2.1.
  
 2.FAN SHUTDOWN WITH NOTIFICATION
 REQUIRED AT FINAL.2001 FBC(M) 606.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-29 Cont ID  
Sent By kstevens Date 2003-07-29 Time 07:10 Rev Time 1.00
Received By kstevens Date 2003-07-28 Time 16:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-07-10 Cont ID  
Sent By kstevens Date 2003-07-10 Time 13:11 Rev Time 1.00
Received By kstevens Date 2003-07-10 Time 13:11 Sent To  
Notes
2003-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 7 WOMENTS & MENS RESTROOM ELEVAT-
 IONS, W/C SHALL BE 18" FROM CENTERLINE
 OF FIXTURE TO WALL. SHOW ON DETAIL. FIG
 28
 2) SHT 7 MENS RESTROOM ELEVATION, URNAL
 HEIGHT TO COMPLY WITH 11-4.18.2. SHOW ON
 DETAIL.
 3) SHOW CLEAR FLOOR SPACE FOR ALL HDCP
 FIXTURES. 11-4.16.2, 4.18.3, 4.19.3, AND
 4.24.5.
 4) MINIMUM FIXTURE TABLE 403.1 AND SHT
 T PLUMBING FIXTURE CALCULATIONS CALLS
 FOR A DRINKING FOUNTAIN. NOTE SHOWN.
 1 DRINKING FOUNTAIN REQUIRED. ALSO SEE
 SECTION 410.1
 5) SHT 2-P 3/4" WATER LINE TO CHILLER,
 RPZ BACKFLOW REQUIRED.
 6) RPZ BACKFLOW REQUIRED FOR WATER SERV-
 ICE TO SPACE. BACKFLOW SHALL BE LOCATED
 MAXIMUM OF 4' ABOVE FLOOR FOR SERVICE &
 TESTING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692