Plan Review Details - Permit 03060175
Plan Review Stops For Permit 03060175
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-20 Cont ID  
Sent By sthyng Date 2003-10-20 Time 08:01 Rev Time 2.50
Received By sthyng Date 2003-10-20 Time 08:01 Sent To M
Notes
2003-10-20 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 3.)THE SURVEY PROVIDED IS DIFFICULT TO
 READ, BUT IT APPEARS THAT THE EXISTING
 HOUSE IS AT 4.7' FROM THE PROPERTY LINE.
 THE SITE PLAN PREPARED BY THE ARCHITECT
 SHOWS THE HOUSE AT 5'.PLEASE ADDRESS.
  
 4.)SEE PREVIOUS CORRECTION LIST #9;
 IMPACT PROECTION REQUIRED FBC1601.
 PROVIDE TWO COPIES OF PRODUCT APPROVALS
 AND A HURRICANE SHUTTER INSTALLATION
 SCHEDULE, SEE ATTACHED.IF THIS IS NOT
 SUBMITTED BEFORE THE ISSUANCE OF THE
 PERMIT, A SEPARATE PERMIT FOR THIS ITEM
 WILL BE REQUIRED.
  
 5.)PREVIOUS CORRECTION LIST, ITEM #4,
 REQUESTED COMPLIANCE WITH FBC3401.7.1.2
 INCLUDING BEDROOM EMERGENCY EGRESS AND
 SMOKE DETECTORS.THIS APPLIES TO THE
 EXISTING HOUSE.SHOW COMPLIANCE, EITHER
 WITH AN EXISTING FLOOR PLAN OR A
 LETTER WITH A WINDOW SCHEDULE (1 PER
 EXISTING BEDROOM), STATING TYPE OF
 WINDOW AND SIZE.
  
 6.)SEE PREVIOUS CORRECTION LIST, ITEM
 #10.TWO COPIES OF ALL DOCUMENTATION IS
 REQUIRED, INCLUDING ALL PRODUCT
 APPROVALS AND ENERGY CALCS.ANY PRODUCT
 APPROVALS NOT SUBMITTED FOR REVIEW WILL
 REQUIRE A SEPARATE PERMIT (MULLIONS,
 IMPACT PROTECTION, SLIDING GLASS DOOR,
 ROOF).
  
 7.)ITEM 13, NOT ADDRESSED.DOES NOT
 SHOW FIREBLOCKING FBC2305.1.4.
  
 8.)STAIRS TO COMPLY WITH FBC1007.3(1),
 SUM OF TWO RISERS AND A TREAD TO BE AT
 LEAST 24".
  
 9.)PROVIDE A GUARDRAIL DETAIL.
  
 10.) HANDRAIL AND GUARDRAIL TO COMPLY
 WITH FBC1608.2.
  
 11.) A-1, CONNECTOR SCHEDULE, UPLIFT FOR
 CONNECTORS EXCEED MAXIMUM ALLOWED IN THE
 CATALOG.
  
 12.) TO EXPEDITE PLAN REVIEW, CLOUD ALL
 CHANGES (SOME CHANGES WERE CLOUDED, SOME
 WERE NOT).
  
 13.) SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC FBC13-101.2.PROVIDE TWO
 COPIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-17 Cont ID  
Sent By pkrauss Date 2003-06-17 Time 12:21 Rev Time 2.50
Received By sthyng Date 2003-06-17 Time 13:39 Sent To  
Notes
2003-06-17 00:00:00********CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT IS
 REQUIRED TO BE FILED WITH THE CLERK OF
 COURTS BEFORE A PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE ORIGINAL RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 4.)AREA CALCULATIONS SHOULD INCLUDE
 THE EXISTING, PROPOSED, AND NEW TOTAL.
 ADDITIONS OF OVER 25% MUST COMPLY WITH
 FBC 3401.7.1.2.SHOW COMPLIANCE ON
 EXISTING HOUSE IF THE ADDITION IS OVER
 25%; BEDROOM EGRESS, ACCESSIBLE
 BATHROOM, POOL SAFETY, SMOKE DETECTORS.
  
 5.)SPECIFY SPACING, 1-A1.
  
 6.)ENERGY CALCS REQUIRED, FBC13-101.2.
  
 7.)SMOKE DETECTORS REQUIRED,FBC905.2.2
  
 8.)ATTIC ACCESS REQUIRED, FBC2309.6.
  
 9.)IMPACT PROTECTION REQUIRED FBC
 1601.IF SHUTTERS ARE USED, SUBMIT A
 HURRICANE SHUTTER ATTACHMENT SCHEDULE,
 SEE ATTACHED.
  
 10.) SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE WINDOWS, IMPACT
 PROTECTION, MULLIONS, SLIDING GLASS
 DOOR, ROOF COVERING.IF PRODUCT
 APPROVALS ARE NOT SUBMITTED, A SEPARATE
 PERMIT FOR THOSE ITEMS WILL BE REQUIRED.
  
 11.)PROVIDE A GUARDRAIL DETAIL.
  
 12.)PROVIDE A STAIR RAILING AND
 HAND RAIL DETAIL.
  
 13.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, INCLUDING FIREBLOCKING.
  
 14.)THE DOOR BUCK (A2) MUST COMPLY
 WITH FBC 1707.4.4.2.
  
 15.)THE POOL MUST COMPLY WITH THE
 RESIDENTIAL SWIMMING POOL SAFETY ACT
 FS 515.
  
 16.)DRAFTSTOPPING REQUIRED, FBC 705.3.
 PROVIDE A DRAFTSTOP DETAIL AND SHOW
 LOCATIONS ON THE JOIST FRAMING PLAN A1.
  
 17.)SPECIFY SOFFIT VENTING TO COMPLY
 WITH FBC 2309.7.
  
 18.)GABLES ARE TO BE STRUCTURALLY
 CONTINUOUS, FBC 1918.3.1.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-07 Cont ID  
Sent By dpalmer Date 2003-10-07 Time 11:29 Rev Time 1.50
Received By dpalmer Date 2003-10-07 Time 11:26 Sent To P
Notes
2003-10-07 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM,
 200A METER/ MAIN FEEDING 150A PANEL?
  
 2)NOTE: PLEASE SEE TABLE 9 FOR FOR
 CONDUIT SIZING/FILL.
  
 3)NOTE: PLEASE SEE THAT SOME NOTES FROM
 FIRST REVIEW HAVE NOT BEEN ADDRESSED AND
 PLEASE SEE COPY OF FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS.
  
 4)NOTE: PLEASE COMPLETE ELECTRICAL LOADS
 /PANELS/OCP ETC. SOME SHOWN BLANK.215.5
 220
 5)NOTE: PLEASE SEE NOTES 2,3,4,5,7,8
 FROM PREVIOUS REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected].
  
  
 PLEASE INCLUDE ALL LICENSE INFORMATION
 ON TITLE BLOCK AS REQ'D UNDER FS AND FAC
 481 AND 61G1-16.004

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-10 Cont ID  
Sent By csiegber Date 2003-09-30 Time 08:03 Rev Time 1.00
Received By dpalmer Date 2003-06-10 Time 08:46 Sent To P
Notes
2003-06-10 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE MISSING KITCHEN
 ISLAND RECEPTS PER 210-52C-2 & C-5.
  
 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/ GFI PROTECT
 -ED. 210-8-A-6
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUIT(S) PER 210-12
  
 4)NOTE: PLEASE OCP FOR AHU`S, SHOWN ON
 PANEL SCHEDULE AS 2-POLE 50'S AND SHOWN
 ON LOAD CALCS AS 5KW?MAX OCP 150%
  
 5)NOTE: PLEASE CLARIFY 50A OCP SHOWN AS
 TRIP FOR DISH/DISP.? ALSO SHOWS 20A?
  
 6)NOTE: PLEASE MOVE GFI IN BATH TO
 MEET 210-52D 3' FROM LAV EDGE.
  
 7)NOTE; PLEASE SUBMIT AIC RATINGS FOR
 NEW EQUIPMENT BEING INSTALLED FOR
 SERVICE.110-9/215-5
  
 8)NOTE: PLEASE SEE MISSING SD`S IN/OUT
 BEDROOMS AND ON EACH LEVEL OF MULTI-
 -LEVEL. NFPA-72 8-1.4.2
  
 9)NOTE: PLEASE CLARIFY GROUNDING/BONDING
 SIZE OF CONDUCTOR TO COLD WATER PIPE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-30 Cont ID  
Sent By sgraham Date 2003-11-04 Time 11:32 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 08:02 Sent To E
Notes
2003-09-30 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-06 Cont ID  
Sent By shernand Date 2003-06-06 Time 14:50 Rev Time 0.00
Received By shernand Date 2003-06-06 Time 14:50 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-04 Cont ID  
Sent By sgraham Date 2003-06-06 Time 12:11 Rev Time 0.00
Received By shernand Date 2003-06-04 Time 14:19 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-10-20 Cont ID  
Sent By sthyng Date 2003-10-20 Time 10:07 Rev Time 0.25
Received By pkrauss Date 2003-10-16 Time 12:16 Sent To B
Notes
2003-10-16 00:00:00DENIED:
 ONLY ONE SET OF ENERGY CALCULATIONS
 SUBMITTED.NO MECHANICAL PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-06-16 Cont ID  
Sent By jleech Date 2003-10-14 Time 19:51 Rev Time 0.30
Received By pkrauss Date 2003-06-16 Time 11:08 Sent To B
Notes
2003-06-16 00:00:00DENIED:MECHANICAL PERMIT 03060273
  
 1.PLEASE PROVIDE ENERGY AND MANUAL J
 CALCULATIONS FOR THE ADDITION. 2001 FBC
 CHAPTER 13 101.2.2 & SUB-CHAPTER 6
  
 2.PROVIDE INFORMATION ON THE A/C
 EQUIPMENT - MODEL #, BTU OF THE AHU, KW
 OF THE HEAT STRIP, AND SEER OF THE
 CONDENSING UNIT.
  
 3.INDICATE LOCATION OF CONDENSING
 UNIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-14 Cont ID  
Sent By jleech Date 2003-10-14 Time 19:50 Rev Time 0.25
Received By jleech Date 2003-10-14 Time 19:50 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-10 Cont ID  
Sent By dpalmer Date 2003-10-07 Time 11:43 Rev Time 0.33
Received By kstevens Date 2003-06-10 Time 12:41 Sent To M
Notes
2003-06-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A-2 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. TUB & SHOWER
 NOT VENTED PROPERLY. (TABLE 906.1)
 ISLAND VENT OR AIR ADMITTENCE VALVE REQ-
 UIRED FOR SALAD SINK. TUB & SHOWER SHALL
 NOT DRAIN INTO A HORIZONTAL TEE. (TABLE
 706.3). LAVS SHALL NOT BE DRAINED TO A
 CROSS FITTING. (THEY ARE NOT BACK TO
 BACK). SEE RED LINE CHANGES ON PLANS.
 PLEASE MAKE CORRECTIONS AND RESUBMIT
 PLANS FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-04 Cont ID  
Sent By shernand Date 2003-06-04 Time 14:20 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***