| Plan Review Stops For Permit 03060175 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-10-20 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-10-20 |
Time |
08:01 |
Rev Time |
2.50 |
| Received By |
sthyng |
Date |
2003-10-20 |
Time |
08:01 |
Sent To |
M |
|
| Notes |
| 2003-10-20 00:00:00 | *****CORRECTIONS***** | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE | | | A PERMIT CAN BE ISSUED. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.)THE SURVEY PROVIDED IS DIFFICULT TO | | | READ, BUT IT APPEARS THAT THE EXISTING | | | HOUSE IS AT 4.7' FROM THE PROPERTY LINE. | | | THE SITE PLAN PREPARED BY THE ARCHITECT | | | SHOWS THE HOUSE AT 5'.PLEASE ADDRESS. | | | | | | 4.)SEE PREVIOUS CORRECTION LIST #9; | | | IMPACT PROECTION REQUIRED FBC1601. | | | PROVIDE TWO COPIES OF PRODUCT APPROVALS | | | AND A HURRICANE SHUTTER INSTALLATION | | | SCHEDULE, SEE ATTACHED.IF THIS IS NOT | | | SUBMITTED BEFORE THE ISSUANCE OF THE | | | PERMIT, A SEPARATE PERMIT FOR THIS ITEM | | | WILL BE REQUIRED. | | | | | | 5.)PREVIOUS CORRECTION LIST, ITEM #4, | | | REQUESTED COMPLIANCE WITH FBC3401.7.1.2 | | | INCLUDING BEDROOM EMERGENCY EGRESS AND | | | SMOKE DETECTORS.THIS APPLIES TO THE | | | EXISTING HOUSE.SHOW COMPLIANCE, EITHER | | | WITH AN EXISTING FLOOR PLAN OR A | | | LETTER WITH A WINDOW SCHEDULE (1 PER | | | EXISTING BEDROOM), STATING TYPE OF | | | WINDOW AND SIZE. | | | | | | 6.)SEE PREVIOUS CORRECTION LIST, ITEM | | | #10.TWO COPIES OF ALL DOCUMENTATION IS | | | REQUIRED, INCLUDING ALL PRODUCT | | | APPROVALS AND ENERGY CALCS.ANY PRODUCT | | | APPROVALS NOT SUBMITTED FOR REVIEW WILL | | | REQUIRE A SEPARATE PERMIT (MULLIONS, | | | IMPACT PROTECTION, SLIDING GLASS DOOR, | | | ROOF). | | | | | | 7.)ITEM 13, NOT ADDRESSED.DOES NOT | | | SHOW FIREBLOCKING FBC2305.1.4. | | | | | | 8.)STAIRS TO COMPLY WITH FBC1007.3(1), | | | SUM OF TWO RISERS AND A TREAD TO BE AT | | | LEAST 24". | | | | | | 9.)PROVIDE A GUARDRAIL DETAIL. | | | | | | 10.) HANDRAIL AND GUARDRAIL TO COMPLY | | | WITH FBC1608.2. | | | | | | 11.) A-1, CONNECTOR SCHEDULE, UPLIFT FOR | | | CONNECTORS EXCEED MAXIMUM ALLOWED IN THE | | | CATALOG. | | | | | | 12.) TO EXPEDITE PLAN REVIEW, CLOUD ALL | | | CHANGES (SOME CHANGES WERE CLOUDED, SOME | | | WERE NOT). | | | | | | 13.) SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC FBC13-101.2.PROVIDE TWO | | | COPIES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-06-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-06-17 |
Time |
12:21 |
Rev Time |
2.50 |
| Received By |
sthyng |
Date |
2003-06-17 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2003-06-17 00:00:00 | ********CORRECTIONS******* | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)A NOTICE OF COMMENCEMENT IS | | | REQUIRED TO BE FILED WITH THE CLERK OF | | | COURTS BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE ORIGINAL RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 3.)PROVIDE A SURVEY FOR THIS PROPERTY. | | | | | | 4.)AREA CALCULATIONS SHOULD INCLUDE | | | THE EXISTING, PROPOSED, AND NEW TOTAL. | | | ADDITIONS OF OVER 25% MUST COMPLY WITH | | | FBC 3401.7.1.2.SHOW COMPLIANCE ON | | | EXISTING HOUSE IF THE ADDITION IS OVER | | | 25%; BEDROOM EGRESS, ACCESSIBLE | | | BATHROOM, POOL SAFETY, SMOKE DETECTORS. | | | | | | 5.)SPECIFY SPACING, 1-A1. | | | | | | 6.)ENERGY CALCS REQUIRED, FBC13-101.2. | | | | | | 7.)SMOKE DETECTORS REQUIRED,FBC905.2.2 | | | | | | 8.)ATTIC ACCESS REQUIRED, FBC2309.6. | | | | | | 9.)IMPACT PROTECTION REQUIRED FBC | | | 1601.IF SHUTTERS ARE USED, SUBMIT A | | | HURRICANE SHUTTER ATTACHMENT SCHEDULE, | | | SEE ATTACHED. | | | | | | 10.) SUBMIT TWO COPIES OF PRODUCT | | | APPROVALS FOR THE WINDOWS, IMPACT | | | PROTECTION, MULLIONS, SLIDING GLASS | | | DOOR, ROOF COVERING.IF PRODUCT | | | APPROVALS ARE NOT SUBMITTED, A SEPARATE | | | PERMIT FOR THOSE ITEMS WILL BE REQUIRED. | | | | | | 11.)PROVIDE A GUARDRAIL DETAIL. | | | | | | 12.)PROVIDE A STAIR RAILING AND | | | HAND RAIL DETAIL. | | | | | | 13.)PROVIDE A STRUCTURAL DETAIL FOR | | | THE STAIRS, INCLUDING FIREBLOCKING. | | | | | | 14.)THE DOOR BUCK (A2) MUST COMPLY | | | WITH FBC 1707.4.4.2. | | | | | | 15.)THE POOL MUST COMPLY WITH THE | | | RESIDENTIAL SWIMMING POOL SAFETY ACT | | | FS 515. | | | | | | 16.)DRAFTSTOPPING REQUIRED, FBC 705.3. | | | PROVIDE A DRAFTSTOP DETAIL AND SHOW | | | LOCATIONS ON THE JOIST FRAMING PLAN A1. | | | | | | 17.)SPECIFY SOFFIT VENTING TO COMPLY | | | WITH FBC 2309.7. | | | | | | 18.)GABLES ARE TO BE STRUCTURALLY | | | CONTINUOUS, FBC 1918.3.1. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-10-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-07 |
Time |
11:29 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2003-10-07 |
Time |
11:26 |
Sent To |
P |
|
| Notes |
| 2003-10-07 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM, | | | 200A METER/ MAIN FEEDING 150A PANEL? | | | | | | 2)NOTE: PLEASE SEE TABLE 9 FOR FOR | | | CONDUIT SIZING/FILL. | | | | | | 3)NOTE: PLEASE SEE THAT SOME NOTES FROM | | | FIRST REVIEW HAVE NOT BEEN ADDRESSED AND | | | PLEASE SEE COPY OF FS 553.80(2)(B) WITH | | | RESPECT TO DESIGN PROFESSIONALS. | | | | | | 4)NOTE: PLEASE COMPLETE ELECTRICAL LOADS | | | /PANELS/OCP ETC. SOME SHOWN BLANK.215.5 | | | 220 | | | 5)NOTE: PLEASE SEE NOTES 2,3,4,5,7,8 | | | FROM PREVIOUS REVIEW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected]. | | | | | | | | | PLEASE INCLUDE ALL LICENSE INFORMATION | | | ON TITLE BLOCK AS REQ'D UNDER FS AND FAC | | | 481 AND 61G1-16.004 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-06-10 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-30 |
Time |
08:03 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-06-10 |
Time |
08:46 |
Sent To |
P |
|
| Notes |
| 2003-06-10 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE MISSING KITCHEN | | | ISLAND RECEPTS PER 210-52C-2 & C-5. | | | | | | 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/ GFI PROTECT | | | -ED. 210-8-A-6 | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUIT(S) PER 210-12 | | | | | | 4)NOTE: PLEASE OCP FOR AHU`S, SHOWN ON | | | PANEL SCHEDULE AS 2-POLE 50'S AND SHOWN | | | ON LOAD CALCS AS 5KW?MAX OCP 150% | | | | | | 5)NOTE: PLEASE CLARIFY 50A OCP SHOWN AS | | | TRIP FOR DISH/DISP.? ALSO SHOWS 20A? | | | | | | 6)NOTE: PLEASE MOVE GFI IN BATH TO | | | MEET 210-52D 3' FROM LAV EDGE. | | | | | | 7)NOTE; PLEASE SUBMIT AIC RATINGS FOR | | | NEW EQUIPMENT BEING INSTALLED FOR | | | SERVICE.110-9/215-5 | | | | | | 8)NOTE: PLEASE SEE MISSING SD`S IN/OUT | | | BEDROOMS AND ON EACH LEVEL OF MULTI- | | | -LEVEL. NFPA-72 8-1.4.2 | | | | | | 9)NOTE: PLEASE CLARIFY GROUNDING/BONDING | | | SIZE OF CONDUCTOR TO COLD WATER PIPE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW.IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-09-30 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2003-11-04 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-30 |
Time |
08:02 |
Sent To |
E |
|
| Notes |
| 2003-09-30 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-06-06 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-06 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-06 |
Time |
14:50 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-06-04 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2003-06-06 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-04 |
Time |
14:19 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2003-10-20 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-10-20 |
Time |
10:07 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2003-10-16 |
Time |
12:16 |
Sent To |
B |
|
| Notes |
| 2003-10-16 00:00:00 | DENIED: | | | ONLY ONE SET OF ENERGY CALCULATIONS | | | SUBMITTED.NO MECHANICAL PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-06-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2003-10-14 |
Time |
19:51 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-06-16 |
Time |
11:08 |
Sent To |
B |
|
| Notes |
| 2003-06-16 00:00:00 | DENIED:MECHANICAL PERMIT 03060273 | | | | | | 1.PLEASE PROVIDE ENERGY AND MANUAL J | | | CALCULATIONS FOR THE ADDITION. 2001 FBC | | | CHAPTER 13 101.2.2 & SUB-CHAPTER 6 | | | | | | 2.PROVIDE INFORMATION ON THE A/C | | | EQUIPMENT - MODEL #, BTU OF THE AHU, KW | | | OF THE HEAT STRIP, AND SEER OF THE | | | CONDENSING UNIT. | | | | | | 3.INDICATE LOCATION OF CONDENSING | | | UNIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-10-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2003-10-14 |
Time |
19:50 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2003-10-14 |
Time |
19:50 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-06-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-07 |
Time |
11:43 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-06-10 |
Time |
12:41 |
Sent To |
M |
|
| Notes |
| 2003-06-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT A-2 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. TUB & SHOWER | | | NOT VENTED PROPERLY. (TABLE 906.1) | | | ISLAND VENT OR AIR ADMITTENCE VALVE REQ- | | | UIRED FOR SALAD SINK. TUB & SHOWER SHALL | | | NOT DRAIN INTO A HORIZONTAL TEE. (TABLE | | | 706.3). LAVS SHALL NOT BE DRAINED TO A | | | CROSS FITTING. (THEY ARE NOT BACK TO | | | BACK). SEE RED LINE CHANGES ON PLANS. | | | PLEASE MAKE CORRECTIONS AND RESUBMIT | | | PLANS FOR REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-11-04 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-04 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
|
|