Plan Review Details - Permit 03060172
Plan Review Stops For Permit 03060172
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-17 Cont ID  
Sent By lsmith Date 2003-06-17 Time 11:16 Rev Time 0.75
Received By lsmith Date 2003-06-17 Time 11:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-09 Cont ID  
Sent By shernand Date 2003-06-04 Time 09:43 Rev Time 0.50
Received By lsmith Date 2003-06-09 Time 10:02 Sent To  
Notes
2003-06-09 00:00:00*********FAILED***********
  
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713
  
 1. SUBMIT DRAWING OF HOUSE SHOWING
 LOCATION OF WINDOWS BEING REPLACED.
 NOTE ALL BEDROOMS.SIZES MUST BE SHOWN
 TO ASSURE COMPLIANCE WITH MEANS OF
 EGRESS IN SLEEPING ROOMS.
 2. IF 2 WINDOWS ARE MULLED TOGETHER IN
 AN OPENING PRODUCT APPROVALS FOR
 MULLINS ARE REQUIRED.
 3. SCHEDULE OF ATTACHMENTS FOR STORM
 PANELS REQUIRED SHOWING TYPE OF ANCHORS
 AND WHAT TYPE WALLS PANELS ARE BEING
 ATTACHED TO.(IE WOOD, CBS, ETC)