Plan Review Details - Permit 03060087
Plan Review Stops For Permit 03060087
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-01-02 Cont ID  
Sent By shill Date 2004-01-02 Time 07:43 Rev Time 1.00
Received By shill Date 2004-01-02 Time 07:43 Sent To  
Notes
2004-01-02 00:00:00PROVISO - SEP PERMIT SHUTTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-20 Cont ID  
Sent By csiegber Date 2003-12-30 Time 15:54 Rev Time 1.00
Received By sthyng Date 2003-11-20 Time 08:58 Sent To E
Notes
2003-11-20 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)THE NOTICE OF COMMENCEMENT
 SUBMITTED WAS FOR 1017 SELKIRK (WRONG
 ADDRESS).
  
 3.)SEE PREVIOUS LIST, ITEM #4.THE
 INSULATION CANNOT BE R4.0 WHEN THE
 ENERGY CALC SPECIFIES A MINIMUM OF R4.2.
  
 4.)SEE PREVIOUS LIST, ITEM #9, SHEET
 2 STILL REFERS TO "UNLOAD DESIGN".
  
 5.)SEE PREVIOUS LIST, ITEM #12,
 CONNECTOR SCHEDULE HAS AN UPLIFT FOR
 TWO STRAPS THAT IS LESS THAN THE UPLIFT
 ON THE PLAN FOR THAT CONNECTOR.REVISE
 THE CONNECTOR SCHEDULE UPLIFT.
  
 6.)SEE PREVIOUS LIST, ITEM #13,
 PROVIDE A WINDOW & DOOR BUCK ATTACHMENT
 DETAIL.
  
 7.)SEE PREVIOUS LIST, ITEM #16,
 PROVIDE TWO COPIES OF THE WINDOW
 MULLION PRODUCT APPROVAL.
  
 8.)ADDITIONAL FEES DUE, $364.43
 (RADON AND VALUE ADJUSTMENT), SEE
 ATTACHED BZ233275.
  
 9.)SEE PREVIOUS LIST.WHEN
 RESUBMITTING, ALL CHANGES MUST BE
 CLEARLY MARKED WITH CLOUDS OR TRIANGLES.
  
 10.) THE CHANGES TO A SEALED PLAN MUST
 BE INITIALED BY THE ENGINEER.
  
 11.)THE ENGINEER'S LICENSE NUMBER
 IS REQUIRED TO BE ON EACH SHEET, FAC
 61G15-23.002.
  
 12.)SEE ATTACHED NOTICE REGARDING
 FS553.80(2)(B).
  
 13.)PROVIDE A KEY PLAN AND HURRICANE
 SHUTTER INSTALLATION SCHEDULE (SEE
 ATTACHED).
  
 14.)IDENTIFY THE JOB ON THE TITLE
 BLOCK (ADDRESS OR LOT NUMBER).
  
 15.)THERE IS AN "EXTENDED WALL".
 PROVIDE A DETAIL.A WALL IS NOT
 "DECORATION PURPOSE ONLY", A WALL IS
 ALWAYS A STRUCTURAL ELEMENT.SHOW ON
 THE FOUNDATION PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-09 Cont ID  
Sent By hmoser Date 2003-11-18 Time 16:49 Rev Time 2.50
Received By sthyng Date 2003-07-09 Time 09:31 Sent To  
Notes
2003-07-09 00:00:00******CORRECTIONS******
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)BEFORE A PERMIT CAN BE ISSUED, A
 NOTICE OF COMMENCEMENT MUST BE FILED
 WITH THE CLERK OF COURTS.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE ORIGINAL RECEIPT
 ATTACHED TO THE APPLICATION.233-5025
  
 4.)THE WALL SECTION SHOWS R4
 INSULATION, THE ENERGY CALC SPECIFIES
 A MINIMUM OF 4.2.
  
 5.)SPECIFY THE SPACING OF THE SOFFIT
 VENTS TO COMPLY WITH FBC2309.7.
  
 6.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC13-103.1.2.
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 8.)ON THE WALL SECTION, THE BOTTOM
 OF FOUNDATION SHALL EXTEND NO LESS THAN
 12 INCHES BELOW FINISH GRADE,
 FBC1804.1.3.
  
 9.)SHEET 2 REFERS TO "BUILDING CODE
 UNLOAD DESIGN CERTIFICATION".REVISE.
  
 10.) SHEET 2, WIND LOAD, SHOWS A MEAN
 ROOF HEIGHT OF 14'2".BUILDING HEIGHT
 IS SHOWN AS 60'.REVISE.
  
 11.)SHEET 2, CONNECTOR SCHEDULE, #1,
 THE NAILING FOR HETAL 16 IS INCONSISTENT
 WITH THE MINIMUM NUMBER OF NAILS
 REQUIRED TO OBTAIN THE 1365 UPLIFT.
 REFER TO THE SIMPSON 2003 CATALOG.
  
 12.)SHEET 2, CONNECTOR SCHEDULE, #2,
 TWO STRAPS ARE SPECIFIED BUT THE UPLIFT
 NUMBER REMAINED THE SAME AS FOR ONE
 STRAP.REVISE.
  
 13.)PROVIDE A WINDOW & DOOR BUCK
 ATTACHMENT SCHEDULE.
  
 14.)PRODUCT APPROVALS WERE SUBMITTED
 FOR SLIDING GLASS DOORS.THERE ARE
 NONE ON THE PLAN.
  
 15.)THE PRODUCT APPROVALS FOR THE
 SINGLE HUNG WINDOW AND THE SHINGLES
 ARE EXPIRED.PROVIDE TWO LEGIBLE COPIES
 OF CURRENT PRODUCT APPROVALS.
  
 16.)PROVIDE TWO COPIES OF THE WINDOW
 MULLION PRODUCT APPROVAL.
  
 17.)DADE COUNTY NOAS ARE AVAILABLE AT:
 WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING
 CODE, PRODUCT CONTROL).
  
 18.)ADDITIONAL FEES DUE, $364.43
 (VALUE ADJUSTMENT).
  
 WHEN RESUBMITTING, ALL CHANGES MUST BE
 CLEARLY MARKED WITH CLOUDS OR TRIANGLES.
 SUBMIT ONE COPY OF THE OLD SHEETS WITH
 THE NEW PLANS.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-06-19 Cont ID  
Sent By sthyng Date 2003-11-20 Time 11:52 Rev Time 0.50
Received By btrobaug Date 2003-06-19 Time 16:50 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-11-16 Cont ID  
Sent By mjacobs Date 2004-11-16 Time 13:42 Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 13:42 Sent To P
Notes
2004-11-16 00:00:00SENT TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 14:26 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 14:26 Sent To P
Notes
2004-10-28 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 15:54 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 15:54 Sent To B
Notes
2003-12-30 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 10:57 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 10:57 Sent To M
Notes
2003-11-06 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-06-04 Time 15:28 Rev Time 0.00
Received By shernand Date 2003-06-04 Time 15:28 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-03 Cont ID  
Sent By shernand Date 2003-06-03 Time 10:14 Rev Time 0.00
Received By shernand Date 2003-06-03 Time 10:14 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-18 Cont ID  
Sent By hmoser Date 2003-11-18 Time 16:36 Rev Time 0.50
Received By hmoser Date 2003-11-18 Time 16:36 Sent To B
Notes
2003-11-18 00:00:00PASS PRIVISO
 NEED A COPY OF THE PAGE FROM THE A.R.I.
 MANUAL WITH THE SEER OF THE EQUIPMENT
 FOR FINAL INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-11-18 Cont ID  
Sent By csiegber Date 2003-11-06 Time 10:57 Rev Time 0.25
Received By hmoser Date 2003-06-23 Time 13:12 Sent To B
Notes
2003-06-24 00:00:00DENIED:
  
 ENERGY CALCULATIONS INDICATE 11 SEER AND
 THE EQUIPMENT SCHEDULE INDICATES A 10
 SEER UNIT.PLEASE CORRECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-30 Cont ID  
Sent By kstevens Date 2004-11-30 Time 18:02 Rev Time 0.33
Received By kstevens Date 2004-11-30 Time 18:02 Sent To  
Notes
2004-11-30 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-11-03 Cont ID  
Sent By kstevens Date 2004-11-03 Time 18:39 Rev Time 0.50
Received By kstevens Date 2004-11-03 Time 18:39 Sent To  
Notes
2004-11-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) REVISIONS TO A SIGNED/SEALED/DATED
 SET OF PLANS SHALL BE SIGNED/SEALED/ AND
 DATED BY THE ENGINEER OF RECORD. ALL
 TITLE BLOCK INFORMATION SHALL BE ON
 REVISIONS. SECTION 104.2.2
 2) SHOW ALL PIPE SIZES ON REVISION.
 SECTION 104.2.1
 3) REMOVE ALL EXTRA PIPE (DEAD ENDS) ON
 RISER DIAGRAM. SEE RED LINES.
 4) CLEAR UP AREA OF RISER THAT IS FADED
 AND HARD TO READ. SECTION 104.2.1
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-21 Cont ID  
Sent By csiegber Date 2004-10-28 Time 14:26 Rev Time 0.33
Received By jleech Date 2003-06-21 Time 13:29 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-06-03 Time 10:14 Rev Time 1.00
Received By mmclean Date   Time   Sent To E
Notes
***NONE***