Plan Review Details - Permit 03060080
Plan Review Stops For Permit 03060080
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-03 Cont ID  
Sent By shill Date 2004-03-03 Time 14:46 Rev Time 1.00
Received By shill Date 2004-03-03 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-01-22 Cont ID  
Sent By pkrauss Date 2004-03-01 Time 13:52 Rev Time 1.00
Received By shill Date 2004-01-22 Time 13:18 Sent To Z
Notes
2004-01-22 00:00:00****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)SEE PREVIOUS LIST, ITEM #3, SHEET
 2 REFERS TO "BUILDING UNLOAD CERTIFICA-
 TION", REVISE.
  
 3.)SEE PREVIOUS LIST, #7.PROVIDE
 TWO COPIES OF COMPLETE, CURRENT NOAS
 FOR THE DOOR.IF NOT SUBMITTED, A
 SEPARATE PERMIT WILL BE REQUIRED.
  
 4.)SEE PREVIOUS LIST, ITEM #16.IF
 AN INSTALLATION SCHEDULE IS NOT
 SUBMITTED, A SEPARATE PERMIT FOR
 SHUTTERS WILL BE REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-20 Cont ID  
Sent By btrobaug Date 2004-01-22 Time 10:50 Rev Time 1.00
Received By sthyng Date 2003-11-19 Time 15:50 Sent To E
Notes
2003-11-19 00:00:00******CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)SEE PREVIOUS LIST, ITEM #4.YOU
 CANNOT SPECIFY R4 OR R4.2 WHEN THE
 ENERGY CALCS REQUIRE A MINIMUM OF 4.2.
  
 3.)SEE PREVIOUS LIST, ITEM #9, NOT
 ADDRESSED.SHEET 2 REFERS TO "BUILDING
 UNLOAD CERTIFICATION", REVISE.
  
 4.)SEE PREVIOUS LIST, ITEM #12.THE
 CONNECTOR SCHEDULE, SHEET 2, SPECIFIES
 TWO STRAPS BUT UPLIFT SHOWS THE SAME
 AS ONE.ON THE FRAMING PLAN, CONNECTOR
 TWO IS SPECIFIED WITH AN UPLIFT WHICH
 EXCEEDS THE TABLE.REVISE THE UPLIFT.
  
 5.)SEE PREVIOUS LIST, ITEM #13.
 PROVIDE A WINDOW AND DOOR BUCK
 ATTACHMENT DETAIL.
  
 6.)SEE PREVIOUS LIST, ITEM #16.
 PROVIDE TWO COPIES OF THE WINDOW
 MULLION PRODUCT APPROVAL.THE FLOOR
 PLAN SHOWS THE WINDOW OPENING AS A
 SINGLE, SCHEDULE SHOWS AS A "PAIR".
  
 7.)THE DOOR PRODUCT APPROVALS ARE
 MISSING THE TECHNICAL SHEETS.
  
 8.)ADDITIONAL FEES DUE, $364.43
 (VALUE ADJUSTMENT AND RADON), SEE
 ATTACHED BZ233274.
  
 9.)SEE PREVIOUS LIST.ALL CHANGES
 TO THE PLAN ARE TO BE CLEARLY MARKED
 WITH CLOUDS OR TRIANGLES.
  
 10.) THERE IS AN "EXTENDED WALL" ON THE
 ELEVATION.PROVIDE A DETAIL AND SHOW
 THE WALL ON THE FOUNDATION PLAN.
  
 11.) CHANGES MADE TO A SEALED PLAN ARE
 TO BE INITIALED BY THE ENGINEER.
  
 12.) SUBMIT A SECOND COPY OF THE SOILS
 REPORT.
  
 13.) THE APPROVED ZONING SURVEY IS
 MISSING FROM THE PACKAGE.SUBMIT, IF
 AVAILABLE.
  
 14.)IDENTIFY THE JOB ON THE TITLE
 BLOCK BY EITHER ADDRESS OR LOT NUMBER.
  
 15.)SEE ATTACHED NOTICE IN REGARDS
 TO FS553.80(2)(B).
  
 16.)PROVIDE A KEY PLAN AND A HURRICANE
 SHUTTER INSTALLATION SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-09 Cont ID  
Sent By hmoser Date 2003-11-18 Time 18:02 Rev Time 3.00
Received By sthyng Date 2003-07-09 Time 07:47 Sent To  
Notes
2003-07-09 00:00:00*******CORRECTIONS*******
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)BEFORE A PERMIT CAN BE ISSUED, A
 NOTICE OF COMMENCEMENT MUST BE FILED
 WITH THE CLERK OF COURTS.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE ORIGINAL RECEIPT
 ATTACHED TO THE APPLICATION.233-5025
  
 4.)THE WALL SECTION SHOWS R4
 INSULATION, THE ENERGY CALC SPECIFIES
 A MINIMUM OF 4.2.
  
 5.)SPECIFY THE SPACING OF THE SOFFIT
 VENTS TO COMPLY WITH FBC2309.7.
  
 6.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC 13-103.1.2.
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 8.)ON THE WALL SECTION, THE BOTTOM
 OF FOUNDATION SHALL EXTEND NO LESS THAN
 12 INCHES BELOW FINISH GRADE,
 FBC1804.1.3.
  
 9.) SHEET 2 REFERS TO "BUILDING CODE
 UNLOAD DESIGN CERTIFICATION".REVISE.
  
 10.) SHEET 2, WIND LOAD, SHOWS A MEAN
 ROOF HEIGHT OF 14'2".BUILDING HEIGHT
 IS SHOWN AS 60'.REVISE.
  
 11.)SHEET 2, CONNECTOR SCHEDULE, #1,
 THE NAILING FOR HETAL 16 IS INCONSISTENT
 WITH THE MINIMUM NUMBER OF NAILS
 REQUIRED TO OBTAIN THE 1365 UPLIFT.
 REFER TO THE SIMPSON 2003 CATALOG.
  
 12.)SHEET 2, CONNECTOR SCHEDULE, #2,
 TWO STRAPS ARE SPECIFIED BUT THE UPLIFT
 NUMBER REMAINS THE SAME AS FOR ONE
 STRAP.REVISE.
  
 13.)PROVIDE A WINDOW & DOOR BUCK
 ATTACHMENT SCHEDULE.
  
 14.)PRODUCT APPROVALS WERE SUBMITTED
 FOR SLIDING GLASS DOORS.THERE ARE
 NONE ON THE PLAN.
  
 15.)THE PRODUCT APPROVALS FOR THE
 SINGLE HUNG WINDOW AND THE SHINGLES
 ARE EXPIRED.PROVIDE TWO LEGIBLE
 COPIES OF CURRENT PRODUCT APPROVALS.
  
 16.)PROVIDE TWO COPIES OF THE
 WINDOW MULLION PRODUCT APPROVAL.
  
 17.)DADE COUNTY NOAS ARE AVAILABLE AT:
 WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING
 CODE, PRODUCT CONTROL).
  
 18.)ADDITIONAL FEES DUE, $364.43
 (VALUE ADJUSTMENT).
  
 WHEN RESUBMITTING, ALL CHANGES MUST BE
 CLEARLY MARKED WITH CLOUDS OR TRIANGLES.
 SUBMIT ONE COPY OF THE OLD SHEETS WITH
 THE NEW PLANS.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-02-24 Cont ID  
Sent By btrobaug Date 2004-02-24 Time 14:55 Rev Time 0.50
Received By btrobaug Date 2004-02-24 Time 14:29 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-02-19 Time 11:36 Rev Time 0.50
Received By btrobaug Date 2004-01-22 Time 09:19 Sent To B
Notes
2004-01-22 00:00:00 
 DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PANEL SCHEDULE SHOWS ONE AHU AND
 THEPLANS SHOW TWO,PLEASE CORRELATE.
  
 2} PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
  
 3} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6',12' RULE.SEE FAMILY &
 LIVING ROOMS.
  
 4} SHOW THE LOCATION OF THE SERVICE
 EQUIPMENT ON THE PLAN.SHOW COMPLIANCE
 WITH 230.70 CWPB AMMENDMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-11-12 Cont ID  
Sent By pkrauss Date 2004-01-21 Time 14:57 Rev Time 0.50
Received By btrobaug Date 2003-11-12 Time 13:47 Sent To P
Notes
2003-11-12 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THESE COMMENTS WERE NOT ADDRESSED ON
 THE PLAN.PLEASE CORRECT AND RESUBMIT
 FORREVIEW.
  
 1} PLEASE INDICATE THE SIZE OF THE
 SERVICE CONDUCTORS IN THE RISER(FROM
 WEATHERHEAD TO METER).
  
 2} THE PANEL SCHEDULE ONLY SHOWS ONE AHU
 AND THERE ARE TWO SHOWN ON THE PLAN
 (SEE MECH PLAN).PLEASE REVISE THE LOAD
 CALCULATION AS WELL.
  
 3} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210-52.SEE
 REVIEWED SET OF PLANS IF YOU HAVE
 QUESTIONS REGARDING THIS ARTICLE.
  
 THESE COMMENTS ARE NEW:
  
 SHOW LOCATION OF THE SERVICE EQUIPMENT
 ON THE PLAN. SHOW COMPLIANCE WITH
 230.70 CWPB AMMENDMENTS.
  
 COMPLY WITH 210.52(C)(1) IN THE KITCHEN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-23 Cont ID  
Sent By csiegber Date 2003-11-06 Time 10:58 Rev Time 0.75
Received By btrobaug Date 2003-06-23 Time 06:52 Sent To P
Notes
2003-06-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE INDICATE THE SIZE OF THE
 SERVICE CONDUCTORS IN THE RISER.
  
 2} THE PANEL SCHEDULE ONLY SHOWS ONE
 AHU AND THERE ARE TWO SHOWN ON THE PLAN
 PLEASE REVISE THE LOAD CALCULATION AS
 WELL.
  
 3} THE AHU IS LISTED AT 7KW ON THE
 SCHEDULE AND 5KW ON THE MECHANICAL
 PLAN,PLEASE CORRELATE.
  
 4} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.SEE
 REVIEWED SET OF PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-11-16 Cont ID  
Sent By mjacobs Date 2004-11-16 Time 13:51 Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 13:51 Sent To P
Notes
2004-11-16 00:00:00SENT TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 14:25 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 14:25 Sent To P
Notes
2004-10-28 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 11:36 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 11:36 Sent To E
Notes
2004-02-19 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-01-26 Cont ID  
Sent By shill Date 2004-01-26 Time 17:29 Rev Time 0.00
Received By shill Date 2004-01-26 Time 17:29 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 15:56 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 15:56 Sent To M
Notes
2003-12-30 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 10:58 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 10:58 Sent To E
Notes
2003-11-06 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-19 Cont ID  
Sent By shernand Date 2003-06-19 Time 16:53 Rev Time 0.00
Received By shernand Date 2003-06-19 Time 16:53 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-17 Cont ID  
Sent By mmclean Date 2003-06-19 Time 12:28 Rev Time 0.00
Received By shernand Date 2003-06-17 Time 15:23 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-03 Cont ID  
Sent By shernand Date 2003-06-03 Time 10:14 Rev Time 0.00
Received By shernand Date 2003-06-03 Time 10:14 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-03-01 Cont ID  
Sent By pkrauss Date 2004-03-01 Time 13:52 Rev Time 0.33
Received By pkrauss Date 2004-03-01 Time 13:42 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-01-28 Cont ID  
Sent By kstevens Date 2004-02-27 Time 18:06 Rev Time 0.10
Received By pkrauss Date 2004-01-28 Time 12:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2004-01-21 Cont ID  
Sent By shill Date 2004-01-26 Time 17:29 Rev Time 0.25
Received By pkrauss Date 2004-01-21 Time 14:56 Sent To E
Notes
2004-01-21 00:00:00PLANS HAVE NOT CHANGED EQUIPMENT SEER #
 CARLOS TO FAX EQUIPMENT INFORMATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-14 Cont ID  
Sent By csiegber Date 2003-12-30 Time 15:56 Rev Time 0.50
Received By hmoser Date 2003-11-18 Time 17:56 Sent To B
Notes
2003-11-18 00:00:00PASS PRIVISO
 NEED A COPY OF ARI PAGE SHOWING
 EQUIPMENT SEER AT FINAL INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-14 Cont ID  
Sent By btrobaug Date 2003-11-12 Time 15:29 Rev Time 0.25
Received By hmoser Date 2003-07-02 Time 07:04 Sent To B
Notes
2003-07-02 00:00:00DENIED:
  
 EQUIPMENT LISTED ON PLAN SHEET 3 DOES
 NOT MATCH THE ENERGY CALCULATIONS
 SUBMITTED.PLEASE REVISE.DUCT LAYOUT
 OKAY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-11-30 Cont ID  
Sent By kstevens Date 2004-11-30 Time 18:00 Rev Time 0.33
Received By kstevens Date 2004-11-30 Time 18:00 Sent To  
Notes
2004-11-30 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-11-03 Cont ID  
Sent By kstevens Date 2004-11-03 Time 18:05 Rev Time 0.50
Received By kstevens Date 2004-11-03 Time 18:05 Sent To  
Notes
2004-11-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) REVISIONS TO A SIGNED, SEALED, AND
 DATED PLANS SHALL BE SIGNED, SEALED, AND
 DATED BY THE ENGINEER OF RECORD. SECTION
 104.2.2
 2) SHOW ALL PIPE SIZES ON REVISION.
 SECTION 104.2.1
 3) REMOVE ALL EXCESS PIPING FROM THE
 RISER DIAGRAM. (SEE RED LINE AREAS)
 SECTION 104.2.1
 4) CLEANOUT AT WASH MACHINE SHALL BE
 LOCATED 4' ABOVE THE FLOOR FOR ACCESS.
 SECTION 708.10
  
 (SEE RED LINES AND CIRCLES ON SANT.
 RISER DIAGRAM SHOWING CORRECTIONS TO BE
 MADE. CORRECT - SIGN/SEAL/DATE
 REVISION,
 AND MAKE SURE TITLE BLOCK WITH ALL
 REQUIRED INFORMATION IS ON REVISION)
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-10-28 Time 14:25 Rev Time 0.50
Received By kstevens Date 2004-02-27 Time 18:06 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-23 Cont ID  
Sent By btrobaug Date 2004-02-24 Time 14:55 Rev Time 0.33
Received By kstevens Date 2003-06-23 Time 18:04 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-06-19 Cont ID  
Sent By shill Date 2004-01-22 Time 13:45 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-06-17 Time 15:23 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-06-04 00:00:006/4/03 DENIED, NEED A CLEAN COPY OF
 SURVEY (2) CALL CONTR MM


Account Summary | Usage Policy | Privacy Policy