Plan Review Details - Permit 03060041
Plan Review Stops For Permit 03060041
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-07-02 Cont ID  
Sent By hpiskura Date 2003-07-02 Time 12:54 Rev Time 0.00
Received By hpiskura Date 2003-07-02 Time 12:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-06-16 Cont ID  
Sent By dpalmer Date 2003-06-16 Time 09:38 Rev Time 0.50
Received By dpalmer Date 2003-06-16 Time 07:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-06-26 Cont ID  
Sent By mcarsill Date 2003-06-26 Time 16:31 Rev Time 0.00
Received By mcarsill Date 2003-06-26 Time 16:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-27 Cont ID  
Sent By csiegber Date 2003-10-27 Time 14:55 Rev Time 0.00
Received By csiegber Date 2003-10-27 Time 14:55 Sent To M
Notes
2003-10-27 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-15 Cont ID  
Sent By shernand Date 2003-07-15 Time 13:14 Rev Time 0.00
Received By shernand Date 2003-07-15 Time 13:14 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-06-02 Cont ID  
Sent By shernand Date 2003-06-02 Time 16:47 Rev Time 0.00
Received By shernand Date 2003-06-02 Time 16:47 Sent To  
Notes
2003-06-02 00:00:00COMM BOARD #64

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-10-30 Cont ID  
Sent By pkrauss Date 2003-10-30 Time 16:06 Rev Time 0.45
Received By pkrauss Date 2003-10-30 Time 16:06 Sent To  
Notes
2003-10-30 00:00:00PROVISO:
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3(AUXILIARY DRAIN PAN)

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-19 Cont ID  
Sent By csiegber Date 2003-10-27 Time 14:55 Rev Time 0.30
Received By pkrauss Date 2003-07-19 Time 08:32 Sent To  
Notes
2003-07-19 00:00:00PROVISO:
 NOTES DATED 6/26/03 BY HAROLD MOSER
 1.HYDRONIC PIPING SYSTEMS SHALL BE
 TESTED HYDRONICALLY AT ONE-HALF TIMES
 THE MAXIMUM SYSTEM DESIGN PRESSURE, BUT
 NOT LESS THAN 100 PSI.FROM RISER TO
 A/C #1 & 2.
 2.HAVE PIPE DIAGRAM WITH PLANS WITH
 PLANS.
 3.HAVE EQUIPMENT SPECIFICATION WITH
 PLANS.
  
 NOTES FROM PATTY KRAUSS 7-19-03
 1.PLAN SHEET M-1 INDICATES "PACKAGE
 UNITS".PLEASE CLARIFY, ARE UNITS A
 PART OF THE BUILDING A/C A CONDENSER
 WATER SYSTEM?ARE THESE UNITS ACTUALLY
 HEAT PUMPS?
 2.SHOULD UNITS BE HEAT PUMPS, INDICATE
 LOCATION, DUCT SIZE AND MATERIAL OF
 OUTSIDE AIR.
 3.PLEASE NOTE DUCT SMOKE DETECTORS TO
 HAVE NOTIFICATION AS PER NFPA 90A -
 4-4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-26 Cont ID  
Sent By kstevens Date 2003-07-18 Time 17:16 Rev Time 0.50
Received By hmoser Date 2003-06-26 Time 19:54 Sent To  
Notes
2003-06-26 00:00:00PLAN DENIED
 1) HYDRONIC PIPING SYSTEMS SHALL BE
 TESTED HYDRONICALLY AT ONE-HALF TIMES
 THE MAXIMUM SYSTEM DESIGN PRESSURE,
 BUT NOT LESS THAN 100 PSI.FROM RISER
 TO A/C #1&2
 2) HAVE PIPE DIAGRAM WITH PLANS WITH
 PLANS
 3) HAVE EQUIPMENT SPECIFICATION WITH
 PLANS
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-18 Cont ID  
Sent By kstevens Date 2003-07-18 Time 16:49 Rev Time 0.50
Received By kstevens Date 2003-07-18 Time 16:48 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-06-21 Cont ID  
Sent By shernand Date 2003-07-15 Time 13:14 Rev Time 0.50
Received By kstevens Date 2003-06-21 Time 18:03 Sent To  
Notes
2003-06-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) INDICATE OCCUPANCY OF UNIT. MORE
 COMMENTS MAY ARISE DEPENDING ON RESPONSE
 2) PROVIDE A SANITARY AND A WATER RISER
 DIAGRAM.
 3) DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. ALSO SEE SECION 410.1
 4) SUBMIT DETAIL FOR TOILET ROOM PER
 SECTION 11-4.22 AND ALL SUBSECTION.
 WATER CLOSET SHALL BE 18" TO WALL FROM
 CENTER OF FIXTURE PER FIG 28. FIGURES
 30A AND 30E ARE FOR TOILET STALLS NOT
 TOILET ROOMS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692