| 2003-06-27 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT:03060040 |
| | ADD:5101 CARIBBEAN BLVD |
| | CONT: PICERNE CONSTRUCTION |
| | TEL: (407)741-3306 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1)PROVIDE ENERGY CALCULATIONS AND |
| | EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| | AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| | EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| | TION. |
| | |
| | 2)2001 FL BLD CODE, 1005.4: |
| | PROVIDE EMERGENCY EGRESS WINDOWS IN |
| | SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| | OPENING HEIGTH OF 24" AND NET CLEAR |
| | OPENING WIDTH OF 20" AND A NET CLEAR |
| | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| | OPENINGS ARE PERMITTED TO HAVE A NET |
| | CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| | SHALL NOT BE MORE THAN 44 " ABOVE THE |
| | FINISH FLOOR. |
| | |
| | 3)905.2.1 APPROVED SINGLE-STATION OR |
| | MULTIPLE STATION SMOKE DETECTORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH NFPA 72, |
| | CHAPTER 2, WITHIN EVERY DWELLING UNIT |
| | WITHIN AN APARTMENT HOUSE, CONDOMINIMUM, |
| | OR TOWNHOUSE AND EVERY GUEST OR SLEEPING |
| | ROOM IN A MOTEL, HOTEL, OR DORMITORY & |
| | SLEEPING ROOMS IN RESIDENTIAL CARE/ |
| | ASSISTED LIVING OCCUPANCIES. WHERE MORE |
| | THAN ONE DETECTOR IS REQUIRED TO BE |
| | INSTALLED WITHIN INDIVIDUAL DWELLING |
| | UNIT, THE DETECTOR SHALL BE WIRED IN |
| | SUCH A MANNER THAT THE ACTUATION OF ONE |
| | ALARM WILL ACTIVATE ALL THE ALARMS IN |
| | THE INDIVIDUAL UNIT. |
| | |
| | 4)905.2.1 RESIDENTIAL SMOKE ALARMS: |
| | NFPA 72.A-8-1.2.1 IN FAMILY UNITS WITH |
| | MORE THAN ONE BEDROOM AREA OR WITH BED- |
| | ROOMS ON MORE THAN ONE FLOOR, MORE THAN |
| | ONE SMOKE DETECTOR IS REQUIRED. |
| | |
| | 5) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED.MISSING STORM SHUT- |
| | TERS IF WINDOW IS NOT LARGE MISSLE |
| | TESTED. |
| | |
| | 6) 1707.4.4.2 TAPERED BUCKS: |
| | SHALL EXTEND BEYOND THE INTERIOR FACE |
| | OF THE WINDOW OR DOOR FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| | |
| | 7) PROVIDE A FLOOR PLAN,THIS UNIT IS IN |
| | BUILDING (4) IS THE UNIT ON THE GRADE |
| | FLOOR, IF SO FAIR HOUSING APPLIES WHAT |
| | TYPE UNIT IS IT "A" OR "B"? |
| | ALSO IS THE WINDOW BEING REPLACED USING |
| | MISSLE IMPACT GLAZING OR STORM SHUTERS? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)805-6715 |