| 2003-06-25 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03052313 |
| | ADD: 2000-6 AE ISAACS AVE |
| | CONT: PLAN REVIEW |
| | CONTACT PERSON: REGINALDA COX |
| | TEL: (561)573-1131 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | NOTE!!!!!! |
| | THE REQUIREMENTS OF THE FLORIDA ACCESS- |
| | IBILITY ACT MAY NOT REGULATE "CHURCHES" |
| | DEPENDING ON THE ACTIVITY OF THE BUILD- |
| | ING. SS 553.505 (1995) CH. 97-76 FL |
| | LAWS, RELIEVED BUILDINGS USED FOR COMMUN |
| | IAL RELIGIOUS OBSERVENCES FROM THE |
| | ACCESSIBILITY REQUIREMENTS OF THE ACT. |
| | FROM MEMO 8/16/98 ALFRED BRAGG III, |
| | ASSISTANT GENERAL COUNSEL |
| | |
| | IT APPEARS THAT THE DESIGNER IS TRYING |
| | TO MEET THE HANDICAPPED REQUIREMENTS, |
| | IN THIS REVIEW I WILL INDICATE ANY |
| | DISCPENANCIES TO THE FL ACCESSIBILITY |
| | CODE WITH (***) BEFORE THE COMMENT EVEN |
| | THOUGH IT MAY NOT BE ENFORCED. |
| | |
| | ACTION : DENIED |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) PLANS INDICATE 2 HR WALLS SEPERATING |
| | ASSEMBLY AREAS FROM THE EXIT ACCESS |
| | CORRIDORS TABLE 704.2.4 FOR UNSPRINKLER- |
| | ED BUILDINGS INDICATE A 1 HR RATING. |
| | |
| | 3) 1019.7.2 GROUP A OCCUPANCY, EACH DOOR |
| | IN A MEANS OF EGRESS FROM AN AREA OF |
| | GROUP A OCCUPANCY MAY BE PROVIDED WITH A |
| | LATCH OR LOCK ONLY IF IT IS PANIC HARD- |
| | WARE OR FIRE EXIT HARDWARE. |
| | DOORS MISSING PANIC HARDWARE, 101,102, |
| | 105,107,107B, 114 & 114B. |
| | |
| | 4) STAIRS AT DOOR 114B MISSING LANDING |
| | AT DOOR! 1007.4.2 STAIRS SHALL HAVE |
| | FLOORS OR LANDINGS AT DOOR OPENINGS. |
| | |
| | 5)1007.5.2 STAIRWAYS SHALL HAVE HAND- |
| | RAILS ON EACH SIDE.EXTERIOR STAIRS AS |
| | WELL AS INTERIOR. |
| | |
| | 6)1015.2 HEIGHT. GUARDRAILS SHALL |
| | FORM A VERTICAL PROTECTIVE BARRIER NOT |
| | LESS THAN 42" HIGH. |
| | |
| | 7)1015.3 OPENINGS. OPEN GUARDRAILS |
| | SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| | MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| | SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| | RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| | REJECT THE PASSAGE OF 2" DIAMETER |
| | SPHERE. |
| | |
| | 8) STAIRWELL SHAFT ENCLOSURE: TABLE |
| | 705.1.2. SECOND FLOOR, (BUSINESS OCC) |
| | REQUIRES 1 HR.,MISSING AT FIRST FLOOR & |
| | DOOR 104, 705.2.3. ALSO SEE 1006.1.3.2 |
| | FOR WINDOWS OPENINGS WITHIN 10' OF |
| | STAIRWELL SHAFTS, 3/4 HR OPENING PROTECT |
| | IVES. |
| | |
| | *** 9) PLATFORM # 099 |
| | 11-4.1.2 VERTICAL ACCESSIBILITY, |
| | NOTHING IN THIS CODE SHALL BE CONSTRUED |
| | TO RELIEVE THE OWNER OF ANY BUILDING, |
| | SSTRUCTURE OR FACILITY FROM THE DUTY TO |
| | PROVIDE VERTICAL ACCESSIBILITY TO ALL |
| | LEVELS ABOVE OR BELOW THE OCCUPIAABLE |
| | GRADE LEVEL. |
| | |
| | *** 10) MANEUVERING CLEARENCES AT DOOR |
| | NUMBER 103, 107A, 109,& 114A. |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | *** 11) COMPANION SEATING 11-4.1.6(3) |
| | (F)(I) EACH ACCESSIBLE SEATING AREA |
| | SHALL HAVE PROVISIONS FOR COMPANION SEAT |
| | ING AND SHALL BE LOCATED ON AN ACCESS- |
| | IBLE ROUTE THAT ALSO SERVES AS A MEANS |
| | OF EMERGENCY EGRESS. |
| | |
| | 12) HANDRAILS FOR THE HANDICAPPED RAMP: |
| | TO COMPLY WITH TABLE 1004, 44" CLEAR BE |
| | TWEEN HANDRAILS, ALSO SEE EDGE PROTEC- |
| | TION (***) 11-4.8.8 FOR RAMP. NOTE ALSO |
| | SEE GUARDRAILS IN NOTE# 7 ABOVE. |
| | |
| | ****13) 11-4.4.8.4(3) HANDICAPPED RAMPS |
| | / LANDINGS, IF RAMPS CHANGE DIRECTION AT |
| | LANDINGS, A MIIMUM LANDING SIZE SHALL BE |
| | 60"X60"(INSIDE OF THE HANDRAILS/ GUARD- |
| | RAIL SYSTEM NOT A OVERALL MEASUREMENT! |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |