Plan Review Details - Permit 03052140
Plan Review Stops For Permit 03052140
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-08-25 Cont ID  
Sent By sthyng Date 2003-08-25 Time 12:21 Rev Time 1.50
Received By sthyng Date 2003-08-25 Time 11:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-08-18 Cont ID  
Sent By sthyng Date 2003-08-18 Time 14:47 Rev Time 2.00
Received By sthyng Date 2003-08-18 Time 14:47 Sent To P
Notes
2003-08-18 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)ADDITIONAL FEES DUE; $705.57.
  
 3.)PROVIDE THE RECEIPT FOR THE IMPACT
 FEES.
  
 4.)SEE PREVIOUS LIST #11; THE CATALOG
 REQUIRES 20 NAILS; PLAN STILL SHOWS 16
 (A6 AND A7).
  
 5.)SEE PREVIOUS LIST #13; REFER TO
 FBC705.3 AND FBC2305.2.2.THE
 DRAFTSTOPPING SHOWN DOES NOT DIVIDE THE
 FLOOR/CEILING ASSEMBLY INTO AREAS LESS
 THAN 500 SF.
  
 6.)ROOF ON THE TYPICAL WALL SECTION
 (A8) NOW SHOWS TILE ON 15# PAPER.IS
 THIS CORRECT?
  
 7.)REFER TO PREVIOUS LIST, #16.THE
 BUCK ATTACHMENTS ARE STILL NOT ON THE
 PLAN.PLEASE PROVIDE.
  
 8.)TYPICAL WALL SECTION SHOWS SPRAY
 FOAM INSULATION ON THE TOP CHORD OF THE
 TRUSS; INSULATION WHICH WAS PREVIOUSLY
 SHOWN ON THE BOTTOM CHORD IS NO LONGER
 ON THE DETAIL.FBC13-604.1.ABC.1,
 PRESCRIPTIVE REQUIREMENTS FOR METHOD A,
 REQUIRES R19 INSULATION ON THE CEILING.
  
 9.)PROVIDE FIREBLOCK AT STAIRS,
 FBC2305.1.4(3).
  
 10.) PROVIDE THE TEST REPORT FOR THE
 METAL GLAZED DOORS.ADDITIONAL
 INFORMATION IS REFERRED TO ON THE
 REPORT AS BEING AVAILABLE ON THEIR
 WEBSITE.
  
 11.) THE PLAN SHOWS A 24 EGRESS WINDOW.
 IF YOU ARE INSTALLING A 25 SINGLE HUNG,
 CHANGE THE PLAN TO REFLECT THIS TO
 COMPLY WITH FBC1005.4.
  
 12.) SEE PREVIOUS LIST #19.I AM STILL
 UNCLEAR AS TO WHERE THE IMPACT CASEMENT
 WINDOW IS TO BE INSTALLED.THE WINDOW
 CHANGES MADE WERE FOR FIXED WINDOWS.
 PRODUCT APPROVAL IS FOR CASEMENT IMPACT.
 THERE AREN'T ANY CASEMENT WINDOWS SHOWN
 ON THE PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-07-07 Cont ID  
Sent By pkrauss Date 2003-08-15 Time 14:21 Rev Time 4.00
Received By sthyng Date 2003-07-07 Time 09:36 Sent To  
Notes
2003-07-07 00:00:00*******CORRECTIONS*******
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 4.)THE NUMBERS ON THE N & S PROPERTY
 LINES OF THE SITE PLAN (S1) DO NOT MATCH
 THE SURVEY.
  
 5.)ADDITIONAL FEES DUE; $705.57.
  
 6.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE ORIGINAL RECEIPT ATTACHED TO THE
 APPLICATION.THIS MAY BE DONE BEFORE
 RESUBMITTAL OR AFTER THE PLANS ARE
 APPROVED BUT BEFORE A PERMIT CAN BE
 ISSUED.233-5025
  
 7.)FOUNDATION NOTES, 3A, "THREE FEET"
 SHOULD BE "FIVE FEET" AS PER SOILS
 REPORT.
  
 8.)GENERAL NOTES #22, A2, SPECS R5
 INSULATION FOR THE BLOCK WALLS.THE
 WALL SECTION SHOWS 3.8 (A8).THE ENERGY
 CALC REQUIRES A MINIMUM OF 4.2.
  
 9.)THE SINGLE HUNG WINDOW AT THE TUB
 (A5) MUST COMPLY WITH FBC2405.1 (SAFETY
 GLASS REQUIREMENT).
  
 10.) THE GIRDER CONNECTION, ROOF FRAMING
 NOTES, SPECIFIES A SEMCO ATTACHMENT.
 THEY ARE NO LONGER IN BUSINESS.
  
 11.) THE TYPICAL STRAPS AND BLOCKING
 DETAIL (A6 AND A7) SPECIFIES SIMPSON
 HETAL 20 WITH 16-10D NAILS, MAX UPLIFT
 OF 1890.THE 2003 CATALOG REQUIRES
 20-10DX1 1/2 IN ORDER TO OBTAIN THE
 1890 MAX UPLIFT.
  
 12.)TYPICAL WALL SECTION, SHOW THE
 1 1/2" WATERSTOP, 4" ABOVE GRADE, 12"
 BELOW GRADE (SHOWN ON THE FOOTER DETAIL
 BUT NOT ON THE WALL SECTION).
  
 13.)DRAFTSTOP REQUIRED, FBC 705.3.
  
 14.)THE TYPICAL WALL SECTION SHOWS
 FIBERGLASS SHINGLES; ELEVATION AND
 PRODUCT APPROVALS ARE FOR CEMENT TILE.
  
 15.)USE OF THE BEVELED BUCK (A8) IS IN
 CONFLICT WITH THE PRODUCT APPROVALS.
  
 16.)THE DOOR BUCK DETAIL AND WINDOW
 BUCK DETAIL REFER TO ATTACHMENTS NOT
 ON THE PLAN.
  
 17.)THE STAIR AND GUARD RAILS ARE TO
 COMPLY WITH FBC1608.2.
  
 18.)GIVE STAIR DIMENSIONS TO COMPLY
 WITH FBC1005.3.
  
 19.)PRODUCT APPROVALS FOR AN IMPACT
 CASEMENT WINDOW WERE SUBMITTED.ALL OF
 THE WINDOWS ON THE PLAN ARE SINGLE
 HUNG OR FIXED.PLEASE CLARIFY.
  
 20.)THE WIND EXPOSURE A2 SHOULD BE
 A,B,C OR D; FBC1606.1.8.
  
 21.)PROVIDE TWO COPIES OF PRODUCT
 APPROVALS:
 MULLIONS (PAS SUBMITTED ARE EXPIRED)
 FRENCH DOOR
 SIDELITES
 ENTRY DOOR
 24 EGRESS WINDOW
 GLASS BLOCK
  
 22.)THERE IS A DETAIL ON THE PLAN,
 BUTT GLASS FRAMING.NUMBER THIS DETAIL
 AND GIVE A CORRESPONDING MARK ON THE
 FLOOR PLAN WHERE THIS IS TO BE
 INSTALLED.GIVE A DETAILED SHOP
 DRAWING AND RATIONAL ANALYSIS OR TEST
 DATA ON THE PLAN FBC2406.2.
  
 23.) A8, FIRE RATED ATTIC ACCESS, REFERS
 TO SFBC, A BUILDING CODE NO LONGER USED.
 THE MINIMUM SIZE FOR THE ATTIC ACCESS
 IS 20X36 FBC2309.6.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-12 Cont ID  
Sent By dbaxter Date 2003-08-13 Time 11:23 Rev Time 1.00
Received By btrobaug Date 2003-08-08 Time 08:51 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-06-27 Cont ID  
Sent By alange Date 2003-07-31 Time 14:13 Rev Time 1.00
Received By btrobaug Date 2003-06-27 Time 12:46 Sent To P
Notes
2003-06-27 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLAN AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE SERVICE IS DESIGNED @ 400 AMPS.
 THE GROUNDING ELECTRODE CONDUCTOR SHOULD
 BE 1/0 PER 250-66.
  
 3} THE AMPERE RATINGS FOR THE A/C SYSTEM
 ARE DIFFERENT IN THE LOAD CALCS,THE
 PANEL SCHEDULE,AND ON THE MECHANICAL
 SHEET.PLEASE CORRELATE,ADJUST
 CALCULATION TO REFLECT ACTUAL
 CONDITIONS.
  
 4} THE LOAD CALCULATIONS INDICATE A 200
 AMP SERVICE,THERE ARE 2-200 AMP MAINS ON
 THE PLANS,PLEASE CLARIFY.
  
 5} THE WATER HEATER IS SHOWN AS 6 KW IN
 THE CALCS AND SHOWN ON A 30 AMP BREAKER
 ON THE SCHEDULE,PLEASE CORRELATE.
  
 6} THE PHASE "C" MARKING ON THE SCHEDULE
 SHOULD BE CHANGED TO PHASE "B".
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 8} ADD A RECEPTACLE IN THE "NOOK"
 TO COMPLY WITH 210-52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-08-13 Cont ID  
Sent By dbaxter Date 2003-08-13 Time 11:23 Rev Time 0.00
Received By dbaxter Date 2003-08-13 Time 11:23 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 14:13 Rev Time 0.00
Received By alange Date 2003-07-31 Time 14:12 Sent To E
Notes
2003-07-31 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 10:55 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 10:55 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-25 Cont ID  
Sent By mmclean Date 2003-06-26 Time 08:39 Rev Time 0.00
Received By shernand Date 2003-06-25 Time 11:19 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-11 Cont ID  
Sent By shernand Date 2003-06-11 Time 15:30 Rev Time 0.00
Received By shernand Date 2003-06-11 Time 15:30 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-05-29 Time 15:41 Rev Time 0.00
Received By shernand Date 2003-05-29 Time 15:41 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-15 Cont ID  
Sent By pkrauss Date 2003-08-15 Time 14:21 Rev Time 0.25
Received By pkrauss Date 2003-08-15 Time 14:15 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-06-28 Cont ID  
Sent By dbaxter Date 2003-08-13 Time 16:04 Rev Time 0.50
Received By rregueir Date 2003-06-28 Time 07:48 Sent To B
Notes
2003-06-28 00:00:00FAIL
 ---------------------------------------
 1. DUCT SIZES AND CFMS NOT SHOWN ON
 PLAN
 2. DRYER EXHAUST REQUIRED PER FBC(M)
 SECTION 504.1
 3. EF 2,3,4 NOT SHOWN ON FAN SCHEDULE
 4. NO A/C DROPS SHOWN IN DEN/STUDY
 5. PROTECTION FROM VEHICLE DAMAGE
 REQUIRED FOR AHU-2 PER 303.4
 6. SHOW COMPLIANCE WITH EITHER SEC 402
 OR 403.3 (FRESH AIR REQUIREMENTS)
  
 REVIEWED BY: RONALD J REGUEIRO
 ANY QUESTIONS PLEASE CALL 561-805-6734

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-22 Cont ID  
Sent By kstevens Date 2003-08-22 Time 18:15 Rev Time 0.33
Received By kstevens Date 2003-08-22 Time 18:15 Sent To  
Notes
2003-08-22 00:00:00PASSED/PROVISO - VENT REQUIRED AT LAUND-
 RY SINK

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-28 Cont ID  
Sent By sthyng Date 2003-08-18 Time 15:23 Rev Time 0.33
Received By jleech Date 2003-06-28 Time 06:26 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2003-06-26 Cont ID  
Sent By mmclean Date 2003-06-26 Time 08:39 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2003-06-18 Cont ID  
Sent By shernand Date 2003-06-25 Time 11:20 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-06-18 00:00:006/18/03 DENIED, NEED ALL SETBACKS &
 HOUSE SHOWING ON SURVEY CALL CONTR MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-06-03 Cont ID  
Sent By shernand Date 2003-06-11 Time 15:30 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-06-03 00:00:006/2/03 DENIED, NEED COPY OF 2 SURVEY MM