Plan Review Details - Permit 03052089
Plan Review Stops For Permit 03052089
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By jwitmer Date 2003-07-17 Time 15:44 Rev Time 0.75
Received By jwitmer Date 2003-07-17 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-23 Cont ID  
Sent By jwitmer Date 2003-06-23 Time 13:05 Rev Time 1.00
Received By jwitmer Date 2003-06-23 Time 13:05 Sent To  
Notes
2003-06-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03052089
 ADD: 4075 N HAVERHILL
 CONT: FRAN CON INC
 TEL: (954)444-1189
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE PRODUCT INFORMATION FOR"ALUMATEK
 SLIDING SECURITY GRILL- INSTALLATION
 INFORMATION , WEIGHT PER FOOT ETC.
  
 2) PROVIDE DOCUMENTATION THAT THE ADDITI
 ONAL LOADING IS OK FOR BAR JOIST.
  
 3 WHEN THE SLIDING DOOR IS PARRALLEL TO
 THE BAR JOIST HOW WILL THEY BE SUPPORT-
 ED?
  
 4) WHERE WILL THE HANDICAPPED BE ABLE TO
 RECEIVE SERVICE?
  
 5) SUPPLY INTERIOR ELEVATIONS FOR FIRE
 SPRINKLER CLEARENCES?
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By btrobaug Date 2003-06-04 Time 17:29 Rev Time 0.50
Received By btrobaug Date 2003-06-04 Time 17:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By nmccray Date 2003-07-17 Time 14:29 Rev Time 0.00
Received By nmccray Date 2003-07-17 Time 14:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-11 Cont ID  
Sent By shernand Date 2003-07-10 Time 11:40 Rev Time 0.00
Received By nmccray Date 2003-06-11 Time 14:42 Sent To  
Notes
2003-06-11 00:00:001) HOW HIGH ARE THE STORAGE AND CARTON
 RACKS.
  
 2) HOW DOES THE MODULAR WALL AFFECT THE
 FIRE SPRINKLER COVERAGE.
  
 3) WHAT IS THE INTERIOR WALL AND CEILING
 CLASSIFICATION. ( CLASS A, CLASS B, OR
 CLASS C ).
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-14 Cont ID  
Sent By shernand Date 2003-07-10 Time 11:40 Rev Time 0.00
Received By shernand Date 2003-07-10 Time 11:40 Sent To  
Notes
2003-07-14 00:00:00COMM BOARD #26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-28 Time 16:57 Rev Time 0.00
Received By shernand Date 2003-05-28 Time 16:57 Sent To  
Notes
2003-05-28 00:00:00COMM BOARD #32

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-06-20 Cont ID  
Sent By pkrauss Date 2003-06-20 Time 10:51 Rev Time 0.20
Received By pkrauss Date 2003-06-20 Time 10:50 Sent To  
Notes
2003-06-20 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-07-18 Cont ID  
Sent By kstevens Date 2003-07-18 Time 09:50 Rev Time 0.25
Received By kstevens Date 2003-07-18 Time 09:50 Sent To  
Notes
2003-07-18 00:00:00NO PLUMBING ON PLANS