Plan Review Details - Permit 03052075
Plan Review Stops For Permit 03052075
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-06-11 Cont ID  
Sent By pkrauss Date 2003-06-03 Time 10:03 Rev Time 0.00
Received By nmccray Date 2003-06-11 Time 09:57 Sent To  
Notes
2003-06-11 00:00:00SEPARATE PLAN AND PERMIT APPLICATION ARE
 REQUIRED FOR HOOD SUPPRESSION SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-28 Time 13:40 Rev Time 0.00
Received By shernand Date 2003-05-28 Time 13:40 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-03 Cont ID  
Sent By pkrauss Date 2003-06-02 Time 15:11 Rev Time 0.45
Received By pkrauss Date 2003-06-02 Time 15:10 Sent To FIRE
Notes
2003-06-02 00:00:00PROVISO:
  
 1.PLAN SHEET 2, SECTION VIEW OF HOOD,
 FANS, AND DUCTWORK.ROOF TERMINATION
 INDICATES THE FAN TERMINATING CLOSE TO
 THE PARAPET/ROOF.PLEASE CLARIFY THE
 DISTANCE BETWEEN THE FAN & PARAPET AS
 WELL AS THE MATERIAL.
  
 PLEASE NOTE AS PER 2001 FBC(M)
 506.3.14.2, EXHAUST OUTLETS SHALL BE
 LOCATED NOT LESS THAN 10' HORIZONTALLY
 FROM PARTS OF THE SAME OR CONTIGUOUS
 BUILDINGS.
  
 2.ADDITIONAL PERMIT REQUIRED FOR FIRE
 SUPRESSION.PLEASE PROVIDE PLANS WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.