| 2003-07-02 00:00:00 | BUILDING DENIED |
| | |
| | 1) THE STRUCTURE IS LOCATED IN AN "AO" |
| | FLOOD ZONE AN ELEVATION CERTIFICATE WILL |
| | BE REQUIRED PRIOR TO C.O. |
| | |
| | 2) ONE HOUR FIRE RATED GLASS BLOCK IS |
| | REQUIRED AT THE ZERO LOT LINE. SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND |
| | LISTING INFORMATION. |
| | |
| | 3) THE DOUBLE FRONT DOOR DOES NOT COMPLY |
| | WITH EGRESS REQUIREMENTS. EXIT DOOR MUST |
| | BE OF THE SIDE SWINGING TYPE WITH A MIN. |
| | CLEAR OPENING OF 32". SEE FBC TABLE 1004 |
| | AND SECTIONS 1003.2.3.1 AND 1012.1. |
| | |
| | 4) INDICATE THE LOCATIONS AND MATERIALS |
| | FOR THE DRAFTSTOPPING THAT IS REQUIRED |
| | AT THE FLOOR/CEILING ASSEMBLY. SEE FBC |
| | 2305.2.2. |
| | |
| | 5) DETAIL 2 ON S-5 AND SECTION D-D ON |
| | S-5 FOR THE GIRDER HANGER APPEAR TO BE |
| | IN ERROR. THE CEILING HEIGHT (BOTTOM OF |
| | THE GIRDER) IS 10'AND THE TOP OF THE |
| | BOND BEAM IS AT 10'-8". THE TOP ANCHOR |
| | HOLE IS AT 11', WHICH WILL BE ABOVE THE |
| | BOND BEAM. SHEET S-1 INDICATES FILLED |
| | CELLS BELOW THE BOND BEAM, BUT NOT ABOVE |
| | IT. PLEASE CORRECT. |
| | |
| | 6) SAFETY GLAZING IS REQUIRED IN THE |
| | MASTER BATHROOM WINDOW PER FBC 2405.2. |
| | PLEASE INDICATE THIS ON PLANS. |
| | |
| | 7) WALL SECTION 1 ON A1.02 INCORRECTLY |
| | SPECIFIES THAT THE ROOF SHEATHING IS |
| | NAILED AT 16" O.C. SEE CITY AMENDMENTS |
| | TO FBC TABLE 2306.1. PLEASE CORRECT. |
| | |
| | 8) FBC 1609.4 NO LONGER ALLOWS THE ONE- |
| | THIRD INCREASE ON STEEL CALCULATIONS. |
| | PLEASE REVISE THE CONNECTOR SCHEDULE ON |
| | SHEET S-3. THE VALUES FOR THE SIMPSON |
| | H-16, HETAL20, META16 AND USP RT24T ARE |
| | INCORRECT. SEE THE 2003 USP AND 2002 |
| | SIMPSON HIGH-WIND RESISTANT CONSTRUCTION |
| | CATALOGS. |
| | |
| | 9) SUBMIT A KEY PLAN FOR THE STORM |
| | PANELS. THE INSTALLATION SCHEDULE HAS |
| | SOME ERRORS. THE PANELS ARE SPECIFIED AS |
| | ALL BEING MOUNTED VERTICALLY, HOWEVER, |
| | THE SHUTTER SPANS LISTED INDICATE THEY |
| | ARE MOUNTED HORIZONTALLY. TABLE 5 ON THE |
| | PRODUCT REQUIRE A MINIMUM PANEL LENGTH |
| | OF 46",HOWEVER,SEVERAL PANELS ARE LESS |
| | THAN 46". THE CALK-IN ANCHORS WILL NOT |
| | WORK IN THE HOLLOW BLOCK THAT IS HIGH |
| | LIGHTED ON THE PRODUCT APPROVAL. PLEASE |
| | CORRECT. |
| | |
| | 10) SHEET A1.01 LISTS TOTAL A/C AREA AS |
| | 1888 SQFT, HOWEVER, THE TOTAL FOR THE |
| | 1ST AND 2ND FLOOR A/C AREAS THAT ARE |
| | LISTED TOTALS 1960 SQFT. THE ENERGY CALC |
| | LISTS CONDITIONED AREA AS 1888 SQFT. |
| | PLEASE CORRECT. |
| | |
| | 11) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - THE FIXED GLASS TOMBSTONE (K) AND |
| | ROUND (N) WINDOWS |
| | - HORIZONTAL SLIDING WINDOWS (EXPIRED ON |
| | 3-17-03) |
| | - GARAGE DOOR (DOES NOT MEET REQUIRED |
| | PRESSURES) |
| | - DOUBLE OUTSWING FRONT DOOR (DOES NOT |
| | MEET THE REQUIRED PRESSURES) |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |