| 2003-07-01 00:00:00 | ******CORRECTIONS******* |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE VALUE HAS BEEN ADJUSTED (SEE |
| | ATTACHED); ADDITIONAL FEES OWED, $73.78. |
| | |
| | 2.)THE "NEW COVER PORCH" (NEW PLAN |
| | VIEW AND EXIST PLAN VIEW) SHOULD BE |
| | SHOWN AS AN EXISTING COVERED PORCH. |
| | |
| | 3.)SEPARATE PERMITS REQUIRED. |
| | |
| | 4.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 5.)THE SLIDING GLASS DOORS ARE NOT |
| | LEGIBLE.THE WINDOW PRODUCT APPROVALS ARE |
| | INCOMPLETE.SEE ATTACHED FOR INSTRUCTIONS |
| | AS TO HOW TO OBTAIN DADE COUNTY PRODUCT |
| | APPROVALS ONLINE. |
| | |
| | 6.)THE WINDOW & DOOR ANCHOR DETAIL |
| | CONFLICTS WITH THE PRODUCT APPROVALS, |
| | SEE ATTACHED. |
| | |
| | 7.)THE TYP WOOD FRAME DETAIL SHOWS A 2 |
| | X6 WALL; THIS IS IN CONFLICT WITH OTHER |
| | DETAILS (2X4 WALL FRAMING). |
| | |
| | 8.)THE PLAN REFERS TO "ENGINEER" IN |
| | ITEM #4, GENERAL NOTES.EITHER REMOVE |
| | THE NOTE OR PUT THE ENGINEER'S TITLE |
| | BLOCK AND SEAL ON THE PLAN. |
| | |
| | 9.)THE NOTE "R19 INSULATION" SHOULD |
| | NOT SAY "OWNER OPTION".THIS IS THE |
| | MINIMUM INSULATION REQUIRED AS PER |
| | ENERGY CALC. |
| | |
| | 10.) SHOW THE R5 INSULATION ON THE |
| | MASONRY ADJACENT WALL, EX TYP SECTION, |
| | AS PER THE ENERGY CALC. |
| | |
| | 11.) FIRESTOP REQUIRED, FBC705.3. |
| | |
| | 12.) HOW WILL YOU KEEP WATER FROM |
| | INTRUDING AT THE BASE OF THE WALL? |