Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-23 Cont ID  
Sent By jwitmer Date 2003-06-23 Time 09:40 Rev Time 0.95
Received By jwitmer Date 2003-06-23 Time 09:40 Sent To  
Notes
2003-06-23 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 03051683
 ADDRESS: 1801 S FLAGLER/ 511
 CONT: JOSEPH A JORY
 TELL # (561)818-6472
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 *****PROVISO*****
 1) CONTRACTOR PULLS VALUES OUT OF PERMIT
 VALUE FOR CABINETS, COUNTER TOPS,
 FLOORING & PAINTING/ UNDER $254,000.00
 OF VALUE EXCEPTION TO SS 481 FOR
 LICENSUR(SEALED PLANS).
  
 2) 609 .TYPE I TYPE II BUILDINGS, FIRE
 RETARDANT TREATED WOOD IF USED IN WALLS.
  
 JIM WITMER
 (561)805-6715

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-06-19 Cont ID  
Sent By btrobaug Date 2003-06-23 Time 09:34 Rev Time 2.22
Received By jwitmer Date 2003-06-19 Time 14:31 Sent To  
Notes
2003-06-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051683
 ADD: 1801 S FLAGLER DR # 511
 CONT: JOSEPH A JORY
 TEL: (561)818-6472
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 2) FL S.S. 481.229(C) REQUIRES A DESIGN
 PROFESSIONAL (ARCHETECT OR ENGINEER)
 FOR WORK WITH A VALUE IN EXCESS OF
 $24,999.99.PLANS SHALL REQUIRE SIGNATURE
 AND SEAL OF DESIGN PROFESSIONAL.
  
 3) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) PLAN DO NOT INDICATE THE TYPE OF CONS
 TRUCTION FOR THE BUILDING? AT THE MINI-
 MUM THIS BUILDING ISA TYPE II CONSTRUC-
 TION, 609.1 REQUIRES ANY WOOD FRAMING
 MEMBERS TO BE FIRE RETARDANT TREATED
 WOOD!
  
 5) FL ACCESSIBILITY CODE 11-4.1.6
 ALTERATIONS(B) IF EXISTING ELEMENTS,
 SPACES, OR COMMON AREAS ARE ALTERED,
 THEN EACH SUCH ALTERED AREA SHALL COMPLY
 WITH THE APPLIABLE PROVISIONS .
 ONE BATHROOM DOOR TO COMPLY WITH SECTION
 11-4.22.2 29" CLEAR OPENING.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-11 Cont ID  
Sent By pkrauss Date 2003-06-02 Time 14:34 Rev Time 1.50
Received By sthyng Date 2003-06-10 Time 18:19 Sent To  
Notes
2003-06-11 00:00:00*****CORRECTIONS*******
  
 1.)PLANS WITH AN ARCHITECT'S BLOCK
 ARE REQUIRED TO BE SIGNED, SEALED AND
 DATED FS481.221.
  
 2.)AN ARCHITECT MUST BE LICENSED IN
 FLORIDA FS 481.203, 481.213.
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)TENANT SPACES ARE REQUIRED TO BE
 SEPARATED BY A 1-HR FIRE RESISTANCE FBC
 704.3.1.WHERE PARTITION WALLS
 PERPENDICULAR TO TENANT SEPARATION WALLS
 ARE REMOVED, THE PATCHING OF THE TENANT
 SEPARATION WALL MUST COMPLY WITH THE
 1-HR FIRE RESISTANCE.SHOW ON THE PLAN.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-06-23 Cont ID  
Sent By btrobaug Date 2003-06-19 Time 09:37 Rev Time 1.00
Received By btrobaug Date 2003-06-18 Time 09:02 Sent To B
Notes
2003-06-19 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING COMMENTS:
  
 1} ON THE ISSUE OF THE OLDER PANEL AND
 HAVING PROBLEMS FINDING AN ARC FAULT
 BREAKER,THE RESOLUTION IS TO SET A
 SMALL SUB-PANEL TO ACCOMMODATE THE
 INSTALLATION OF BREAKERS AS NEEDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-05-23 Cont ID  
Sent By shernand Date 2003-06-12 Time 10:08 Rev Time 0.50
Received By btrobaug Date 2003-05-23 Time 11:35 Sent To P
Notes
2003-05-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE ADDRESS THE FOLLOWING COMMENTS
 AND RESUBMIT FOR REVIEW.
  
 1} ADD A RECEPTACLE TO IN THE BEDROOM TO
 COMPLY WITH 210-52(A)(1).
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12.
  
 NOTE: PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER
 OF RECORD. PER FS/FAC 481.221 & 471.025
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 10:08 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 10:08 Sent To E
Notes
2003-06-12 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-22 Cont ID  
Sent By shernand Date 2003-05-22 Time 15:18 Rev Time 0.00
Received By shernand Date 2003-05-22 Time 15:17 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-06-02 Cont ID  
Sent By kstevens Date 2003-05-30 Time 13:10 Rev Time 0.20
Received By pkrauss Date 2003-06-02 Time 14:26 Sent To B
Notes
2003-06-02 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
  
 1.NOTE ON PLAN SHEET 6 INDICATES AHU
 TO BE REPLACED, SOME GRILLES MAY HAVE TO
 BE RELOCATED.
  
 2.PROVIDE THE ABOVE INFORMATION WITH
 MECHANICAL PERMIT APPLICATION.
  
 3.SEE PLUMBING & ELECTRICAL COMMENTS
 ON COMPLIANCE WITH FS/FAC 481.221 &
 471.025.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-06-23 Cont ID  
Sent By kstevens Date 2003-06-23 Time 09:27 Rev Time 0.50
Received By kstevens Date 2003-06-23 Time 09:27 Sent To  
Notes
2003-06-23 00:00:00CONTRACT PRICE BELOW $25.000 - (SEE
 APPLICATION) - CONTRACTOR INDICATED THAT
 THERE IS A 2" TRAP FOR SHOWER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-06-20 Cont ID  
Sent By kstevens Date 2003-06-20 Time 10:36 Rev Time 0.33
Received By kstevens Date 2003-06-20 Time 10:36 Sent To  
Notes
2003-06-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLA. STATUTES
 FBC-2001 AMENDMENTS. ADMIN.
 CODE, CHAPTER 1
  
 1) ALL WORK $25,000 AND OVER REQUIRES A
 DESIGN PROFESSIONAL. PLANS SHALL BE
 SIGNED, SEALED, DATED, AND HAVE A TITLE
 BLOCK THAT HAS THE FOLLOWING INFORMATION
 NAME OF FIRM, ADDRESS, TELEPHONE NUMBER
 AND FIRM LICENSES NUMBER.
 FLA S.S. 481.299(C)
 FLA S.S. 61G15-23.002 OR 61G16.003
 2) ALL INFORMATION, DRAWINGS, SPECIFI-
 CATIONS AND ACCOMPANING DATA SHALL BEAR
 THE NAME AND SIGNATURE OF THE PERSON RE-
 SPONSIBLE FOR THE DESIGN. SEC 104.2.1
 3) SIGNED, SEALED, & DATED LETTER FROM
 AN ENGINEER REQUIRED FOR SHOWER IF 2"
 SANITARY DRAIN IS NOT AVAILABLE. A TITLE
 BLOCK COMPLYING WITH 61G15-23.002(2).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-30 Cont ID  
Sent By btrobaug Date 2003-05-23 Time 11:44 Rev Time 0.33
Received By kstevens Date 2003-05-30 Time 13:05 Sent To M
Notes
2003-05-30 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES.
  
 1) 61G1-16.003 THE PERSONAL SEAL, SIG-
 NATURE AND DATE OF THE ARCHITECT SHALL
 APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO
 BE FILED FOR PUBLIC RECORD.
 2) 61G1-16.004(2) FIRM LICENSE NUMBER
 REQUIRED ON TITLE BLOCK.
 3) 2" DRAIN REQUIRED FOR SHOWER. IF ONLY
 1-1/2" DRAIN IS AVAILABLE, A LETTER FROM
 AN ENGINEER, SIGNED AND SEALED, INDICAT-
 ING THAT THE 1-1/2" DRAIN WILL BE SUFFI-
 CIENT SHALL BE REQUIRED ON THE JOBSITE
 AT TIME OF ROUGH INSPECTION. LETTER
 SHALL BE DATED AND HAVE A TITLE BLOCK
 COMPLYING WITH 61G15-23.002(2).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692