Plan Review Details - Permit 03051671
Plan Review Stops For Permit 03051671
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-06-11 Cont ID  
Sent By sthyng Date 2003-06-11 Time 16:10 Rev Time 1.00
Received By sthyng Date 2003-06-11 Time 16:10 Sent To  
Notes
2003-06-11 00:00:00******PROVISO*******
 SUBMIT PRODUCT APPROVALS FOR
 DOORS, WINDOWS, SHUTTERS, MULLIONS
 AND FRENCH DOORS.ALSO SUBMIT
 HURRICANE SHUTTER SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-10 Cont ID  
Sent By kstevens Date 2003-06-07 Time 16:41 Rev Time 2.00
Received By sthyng Date 2003-06-10 Time 11:52 Sent To  
Notes
2003-06-10 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)ARCHITECT'S SEAL IS REQUIRED TO
 BE DATED.
  
 2.)SEPARATE PERMITS ARE REQUIRED FOR
 ROOF, MECHANICAL, PLUMBING, AND
 ELECTRIC.
  
 3.)ENERGY CALCS REQUIRED FBC 13-101.2.
  
 4.)A NOTICE OF COMMENCEMENT IS
 REQUIRED TO BE FILED WITH THE CLERK OF
 COURTS BEFORE A PERMIT CAN BE ISSUED.
  
 5.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE ORIGINAL RECEIPT ATTACHED TO
 THE APPLICATION.233-5025
  
 6.)ADDITIONAL FEES REQUIRED; $2.16.
  
 7.)FOR WINDOWS BEING REPLACED IN THE
 EXISTING HOUSE, SHOW THE SIZE AND
 TYPE.BEDROOMS ARE REQUIRED TO HAVE
 EMERGENCY EGRESS FBC 1005.4.
  
 8.)IMPACT PROTECTION REQUIRED FOR
 WINDOWS, FBC 1606.1.4.THIS INCLUDES
 THE REPLACEMENT WINDOWS.
  
 9.)SHOW THE 1 1/2" WATERSTOP, 4"
 ABOVE GRADE MIN, AND 12" MIN BELOW
 GRADE (FOUNDATION) ON THE WALL SECTIONS.
 IT IS SHOWN GRAPHICALLY, BUT PLEASE
 GIVE DIMENSIONS.
  
 10.)FIRESTOP REQUIRED, FBC 705.3.
  
 11.)SUBMIT TWO COPIES OF PRODUCT
 APPROVALS:
 WINDOWS (EACH TYPE TO BE INSTALLED)
 IMPACT PROTECTION
 SHINGLES (MAY BE SUBMITTED W/ROOF
 PERMIT APPLICATION)
 NEW DOOR AT LIVING ROOM
 MULLIONS
 FRENCH DOORS
 IF PRODUCT APPROVALS ARE NOT SUBMITTED
 WITH THE OTHER CORRECTIONS, A PERMIT
 MUST BE APPLIED FOR SEPARATELY FOR
 THESE ITEMS.
  
 12.)IF HURRICANE SHUTTERS ARE TO BE
 INSTALLED, PROVIDE A HURRICANE SHUTTER
 SCHEDULE (SEE ATTACHED).

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-22 Cont ID  
Sent By btrobaug Date 2003-10-22 Time 15:11 Rev Time 0.33
Received By btrobaug Date 2003-10-22 Time 14:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-15 Time 10:58 Rev Time 1.00
Received By btrobaug Date 2003-10-09 Time 11:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-06-05 Cont ID  
Sent By shernand Date 2003-05-22 Time 15:32 Rev Time 0.50
Received By btrobaug Date 2003-05-23 Time 14:04 Sent To M
Notes
2003-06-05 00:00:00 
 THERE ARE NO ELECTRICAL PLANS SUBMITTED
 FOR REVIEW.PLEASE NOTE THAT AN
 ELECTRICAL PERMIT IS REQUIRED FOR THIS
 WORK AND PLANS ARE TO BE SUBMITTED PER
 215-5 NEC.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-15 Cont ID  
Sent By csiegber Date 2003-10-15 Time 10:58 Rev Time 0.00
Received By csiegber Date 2003-10-15 Time 10:58 Sent To E
Notes
2003-10-15 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-23 Cont ID  
Sent By mmclean Date 2003-06-04 Time 12:15 Rev Time 0.00
Received By shernand Date 2003-05-22 Time 15:32 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-06-06 Cont ID  
Sent By btrobaug Date 2003-06-05 Time 06:44 Rev Time 0.25
Received By pkrauss Date 2003-06-05 Time 16:52 Sent To P
Notes
2003-06-05 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE EQUIPMENT
 INFORMATION SHOULD ANY HVAC EQUIPMENT
 BE REPLACED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-06-07 Cont ID  
Sent By pkrauss Date 2003-06-06 Time 07:05 Rev Time 0.25
Received By kstevens Date 2003-06-07 Time 16:40 Sent To B
Notes
2003-06-07 00:00:00NO PLUMBING PLANS SUBMITTED

Review Stop Z ZONING
Rev No 1 Status P Date 2003-06-04 Cont ID  
Sent By shernand Date 2003-05-23 Time 14:47 Rev Time 1.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***