Plan Review Details - Permit 03051660
Plan Review Stops For Permit 03051660
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-07-05 Cont ID  
Sent By jwitmer Date 2003-07-05 Time 15:44 Rev Time 0.50
Received By jwitmer Date 2003-07-05 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-06-23 Cont ID  
Sent By nmccray Date 2003-07-02 Time 11:04 Rev Time 1.50
Received By jwitmer Date 2003-06-23 Time 09:07 Sent To  
Notes
2003-06-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03051660
 ADD: 2500 METROCENTER BLVD
 CONT: (PLAN REVIEW)
 CONTACT PERSON: ARCHITECTURAL
 DESIGN COLLABORATE
 TEL: (786)402-5060
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE THE TENNANT ADDRESS FOR THE (3)
 SUITES, TENNANT ADDRESSES CAN NOT BE THE
 SAME AS SITE ADDRESS.
  
 2)TABLE 704.1 OCCUPANCY SEPERATION
 REQUIREMENTS; WHAT TYPE OF OCCUPANCY IS
 LOCATED NEXT SUITE?
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY, AND IF FIRE SPRINK-
 LERED?
  
 5) PROVIDE INFORMATION FOR DOORS WITH
 ELEC LOCKS, PER 1012.6.1 IF FIRE SPRINK-
 LERED IF NOT 1012.7.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-05-21 Cont ID  
Sent By dpalmer Date 2003-05-21 Time 16:46 Rev Time 0.33
Received By dpalmer Date 2003-05-21 Time 16:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-02 Cont ID  
Sent By nmccray Date 2003-07-02 Time 11:04 Rev Time 0.00
Received By nmccray Date 2003-07-02 Time 11:04 Sent To B
Notes
2003-07-02 00:00:00*************PROVISO********************
 PLEASE NOTE CHAPTER 38 AND CHAPTER 7 OF
 NFPA 101 LIFE SAFETY CODE 2000 EDITION
  
 ROUTED TO JIM WITMER
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-07-01 Time 09:54 Rev Time 0.00
Received By mcarsill Date 2003-06-13 Time 08:18 Sent To  
Notes
2003-06-13 00:00:001) IS BUILDING FIRE SPRINKLER PROTECTED.
  
 2) PLEASE EXPLAIN CARD READERS AND HOW
 THEY AFFECT EXITING.
  
 3) NO INTERIOR CLASSIFCATION INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-09-03 Time 11:00 Rev Time 0.00
Received By csiegber Date 2003-09-03 Time 10:59 Sent To P
Notes
2003-09-03 00:00:00TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-07-01 Time 09:54 Rev Time 0.00
Received By shernand Date 2003-07-01 Time 09:54 Sent To FIRE
Notes
2003-07-01 00:00:00FIRE TO FORWARD TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 16:32 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 16:32 Sent To  
Notes
2003-05-21 00:00:00COMM BOARD #53

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-06-23 Cont ID  
Sent By pkrauss Date 2003-06-23 Time 13:17 Rev Time 0.45
Received By pkrauss Date 2003-06-23 Time 13:17 Sent To  
Notes
2003-06-23 00:00:00PROVISO:
  
 PLEASE IDENTIFY ANY EXISTING FIRE
 ON PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-13 Cont ID  
Sent By kstevens Date 2003-09-13 Time 09:24 Rev Time 1.00
Received By kstevens Date 2003-09-13 Time 09:24 Sent To  
Notes
2003-09-13 00:00:00REVISION OK - DELETED TO LAVS IN TOILET
 ROOMS. MINIMUM FACIILITIES MET PER TABLE
 403.1

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-06-14 Cont ID  
Sent By csiegber Date 2003-09-03 Time 11:00 Rev Time 0.33
Received By kstevens Date 2003-06-14 Time 14:54 Sent To  
Notes
2003-06-14 00:00:00PASSED/PROVISO
  
  
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 (CUP DISPENSER)