Plan Review Details - Permit 03051640
Plan Review Stops For Permit 03051640
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-08 Time 11:19 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 11:19 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-21 Cont ID  
Sent By shernand Date 2003-05-21 Time 15:53 Rev Time 0.00
Received By shernand Date 2003-05-21 Time 15:53 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-07-14 Cont ID  
Sent By kstevens Date 2003-07-14 Time 12:56 Rev Time 1.00
Received By kstevens Date 2003-07-12 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-07-08 Time 11:19 Rev Time 1.00
Received By kstevens Date 2003-05-29 Time 16:10 Sent To  
Notes
2003-05-29 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. PLEASE SHOW LENGTH OF
 PIPES FROM DROP TO RANGE/GRILL & FRYER.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 4. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692